Overhead Alloy Reinforced Acar Aluminum Conductor 950mcm

Overhead Alloy Reinforced Acar Aluminum Conductor 950mcm
ACAR
Bare
Stranded
Overhead
Aluminum
Bare
Bare
Round Wire
Power Line
ISO9001
Jinshui
6201 Aluminum Alloy
3
ASTM
Right
Jinshui
Steel-Wood Drum
950MCM
China
7614900000

Product Description

Standard
ASTM B524: Standard Specification for Concentric-lay-stranded Aluminum Conductors, Aluminum Alloy Reinforced (ACAR, 1350/6201)
ASTM B230: Standard Specification for Aluminum 1350-H19 Wire for Electrical Purposes
ASTM B398: Standard Specification for Aluminum-Alloy 6201-T81 and 6201-T83 Wire for Electrical Purposes

Application
This overhead alloy reinforced acar aluminum conductor is used in high voltage overhead power transmission lines. Compared with ACSR conductor of the same diameter, AAAC has smaller linear mass and lower resistivity.

Product Details
1) Conductor: 1350 aluminum, 18/3.62mm
2) Conductivity: 61.2% IACS
3) Mechanical performance of aluminum wire

Diameter Min. Tensile Strength (MPa) Min. Elongation in 250mm (%)
mm Average for a lot Individual test value Average for a lot Individual test value
0.227 to 1.25 170.0 160.0
1.26 to 1.50 200.0 185.0 1.4 1.2
1.51 to 1.75 195.0 185.0 1.5 1.3
1.76 to 2.00 195.0 185.0 1.6 1.4
2.01 to 2.25 190.0 180.0 1.6 1.5
2.26 to 2.50 185.0 175.0 1.6 1.5
2.51 to 2.75 180.0 170.0 1.6 1.5
2.76 to 3.00 175.0 165.0 1.7 1.6
3.01 to 3.50 170.0 160.0 1.8 1.7
3.51 to 3.75 170.0 160.0 1.9 1.8
3.76 to 4.50 165.0 160.0 2.0 1.9
4.51 to 5.25 165.0 160.0 2.1 2.0
5.26 to 6.50 160.0 155.0 2.3 2.2

4) Reinforced core: 6201 aluminum alloy, 19/3.62mm
5) Alloy conductivity: 52.5% IACS
6) Alloy mechanical performance

Diameter (mm) Min Tensile Strength (MPa) Elongation in 250mm
Over Through Average for a lot Individual test %
3.25 4.75 315 305 3.0
1.50 3.25 330 315 3.0

7) Sectional area: 950MCM (481mm2)
8) Cable specification

Sectional Area
(MCM)
Aluminum Wire
(No./mm)
Alloy Wire
(No./mm)
Overall Dia.
(mm)
Aprrox. Weight
(kg/km)
Min. Breaking Load
(kN)
Max. Resist. @ 20ºC
(Ω/km)
950 33/4.07 4/4.07 28.5 1330 79.5 0.061
950 30/4.07 7/4.07 28.5 1330 86.1 0.062
950 24/4.07 13/4.07 28.5 1330 95.0 0.063
950 18/4.07 19/4.07 28.5 1330 106.1 0.065

Packaging details

Polyethylene film packaging
1) Usually used for cables with an overall diameter 10mm and below
2) 100 meters per roll or as per customer’s requirements
3) Packaging dimension: 50cm * 50cm * 20cm or below
4) Weight: 30 kg/roll or below
Steel-wood drum packaging
1) Used for cables with a overall diameter of 10mm and above
2) Drum size: 180cm * 180cm *110cm (different sizes are available according to packaging length)
3) Standard length: as per customer’s requirements.

Customer service
1) Select the right cable as per customer’s requirements
2) Design suitable packaging to guarantee safe and the most economic delivery
3) Provide installation and use guidance
4) Product quality guarantee under the normal use