Aluminum Conductor Steel Reinforced ACSR Conductor for IEC 61089 Standard
1. Application
ACSR conductors have been widely used in power transmission lines with various voltage levels, because they have such good characteristics as simple structure, convenient installation and maintenance, low cost large transmission capacity. And they are also suitable for laying across rivers valleys and the places where special geographical features exist.
2. Standard
Basic design to IEC 61089.
Code Number |
Stranding&Wire Diameter |
Approx Overall diameter |
Sectional Area |
Approx Weight |
Breaking Load |
DC Resistance |
|||
Al |
Steel |
|
Al |
Steel |
Total |
||||
mm |
mm |
mm |
mm 2 |
mm 2 |
mm 2 |
Kg/km |
KN |
Ohm/km |
|
16 |
6/1.84 |
1/1.84 |
5.53 |
16 |
2.67 |
18.7 |
64.6 |
6.08 |
1.7934 |
25 |
6/2.30 |
1/2.30 |
6.91 |
25 |
4.17 |
29.2 |
100.9 |
9.13 |
1.1478 |
100 |
6/4.61 |
1/4.61 |
13.8 |
100 |
16.7 |
117 |
403.8 |
34.33 |
0.2869 |
125 |
18/2.97 |
1/2.97 |
14.9 |
125 |
6.94 |
132 |
397.9 |
29.17 |
0.2304 |
160 |
18/3.36 |
1/3.36 |
16.8 |
160 |
8.89 |
169 |
509.3 |
36.18 |
0.18 |
250 |
22/3.80 |
7/2.11 |
21.6 |
250 |
24.6 |
275 |
880.6 |
68.72 |
0.1154 |
400 |
54/3.07 |
7/3.07 |
27.6 |
400 |
51.9 |
452 |
1510.3 |
123.04 |
0.0723 |
450 |
54/3.26 |
7/3.26 |
29.3 |
450 |
58.3 |
508 |
1699.1 |
138.42 |
0.0643 |
500 |
54/3.43 |
7/3.43 |
30.9 |
500 |
64.8 |
565 |
1887.9 |
153.8 |
0.0578 |
560 |
54/3.63 |
19/2.18 |
32.7 |
560 |
70.9 |
631 |
2103.4 |
172.59 |
0.0516 |
630 |
54/3.85 |
19/2.31 |
34.7 |
630 |
79.8 |
710 |
2366.3 |
191.77 |
0.0459 |
710 |
54/4.09 |
19/2.45 |
36.8 |
710 |
89.9 |
800 |
2666.8 |
216.12 |
0.0407 |
800 |
72/3.76 |
7/2.51 |
37.6 |
800 |
34.6 |
835 |
2480.2 |
167.41 |
0.0361 |
900 |
72/3.99 |
7/2.66 |
39.9 |
900 |
39.9 |
939 |
2790.2 |
188.33 |
0.0321 |
3. Cable Construction
ACSR conductors are formed by several wires of aluminium and galvanized steel, stranded in concentric layers. The wire or wires which form the core, are made of galvanized steel and the external layer or layers, are of aluminium.
Galvanized steel core consist normally of 1, 7 or 19 wires. The diameters of steel and aluminium wires can be the same, or different.
By varying the relative proportions of aluminium and steel, the required characteristics for any particular application can be reached.
A higher U. T. S. Can be obtained, by increasing steel content, and a higher current carrying capacity by increasing aluminium content.
4. Production Progress
ACSR conductor producing process is drawing stranding and cabling, our factory possess 2 subsidiaries, Zhulin factory is professional bare conductor workshop with 20 production lines.
5. Package
6. About Us
People’s Cable Group Co., Ltd. Was founded in 2007, located in Zhengzhou Gongyi economic development zone. Our company has 2 factories (Zhitian factory and Zhulin factory), occupies total area of more than 300, 000 square meters, with building area 230, 000 square meters.
7. Certification
As first rank of the cable supplier in China, we have obtained CCC, ISO9001, ISO14001, OHSAS certificates, passed the SGS and BV test, and our brand "RMJT" be given China famous brand.
8. Customer Visit
We have a professional sales team with each of them has engaged in this job for 3-10 years, so that we can provide the comprehensive and professional technology for you. With the perfect quality and after sales service, till now we have exported to more than 80 countries, welcome to visit us and establish win-win establish relationship!
9. Contact Us
Sara Liu
TEL: +86-371-55367868
Mobile +86 18339931106
Watap +86 18339931106
- Next: Thhn Wire Copper PVC Insulation Nylon Jacket Electric Building Wire