Power Cablehalogen-Free, Flame Retardant Tfl492324/0
Product Description
free insulation and sheath. Intended for indoor use.
TFL492324/0, TFL492325/0 and TFL492326/0 has a UV-stabilized sheath and can be
used outdoor as well.
2 Design
Dimensions and other engineering data according to product list table 2.
Conductor: Stranded, tinplated copper wires.
Insulation: Halogen free, thermoplastic. Colours according to product list.
Shield: AL/PET band together with braid of annealed and tinned copper wires.
Sheath: Halogen free, thermoplastic. Colours according to product list.
3 Type
TFL492322 (2×2.5mm2, 2x14AWG)
TFL492323(2x4mm2, 2x12AWG )
TFL492324(2x6mm2, 2x10AWG )
TFL492324/0(2x6mm2, 2x10AWG )
TFL492325/0(2x10mm2, 2x8AWG )
TFL492326/0(2x16mm2, 2x6AWG )
Construction Specificatioion
NO. Item Material Diameter (mm)
1 Inner conductor Stranded Tinned copper wire 3*26*0.29
2 Insulation LSZH(Black/Gray) 3.3*6.6
3 Shield Al-PET+Tinned Copper wire braiding
4 Jacket LSZH(Black/) 9.5*9.5
5 Marking: ********* 2×10 AWG (2×6mm2) Max 600V 90ºC DRY Cable Tray Use (UL) Telephone Central Office Power Cable Sunlight Resistant E335342 YYWW *****M
Electrical Characteristics
NO. Item Value
1 Rated voltage(V) 600
2 Conductor DC Resistance(Ω/km@20ºC) 3.39
3 Test Voltage (1minute,AC.V) 2000
4 Insulation Resistivity(GΩ/m at 20 ºC) 2
5 Inductance(μH/m) 0.4
Mechanical and Environmental Characteristics/
NO. Item Value
1 Operating Temperature -40~+90 ºC
2 Tensile Strength of Insulation& Sheath ≥10 MPa
3 Breaking elongation of Insulation & Sheath ≥100%
4 Sunlight Resistant UL1581.1200-720h
5 Flame Retardancy IEC60332.3
6 Halogen Free IEC 60754-2
7 Smoke Density IEC 61034-1
8 RoHS Compliant
- Next: IEC60502-2 XLPE Insualted Armoured Underground 6/10kv Copper Cable 3X185mm2
- Previous: IEC60502-2 XLPE Insualted Armoured Underground 12/20kv Copper Cable 3X70mm2