Cu/XLPE/Cts/PVC/Swa/PVC, Power Cable, 8.7/15 (17.5) Kv, 3/C (IEC 60502-2)

Cu/XLPE/Cts/PVC/Swa/PVC, Power Cable, 8.7/15 (17.5) Kv, 3/C (IEC 60502-2)
CU/XLPE/CTS/PVC/SWA/PVC
Underground, Industrial, Power Station
Low and Medium Voltage Cable
DC Cable
XLPE
PVC
Round Wire
Bare Copper Wire
ISO, CCC, CE
Cu/XLPE/Cts/PVC/Swa/PVC
Boan
8.7/15 (17.5) Kv
2
3
25-400 mm2
Steel Wire Armour
DingAn
Heated Steel-Wooden Drum/Steel Drum
SGS
Jiangsu Yixing, China
8544601200

Product Description

CU/XLPE/CTS/PVC/SWA/PVC, Power Cable, 8.7/15 (17.5) KV, 3/C (IEC 60502-2)
The cable design conforms to IEC 60502 part 2. However if requested, we can separately offer guaranteed technical particulars for cables as per different international specifications or specific customer needs.

CONSTRUCTIONAL FEATURES

Conductor
Copper Conductors upto 1000 sq mm will be circular compacted & stranded and shall comply with IEC-60228 Class 2.

Conductor screen
This will be an extruded layer of semiconducting XLPE applied under simultaneous triple extrusion process over the conductor along with the insulation and the insulation screen.

Insulation
This will be an extruded layer of insulating grade XLPE applied over conductor screen under triple extrusion process along with conductor screen and insulation screen.

Insulation screen
This will be a layer of semiconducting XLPE which will be applied by tripe extrusion process over the insulation.

Metallic screen
It will consist of a layer of copper wires applied helically with overlap over insulation screen. Other combinations of metallic screens as per customer’s requirement can also be provided on request.

Inner Sheath (Bedding)
Extruded layer of PVC or PE is applied over the laid-up cores. PVC is normally of grade ST2 or PE of grade ST7 as per IEC 60502 Part 2.

Armour

The armour is applied over inner sheath. For Single core cables this is of aluminium wires and for multicore cables the armour can be of one among the following options: –
A) Galvanized steel wire.
B) Galvanized steel tape.
C) Galvanised steel strip.
The armour is applied helically over the bedding.

Outer sheath
An extruded layer is applied over the armour in case of armoured cables and over the laid up cores in case of unarmoured cables. Outer sheath material can be either PVC of grade ST2 or PE of grade ST7 as per IEC-60502 Part 2.

Section Conductor diameter Conductor weight Insulation thickness Bedding thickness Armour wire diameter Outer sheath thickness Cable overall diameter Cable weight Minimum bending radius of cable DC resistance of conductor at 20 °C Armour DC resistance at 20 °C Short circuit current rating of armour for 1 second
mm2 mm kg/km mm mm mm mm mm kg/km mm ohm/km ohm/km kA
25 5.9 665 4.5 1.4 2.5 2.6 51.0 4405 612 0.727 0.690 10.02
35 6.9 922 4.5 1.4 2.5 2.7 53.0 4890 636 0.524 0.660 10.48
50 8.1 1242 4.5 1.5 2.5 2.8 56.0 5505 672 0.387 0.620 11.16
70 9.7 1800 4.5 1.5 2.5 2.9 59.5 6455 714 0.268 0.573 12.07
95 11.4 2500 4.5 1.6 2.5 3.0 63.5 7635 762 0.193 0.523 13.21
120 12.9 3152 4.5 1.7 2.5 3.1 67.5 8710 810 0.153 0.490 14.12
150 14.3 3888 4.5 1.7 2.5 3.2 70.5 9785 846 0.124 0.467 14.80
185 16.0 4875 4.5 1.8 3.15 3.4 76.0 12135 912 0.0991 0.354 19.53
240 18.4 6410 4.5 1.9 3.15 3.6 82.0 14460 984 0.0754 0.324 21.33
300 20.6 8039 4.5 2.0 3.15 3.7 87.0 16820 1044 0.0601 0.299 23.14
400 23.3 10301 4.5 2.1 3.15 4.0 94.5 20190 1134 0.0470 0.273 25.31