H07V-U PVC Insulated Solid Wire
Product Description
—PVC Insulated Copper Wire, Earth Wire
Application:
This kind of PVC Insulated conductor H07V-U is used for laying in electric-installation tubes, under and on plaster installation in dry rooms and in closed installation conduits. Direct laying in cable guides is not permitted. Also applied for internal wiring of distribution and switching boxes equipment, same as for protective laying for lighting of nominal voltage up to 1000 V alternating current, or up to 750 V direct current against earth.
Standards:
BS6004
IEC 60227-3
HRN HD 21.3 S3
DIN VDE 0281 part 3
Conductor: | bare copper conductor of class 1 (solid) acc, to IEC 60228 / HD 383 / DIN VDE 0295 | |
Insulation: | PVC compound TI1 acc. to IEC 60227-3 / HD 21.3 S3 / DIN VDE 00281 part 3 | |
Conductor colour | acc. to IEC 60446 i.e. EN 60446 (corresponding to DIN VDE 0293) |
Technical data:
Temperature range: | |
during installation: | +5 °C up to+70 °C |
fixed installed: | -30 °C up to+70 °C |
at short circuit of max. 5 s: | up to 160 °C |
ambient temperature at storage: | up to 40 °C |
Nominal voltage: | Uο/U = 300/500 V |
Test voltage: | 2000 V |
Minimal inner bending radius: | 4D |
Behavior in fire: | IEC 60332-1 |
NOTE:
If you want to know more details about this PVC insulated conductor H07V-U single wire, please visit our website(homepage) because we have no ways to show so much information on this platform. Thank you.
Dimensions – conductor cross-section | Construction of individual conductor | External diameter | Insulation thickness | Conductor resistance at 20 °C | Specific. el. resistance of insulation at 70°C | Cu weight | Cable weight | Packing* |
nominal | min-max. | nominal | max. | min. | approx | |||
mm² | n x mm | mm | mm | Ω/km | MΩkm | kg/km | kg/km | |
1,5 | 1 x 1,38 | 2,6 – 3,2 | 0,7 | 12,10 | 0,011 | 14,4 | 20 | c.100 |
2,5 | 1 x 1,78 | 3,2 – 3,9 | 0,8 | 7,41 | 0,010 | 24,0 | 31 | c.100 |
4 | 1 x 2,26 | 3,6 – 4,4 | 0,8 | 4,61 | 0,0087 | 38,4 | 46 | c.100 |
6 | 1 x 2,70 | 4,1 – 5,0 | 0,8 | 3,08 | 0,0070 | 57,6 | 65 | c.100 |
10 | 1 x 3,5 | 5,3 – 6,4 | 1,0 | 1,83 | 0,0072 | 96,0 | 110 | c.100 |
Packing: C.100 means 100 meters per coil.
- Next: Single or Three Cores Copper XLPE Insulation Unarmoured Power Cable
- Previous: H07V-R PVC Insulated Conductor with Multi Wire Stranded