Copper Conductors with XLPE Insulation and Bare Neutral
More product about Bare NeutralProduct Description
* They are composed of on eor more insulated conductors and one neutral (bare or insulated )
conductor.
* They are required as two ( Duplex) or three (Triplex) or four (Quadru -plex) conductors.
* As per NEMA WC 7/ IEC 60228.
2. Technical Information
Two conductors (Duplex)
Phase | Max. Resitance | Approx. Overall | Approx. | |
Sectional area |
Insulation thickness |
at 20ºC | Diameter | Weight |
mm² | mm | Ω/km | mm | kg/km |
10 | 1.2 | 1.830 | 10.7 | 198 |
16 | 1.2 | 1.150 | 12.8 | 307 |
25 | 1.2 | 0.727 | 15.3 | 469 |
35 | 1.2 | 0.524 | 17.6 | 650 |
50 | 1.5 | 0.387 | 21.2 | 898 |
70 | 1.5 | 0.268 | 24.5 | 1247 |
95 | 1.5 | 0.193 | 28.3 | 1736 |
120 | 1.7 | 0.153 | 31.8 | 2170 |
Three conductors (Triplex)
Phase | Max. Resitance | Approx. Overall | Approx. | |
Sectional area |
Insulation thickness |
at 20ºC | Diameter | Weight |
mm² | mm | Ω/km | mm | kg/km |
10 | 1.2 | 1.830 | 13.7 | 305 |
16 | 1.2 | 1.150 | 15.8 | 471 |
25 | 1.2 | 0.727 | 18.5 | 719 |
35 | 1.2 | 0.524 | 20.7 | 991 |
50 | 1.5 | 0.387 | 25.0 | 1357 |
70 | 1.5 | 0.268 | 28.7 | 1900 |
95 | 1.5 | 0.193 | 32.4 | 2631 |
120 | 1.7 | 0.153 | 36.6 | 3285 |
Four Conductors (Quadruplex)
Phase | Max. Resitance | Approx. Overall | Approx. | |
Sectional area |
Insulation thickness |
at 20ºC | Diameter | Weight |
mm² | mm | Ω/km | mm | kg/km |
10 | 1.2 | 1.830 | 16.3 | 413 |
16 | 1.2 | 1.150 | 18.8 | 634 |
25 | 1.2 | 0.727 | 22.0 | 970 |
35 | 1.2 | 0.524 | 24.6 | 1332 |
50 | 1.5 | 0.387 | 29.8 | 1821 |
70 | 1.5 | 0.268 | 34.2 | 2553 |
95 | 1.5 | 0.193 | 38.6 | 3526 |
120 | 1.7 | 0.153 | 43.5 | 4579 |
3.SERVICING
Purpose:
To establish and maintain a procedure for performing and verifying that our service meets specified requirements and that a suitable method of feedback exists from the customer back to the appropriate individual or department within YIFANG.
Scope:
YIFANG does not currently have any contracts that obligate the company to provide installation or service above and beyond normal product service and delivery. Service activity not specified by contract (such as the treatment of a customer complaint) shall be determined and performed free of charge on a case by case basis. Service concerns will be recorded and will provide a feed-back system as required by the customer.
Similar Or Related
12/20kV 1X25mm2 Aluminum Conductor XLPE Insulation Copper Wire Screened Medium Voltage Power Underground Cable
Read More
20.3/35kV 1X35mm2 Aluminum Conductor XLPE Insulation Copper Wire Screened Medium Voltage Power Underground Cable
Read More
3.5/6kV 1X35mm2 Aluminum Conductor XLPE Insulation Copper Wire Screened Medium Voltage Power Underground Cable
Read More