N2xsey, Power Cable, 8.7/15 Kv, 3/C, Cu/XLPE/Cws/PVC (DIN VDE 0276-620)

N2xsey, Power Cable, 8.7/15 Kv, 3/C, Cu/XLPE/Cws/PVC (DIN VDE 0276-620)
N2XSEY
Construction, Underground, Power Station
Low and Medium Voltage Cable
DC Cable
XLPE
PVC
Round Wire
Bare Copper Wire
ISO, CCC
N2xsey
Boan
DIN VDE 0276-620
8.7/15 Kv
3
25-400 mm2
Copper Wire
DingAn
Heated Steel-Wooden Drum/Steel Drum
SGS
Jiangsu Yixing, China
8544601200

Product Description

N2XSEY, Power Cable, 8.7/15 KV, 3/C, CU/XLPE/CWS/PVC (DIN VDE 0276-620)
Application:

To be laid directly in ground, water, outdoors, indoors and in cable ducts e.g. in industrial and switchboard plants.

Information:
Short circuit temperature at core (max. 5 sec.)
<=300mm² –> 160°C
>300mm² –> 140°C

Standards:
DIN VDE 0276-620
HD 620 S1: 1996
IEC 60502

Technical data:
Nominal voltage Uo/U [V] 8700/15000 volt
Test voltage [V]AC 21000
Temperature range in motion -5°C till +70°C
fixed -20°C till +70°C
Operating temperature short circuit°C 250
Short circuit time max.[sec] 5
Bending radius min.x diamete15
Flammability standard EN 60332-1-2

Cross-Section Area Approx. Conductor Diameter Insulation Thickness Copper Tape Thickness Copper Wire Screen Area Insulation Diameter Sheath Thickness Overall Diameter Approx. Weight
mm² mm mm mm mm² mm mm mm kg/km
25 6.05 4.5 0.1 16 16.5 1.7 46 3500
35 7.10 4.5 0.1 16 17.5 1.7 48 3800
50 8.25 4.5 0.1 16 18.7 1.7 51 4400
70 9.90 4.5 0.1 16 20.3 1.8 55 5300
95 11.7 4.5 0.1 16 22.1 1.8 59 6400
120 13.1 4.5 0.1 16 23.5 1.9 62 7400
150 14.3 4.5 0.1 25 24.7 1.9 65 8500
185 16.3 4.5 0.1 25 26.7 2 69 10000
240 18.7 4.5 0.1 25 29.1 2.1 75 12200
300 20.9 4.5 0.1 25 31.3 2.1 80 14400
400 23.7 4.5 0.1 35 34.1 2.2 87 17500