0.6/1kv LSZH Sheath Power Cable
Product Description
STANDARD
Basic design to BS 8573:2012
FIRE PERFORMANCE
Flame Retardance (Single Vertical Wire Test) | BS EN 60332-1-2:2004 |
Reduced Fire Propagation (Vertically-mounted bundled wires; cable test) | BS EN 60332-3-24:2009 (cat. C) |
Halogen Free | BS EN 50267-2-1 |
Minimum Smoke Emission | BS EN 61034-2 |
Spark Test | BS EN 62230 |
VOLTAGE RATING
600/1000V
CABLE CONSTRUCTION
Conductor: Annealed copper conductor, strand according to BS EN 60228 class 2.
Insulation: XLPE type GP8 according to BS 7655-1.3. HEPR type GP6 according to BS 7655-1.2, or crosslinked polyolefi n material type EI 5 according to BS EN 50363-5 can be offered as option.
Inner Covering option: The laid up cores may be coverd by an optional extrued inner covering or separating tape. It shall be possible to separate the cores easily.
Outer Sheath: Thermoplastic LSZH type LTS 4 according to BS 7655-6.1.
Outer Sheath option: UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.
COLOUR CODE
Insulation Colour:
Blue, brown black and grey,
Alternatively, green-and-yellow, brown, black, grey
Sheath Colour: Black, other colours can be offered upon request.