China Lowest Price 0.6/1kv Al/XLPE ABC Cable (aerial bundle cable) , Power Cable
More product about China ABC CableProduct Description
Application
Used for overhead power transmission and distribution lines of AC rated voltage up to and including 1kV or rated voltage 10kV.
Standard
Rated voltages up to and including 1KV aerial insulated cable implement the standard GB/T 12527, ANSI/ICEA S-76-474, NFC 33029, BS 7870-5, DINVDE0276-626-A1, AS3560-1. Rated voltage 10KV aerial insulated cable implement the standard GB/T 14049.
Application Properties
Rated voltage is up to and including 1KV, 10KV.
The conductor long-term maximum working temperature:PVC and PE insulation should not exceed 70 °C,XLPE insulation should not exceed 90°C.
During short circuit (maximum permanent time is not more than 5 seconds), the maximum temperature of cable conductor : XLPE insulation 250°C, High-density polyethylene insulation 150°C;
When laying the cable, minimum ambient temperature of laying should not be lower than -20°C.
The minimum bending radius:≥20 (D+d)±5%mm, D is the cable overall diameter, d is the conductor diameter.
Product Performance
Conductor DC resistance ( at 20°C ) conform to the stipulation of GB/T 3956-2008.
AC Volage Test:3.5kV,lasting for 5min,without breakdown.
Type and Description
Overhead Insulated Power Cable of rated voltage up to and including 1kV.
Type |
Description |
Main Application |
JKV |
Copper conductor PVC insulated overhead cable with rated voltage 1KV. |
Overhead fixed installation, Lead household line. |
JKLV |
Aluminum conductor PVC insulated overhead cable with rated voltage 1KV. |
|
JKLHV |
Aluminum alloy conductor PVC insulated overhead cable with rated voltage 1KV. |
|
JKY |
Copper conductor PE insulated overhead cable with rated voltage 1KV. |
|
JKLY |
Aluminum conductor PE insulated overhead cable with rated voltage 1KV. |
|
JKLHY |
Aluminum alloy conductor PE insulated overhead cable with rated voltage 1KV. |
|
JKLGY |
ACSR conductor PE insulated overhead cable with rated voltage 1KV. |
|
JKYJ |
Copper conductor XLPE insulated overhead cable with rated voltage 1KV. |
|
JKLYJ |
Aluminum conductor XLPE insulated overhead cable with rated voltage 1KV. |
|
JKLHYJ |
Aluminum alloy conductor XLPE insulated overhead cable with rated voltage 1KV. |
|
JKLGYJ |
ACSR conductor PE insulated overhead cable with rated voltage 1KV. |
Specification
Overhead Insulated Power Cable of Rated Voltages up to and Including 1 kv.
Type |
Core |
Main line core nominal area mm2 |
JKV,JKLV,JKLHV,JKY, JKLY,JKLHY,JKLGY,JKYJ, JKLYJ,JKLHYJ,JKLGYJ |
1 |
10~400 |
2,4 |
10~120 |
|
JKLV,JKLY,JKLYJ |
3+k |
10~120 |
K is the no of neutral core or load bearing line core. According to engineering requirements, to select one to go with the main core. (A) represents steel stranded neutral core. (B) represents aluminium alloy stranded neutral core. |
Triplex Aluminum Service Drop Cable
Code Word | Phase conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+ | |||||||
Size (AWG) | Stranding | Insul. Thick. (mils) | Size (AWG) | Size (kcmil) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
AAAC 6201 ALLOY FULL NEUTRAL MESSENGER | |||||||||||
Minex | 6 | 1 | 45 | 6 | 30.58 | 7 | 1110 | 101 | 101 | 85 | 70 |
Hippa | 6 | 7 | 45 | 6 | 30.58 | 7 | 1110 | 107 | 107 | 85 | 70 |
Prawn | 4 | 1 | 45 | 4 | 48.69 | 7 | 1760 | 152 | 152 | 115 | 90 |
Barnacle | 4 | 7 | 45 | 4 | 48.69 | 7 | 1760 | 160 | 160 | 115 | 90 |
Shrimp | 2 | 7 | 45 | 2 | 77.47 | 7 | 2800 | 243 | 243 | 150 | 120 |
Gammarus | 1/0 | 7 | 60 | 1/0 | 123.3 | 7 | 4460 | 390 | 390 | 205 | 160 |
Leda | 1/0 | 9 | 60 | 1/0 | 123.3 | 7 | 4460 | 384 | 384 | 205 | 160 |
Dunganese | 2/0 | 7 | 60 | 2/0 | 155.4 | 7 | 5390 | 474 | 474 | 235 | 185 |
Cyclops | 2/0 | 11 | 60 | 2/0 | 155.4 | 7 | 5390 | 474 | 474 | 235 | 185 |
Flustra | 3/0 | 17 | 60 | 3/0 | 195.7 | 7 | 6790 | 587 | 587 | 275 | 215 |
Lepas | 4/0 | 18 | 60 | 4/0 | 246.9 | 7 | 8560 | 728 | 728 | 315 | 245 |
*Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Haiotis/XLP).+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.++Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTM B-399 for 6201. |
Code Word | Phase conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+ | |||||||
Size (AWG) | Stranding | Insul. Thick. (mils) | Size (AWG) | Size (kcmil) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
AAAC 6201 ALLOY REDUCED NEUTRAL MESSANGER | |||||||||||
Artemia | 4 | 1 | 45 | 6 | 30.58 | 7 | 1110 | 135 | 135 | 115 | 90 |
Crab | 4 | 7 | 45 | 6 | 30.58 | 7 | 1110 | 143 | 143 | 115 | 90 |
Solaster | 2 | 7 | 45 | 4 | 48.69 | 7 | 1760 | 216 | 216 | 150 | 120 |
Sandcrab | 1/0 | 7 | 60 | 2 | 77.47 | 7 | 2800 | 347 | 347 | 205 | 160 |
Echinus | 1/0 | 9 | 60 | 2 | 77.47 | 7 | 2800 | 341 | 341 | 205 | 160 |
Crayfish | 2/0 | 7/w | 60 mls | 2/0 | — | 7 | 2510 | 485.8 | 455.3 | 235 Amps | 185 Amps |
Sipho | 2/0 | 7/w | 60 mls | 2/0 | — | 7 | 2510 | 485.8 | 455.3 | 235 Amps | 185 Amps |
Fulgar | 3/0 | 17 | 60 | 1/0 | 123.3 | 7 | 4460 | 519 | 519 | 275 | 215 |
Arca | 4/0 | 18 | 60 | 2/0 | 155.4 | 7 | 5390 | 643 | 643 | 315 | 245 |
*Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Haiotis/XLP).+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun.++Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTM B-399 for 6201. |
Code Word | Phase conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+…………… | ||||||
Size (AWG) | Stranding | Insul. Thick. (mils) | Size (AWG) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
AAC NEUTRAL-MESSENGER | ||||||||||
Haiotis | 6 | 7/w | 45 mls | 6 | 7 | 563 | 109.1 | 101.6 | 85 Amps | 70 Amps |
Patella | 6 | 7 | 45 | 6 | 7 | 563 | 103 | 103 | 85 | 70 |
Fusus | 4 | 7/w | 45 mls | 4 | 7 | 881 | 161.8 | 151.7 | 115 Amps | 90 Amps |
Oyster | 4 | 7 | 45 | 4 | 7 | 881 | 154 | 154 | 115 | 90 |
Clam | 2 | 7 | 45 | 2 | 7 | 1350 | 233 | 233 | 150 | 120 |
Murex | 1/0 | 7 | 60 | 1/0 | 7 | 1990 | 374 | 374 | 205 | 160 |
Purpura | 1/0 | 9 | 60 | 1/0 | 7 | 1990 | 368 | 368 | 205 | 160 |
Nassa | 2/0 | 7 | 60 | 2/0 | 7 | 2510 | 462 | 462 | 235 | 185 |
Melita | 3/0 | 17 | 60 | 3/0 | 19 | 3310 | 562 | 562 | 275 | 215 |
Portunus | 4/0 | 18 | 60 | 4/0 | 19 | 4020 | 696 | 696 | 315 | 245 |
Nannynose | 336.4 | 19 | 80 | 336.4 | 19 | 6146 | 1118 | 1118 | 420 | 325 |
* Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Haiotis/XLP).+ Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun. |
Code Word | Phase conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+ | ||||||
Size (AWG) | Stranding | Insul. Thick. (mils) | Size (AWG) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
ASCR NEUTRAL-MESSENGER | ||||||||||
Paludina | 6 | 1 | 45 | 6 | 6/1 | 1190 | 109 | 109 | 85 | 70 |
Voluta | 6 | 7 | 45 | 6 | 6/1 | 1190 | 114 | 114 | 86 | 70 |
Whelk | 4 | 1 | 45 | 4 | 6/1 | 1860 | — | 164 | 115 | 90 |
Periwinkle | 4 | 7 | 45 | 4 | 6/1 | 1860 | 172 | 172 | 115 | 90 |
Conch | 2 | 7 | 60 | 1/0 | 6/1 | 4380 | 420 | 420 | 205 | 160 |
Neritina | 1/0 | 7 | 60 | 1/0 | 6/1 | 4380 | 420 | 420 | 205 | 160 |
Cenia | 1/0 | 9 | 60 | 1/0 | 6/1 | 4380 | 414 | 414 | 205 | 160 |
Runcina | 2/0 | 7 | 60 | 2/0 | 6/1 | 5310 | 520 | 520 | 235 | 185 |
Triton | 2/0 | 11 | 60 | 2/0 | 6/1 | 5310 | 512 | 512 | 235 | 185 |
Mursia | 3/0 | 17 | 60 | 3/0 | 6/1 | 6620 | 635 | 635 | 275 | 215 |
Zuzara | 4/0 | 18 | 60 | 4/0 | 6/1 | 8350 | 789 | 789 | 315 | 245 |
Limpet | 336.4 | 19 | 80 | 336.4 | 18/1 | 8680 | 1167 | 1167 | 420 | 325 |
*Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Haiotis/XLP).+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun. |
Code Word | Phase conductor | Bare Neutral Messenger | Weight Per 1000 ft. (lbs.) | Allowable Ampacity+ | ||||||
Size (AWG) | Stranding | Insul. Thick. (mils) | Size (AWG) | Strand- ing | Rated Strength (lbs.) | XLP | POLY | XLP | POLY | |
ASCR REDUCED NEUTRAL-MESSENGER | ||||||||||
Scallop | 4 | 1 | 45 | 6 | 6/1 | 1190 | — | 142 | 115 | 90 |
Strombus | 4 | 7 | 45 | 6 | 6/1 | 1190 | 151 | 151 | 115 | 90 |
Cockle | 2 | 7 | 45 | 4 | 6/1 | 1190 | 220 | 220 | 150 | 120 |
Janthina | 1/0 | 7 | 60 | 2 | 6/1 | 2853 | 366 | 366 | 205 | 160 |
Ranella | 1/0 | 9 | 60 | 2 | 6/1 | 2853 | 360 | 360 | 205 | 160 |
Cavolinia | 2/0 | 7 | 60 | 1 | 6/1 | 3550 | 453 | 453 | 235 | 185 |
Clio | 2/0 | 11 | 60 | 1 | 6/1 | 3550 | 444 | 444 | 235 | 185 |
Sanddollar | 3/0 | 19/w | 60 mls | 1/0 | 6/1 | 4380 | 565 | 552 | 275 Amps | 215 Amps |
Aega | 3/0 | 17 | 60 | 1/0 | 6/1 | 4380 | 549 | 549 | 275 | 215 |
Cuttlefish | 4/0 | 19/w | 60 mls | 2/0 | 6/1 | 5310 | 699 | 684 | 315 Amps | 245 Amps |
Cerapus | 4/0 | 18 | 60 | 2/0 | 6/1 | 5310 | 681 | 681 | 315 | 245 |
Cowery | 336.4 | 19 | 80 mls | 336/4 | 18/1 | 8680 | 1209 | 1167 | 420 Amps | 325 Amps |
*Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Haiotis/XLP).+Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperature of 40°C; emissivity 0.9; 2 ft./sec. wind in sun. |