AAAC Cable, IEC ASTM BS DIN Standard
Product Description
AAAC Cable (All Aluminum Alloy Conductor) referred to have higher strength but lower conductivity than pure aluminum. Being lighter, alloy conductors can sometimes be used to advantage in place of the more conventional ACSR; Having lower breaking loads than the latter, their use becomes particularly favourable when ice and win loadings are low.
We can supply this conductor according to different recognized standards, such as BS EN50182, IEC61089, ASTM B399DIN 48, customer special specification also can be satisfied.
The data sheets below show the most common standards, British standard and IEC standard.
Aluminium Alloy Type B IEC 104 | |||||||
Characteristics of A2 Conductors IEC 61089 | |||||||
Code number | Area | Number of wires | Diameter | Linear mass | Rated strength | D.C resistance | |
Wire | Cond | ||||||
mm2 | mm | mm | kg/km | kN | Ohm/km | ||
16 | 18.4 | 7 | 1.83 | 5.49 | 50.4 | 5.43 | 1.7896 |
25 | 28.8 | 7 | 2.29 | 6.86 | 78.7 | 8.49 | 1.1453 |
40 | 46 | 7 | 2.89 | 8.68 | 125.9 | 13.58 | 0.7158 |
63 | 72.5 | 7 | 3.63 | 10.9 | 198.3 | 21.39 | 0.4545 |
100 | 115 | 19 | 2.7 | 13.9 | 316.3 | 33.95 | 0.2877 |
125 | 144 | 19 | 3.1 | 15.5 | 395.4 | 42.44 | 0.2302 |
160 | 184 | 19 | 3.51 | 17.6 | 506.1 | 54.32 | 0.1798 |
200 | 230 | 19 | 3.93 | 19.6 | 632.7 | 67.91 | 0.1439 |
250 | 288 | 19 | 4.39 | 22 | 790.8 | 84.88 | 0.1151 |
315 | 363 | 37 | 3.53 | 24.7 | 998.9 | 106.95 | 0.0916 |
400 | 460 | 37 | 3.98 | 27.9 | 1268.4 | 135.81 | 0.0721 |
450 | 518 | 37 | 4.22 | 29.6 | 1426.9 | 152.79 | 0.0641 |
500 | 575 | 37 | 4.45 | 31.2 | 1585.5 | 169.76 | 0.0577 |
560 | 645 | 61 | 3.67 | 33 | 1778.4 | 190.14 | 0.0516 |
630 | 725 | 61 | 3.89 | 35 | 2000.7 | 213.9 | 0.0458 |
710 | 817 | 61 | 4.13 | 37.2 | 2254.8 | 241.07 | 0.0407 |
800 | 921 | 61 | 4.38 | 39.5 | 2540.6 | 271.62 | 0.0361 |
900 | 1036 | 91 | 3.81 | 41.8 | 2861.1 | 305.68 | 0.0321 |
1000 | 1151 | 91 | 4.01 | 44.1 | 3179.0 | 339.53 | 0.0289 |
1120 | 1289 | 91 | 4.25 | 46.7 | 3560.5 | 380.27 | 0.0258 |
1250 | 1439 | 91 | 4.49 | 49.4 | 3973.7 | 424.41 | 0.0231 |
Aluminium Alloy Type A IEC 104 | |||||||
Characteristics of A3 Conductors IEC 61089 | |||||||
Code number | Area | Number of wires | Diameter | Linear mass | Rated strength | D.C resistance | |
Wire | Cond | ||||||
mm2 | mm | mm | kg/km | kN | Ohm/km | ||
16 | 18.6 | 7 | 1.84 | 5.52 | 50.8 | 6.04 | 1.7896 |
25 | 29 | 7 | 2.30 | 6.90 | 79.5 | 9.44 | 1.1453 |
40 | 46.5 | 7 | 2.91 | 8.72 | 127.1 | 15.10 | 0.7158 |
63 | 73.2 | 7 | 3.65 | 10.9 | 200.2 | 23.06 | 0.4545 |
100 | 116 | 19 | 2.79 | 14.0 | 319.3 | 37.76 | 0.2877 |
125 | 145 | 19 | 3.12 | 15.6 | 399.2 | 47.20 | 0.2302 |
160 | 186 | 19 | 3.53 | 17.6 | 511.0 | 58.56 | 0.1798 |
200 | 232 | 19 | 3.95 | 19.7 | 638.7 | 73.20 | 0.1439 |
250 | 290 | 19 | 4.41 | 22.1 | 798.4 | 91.50 | 0.1151 |
315 | 366 | 37 | 3.55 | 24.8 | 1008.4 | 115.29 | 0.0916 |
400 | 465 | 37 | 4.00 | 28.0 | 1280.5 | 146.40 | 0.0721 |
450 | 523 | 37 | 4.24 | 29.7 | 1440.5 | 164.70 | 0.0641 |
500 | 581 | 37 | 4.47 | 31.3 | 1600.6 | 183.00 | 0.0577 |
560 | 651 | 61 | 3.69 | 33.2 | 1795.3 | 204.96 | 0.0516 |
630 | 732 | 61 | 3.91 | 35.2 | 2019.8 | 230.58 | 0.0458 |
710 | 825 | 61 | 4.15 | 37.3 | 2276.2 | 259.86 | 0.0407 |
800 | 930 | 61 | 4.40 | 39.6 | 2564.8 | 292.80 | 0.0361 |
900 | 1046 | 91 | 3.83 | 42.1 | 2888.3 | 329.40 | 0.0321 |
1000 | 1162 | 91 | 4.03 | 44.4 | 3209.3 | 366.00 | 0.0289 |
1120 | 1301 | 91 | 4.27 | 46.9 | 3594.4 | 409.92 | 0.0258 |