Aluminum Clad Steel Reinforced ACSR

Aluminum Clad Steel Reinforced ACSR
ACSR
Power Transmission
Low and Medium Voltage Cable
AC Cable
PVC
PVC
Round Wire
Aluminum Conductor Steel Reinforced
IEC DIN
ACSR
JYTOP
RNE DA
Standard Export Drum
DIN48201
Henan, China
8544492100

Product Description

Aluminum Clad Steel Reinforced ACSR

ACSR conductor
ASTM B232 standard Merlin acsr conductor
ACSR,AAC,AAAC,ASCSR&ACAR conductor widely used in power transmission lines with various voltage levels. since they have such good
characteristics as simple structure, convenient installation and maintenance, low cost for the line, large transmission capacity and are also
suitable for laying across rivers and valleys where special geographical teatures exist.

1. Specification:

(1) all aluminium conductor (AAC)
(2) all aluminimum alloy conductor(AAAC)
(3) aluminum conductor steel reinforced (ACSR)
(4) anti-corrosion type ACSR
(5) aluminimum conductor aluminimum clad steel reinforced(ACSR/AW)
(6)rear earth aluminimum conductor steel reinforced(ACSR/RE)
(7)aluminimum conductor aluminimum alloy reinforced(ACAR)

ACSR British Sizes BS215-1
Code
name
Nominal
Al. Area
Stranding and
Wire diameter
Sectional
area of Al.
Total sectional
area
Overall
diameter
Calculated
Breaking Load
Calculate D.C
Resistance at 20
Final modulus of elasticity
mm2 Al. Steel mm2 mm2 mm daN /km hbar
Mole 10 6/1.50 1/1.50 10.52 4.50 43 414 2.706 7900
Squirrel 20 6/2.11 1/2.11 20.94 6.33 85 788 1.368 7900
Gopher 25 6/2.36 1/2.36 26.24 7.08 106 961 1.093 7900
Weasel 30 6/2.59 1/2.59 31.61 7.77 128 1146 0.9077 7900
Fox 35 6/2.79 1/2.79 36.66 8.37 149 1320 0.7822 7900
Ferret 40 6/3.00 1/3.00 42.41 9.00 172 1520 0.6766 7900
Rabbit 50 6/3.35 1/3.35 52.88 10.05 214 1835 0.5426 7900
Mink 60 6/3.66 1/3.66 63.18 10.98 255 2180 0.4545 7900
Shunk 60 12/2.59 7/2.59 63.27 12.95 465 5300 0.4567 10500
Beaver 70 6/3.99 1/3.99 74.82 11.97 302 2570 0.3825 7900
Horse 70 12/2.79 7/2.79 73.37 13.95 538 6120 0.3936 10500
Racoon 75 6/4.10 1/4.10 79.20 12.30 320 2720 0.3622 7900


2. Elative manufacturing standards:
IEC83, IEC1089, 31, B232, BS215, DIN48204

(1). Standard: IEC61089, BS215 part2, ASTM B232, DIN48204, BS EN50182
(2). Specification: ACSR is composed by bare concentric-lay-stranded galvanized steel wire(s) with aluminum wires surrounded by one or
more layers of helically. Greased ACSR can also be supplied.
(3). Application: ACSR is widely used in overhead electric power transmission and distribution lines with various voltage levels

We can supply this conductor according to different recognized standards, such as IEC61089, BS215, BS EN 50182: 2001, STM B231, CSA C49,
DIN480201, JIS C3109, customer special specification also can be satisfied.

Tags: , ,

Similar Or Related





Please enter your first and last name separated by a space (e.g. Jane Miller)




Success! Thanks for Your Request.