All Aluminium Alloy Conductor (AAAC) Power Cable
Product Description
Conductor(AAAC) have been widely used in power transmission lines with various voltage levels, and also used in power lines across great rivers, heavy ice area, and other places special geographical characteristics. The conductor have excellent advantages of high strength, large current carrying capacity and good catenary property as well as wear-resistance, anti-crush and corrosion-proof with simple structure, convenient installation and maintenance, low cost for the line, large transmission capacity.
2. Specifications
Conductor(AAAC) bear conductor meets or exceeds the following ASTM Specifications:
B-398 Aluminum Alloy 6201-T81 Wire for Electrical Purpose.
B-399 Concentrical-Lay-Stranded 6201-T81 Aluminum Alloy Conductors
3. Product Performance
(1). The electrical performance of AAAC is indicated in DCΩ /km(20oC). The resistivity of aluminum alloy wire for stranded wires is:
LHA1: not greater than 32.840nΩ . m
LHA2: not greater than 32.530nΩ . m
(2). The rated tensile strength of AAAC is denoted with the result of total cross-section areas of all aluminum alloy conductors multiplied by min. Tensile strength of corresponding size specified in the standard for aluminum alloy wire.
4. Material Standard
The high-strength aluminum alloy conductor used for AAAC conforms to the standard JB/T 8134-1997(equivalent to IEC 60104: 1987).
Construction of All Aluminum Alloy Conductor
Code Name | Area | Size & Stranding of ACSR with Equal Diameter | No. & Diameter of wires | Overall Diameter | Weight | Nominal Breaking Load | Area | Stranding and Wire Diameter | Approx Overall Diameter | Weight | Nominal Breaking Load | Max.D.C. Resistance at 20ºC | |||
Nominal | Actual | Nominal | Actual | ||||||||||||
MCM | mm2 | AWG or MCM | Al/Steel | mm | mm | kg/km | kN | AWG or MCM | mm² | mm | mm | kg/km | kN | Ω/km | |
Akron | 30.58 | 15.48 | 6 | 6/1 | 7/1.68 | 5.04 | 42.7 | 4.92 | 6 | 13.3 | 7/1.554 | 4.67 | 37 | 4.22 | 2.5199 |
Alton | 48.69 | 24.71 | 4 | 6/1 | 7/2.12 | 6.35 | 68.0 | 7.84 | 4 | 21.15 | 7/1.961 | 5.89 | 58 | 6.71 | 1.5824 |
Ames | 77.47 | 39.22 | 2 | 6/1 | 7/2.67 | 8.02 | 108 | 12.45 | 2 | 33.63 | 7/2.474 | 7.42 | 93 | 10.68 | 0.9942 |
Azusa | 123.3 | 62.38 | 1/0 | 6/1 | 7/3.37 | 10.11 | 172 | 18.97 | 1/0 | 53.48 | 7/3.119 | 9.36 | 148 | 16.97 | 0.6256 |
Anaheim | 155.4 | 78.65 | 2/0 | 6/1 | 7/3.78 | 11.35 | 217 | 23.93 | 2/0 | 67.42 | 7/3.503 | 10.51 | 186 | 20.52 | 0.4959 |
Amherst | 195.7 | 99.22 | 3/0 | 6/1 | 7/4.25 | 12.75 | 273 | 30.18 | 3/0 | 85.03 | 7/3.932 | 11.8 | 234 | 25.86 | 0.3936 |
Alliance | 246.9 | 125.1 | 4/0 | 6/1 | 7/4.77 | 14.31 | 345 | 38.05 | 4/0 | 107.23 | 7/4.417 | 13.26 | 296 | 32.63 | 0.3119 |
Butte | 312.8 | 158.6 | 266.8 | 26/7 | 19/3.26 | 16.30 | 437 | 48.76 | 250 | 126.66 | 19/2.913 | 14.57 | 349 | 38.93 | 0.2642 |
Canton | 394.5 | 199.9 | 336.4 | 26/7 | 19/3.66 | 18.30 | 551 | 58.91 | 300 | 152.1 | 19/3.193 | 15.97 | 419 | 46.77 | 0.2199 |
Cairo | 465.4 | 235.8 | 397.5 | 26/7 | 19/3.98 | 19.88 | 650 | 69.48 | 350 | 177.35 | 19/3.447 | 17.24 | 489 | 52.25 | 0.1887 |
Darien | 559.5 | 283.5 | 477.0 | 26/7 | 19/4.36 | 21.79 | 781 | 83.52 | 400 | 202.71 | 19/3.686 | 18.43 | 559 | 59.74 | 0.165 |
Elgin | 652.4 | 330.6 | 556.5 | 26/7 | 19/4.71 | 23.54 | 911 | 97.42 | 450 | 228 | 19/3.909 | 19.55 | 629 | 67.19 | 0.1467 |
Flint | 740.8 | 375.3 | 636.0 | 26/7 | 37/3.59 | 25.16 | 1035 | 108.21 | 500 | 253.35 | 19/4.120 | 20.6 | 698 | 74.64 | 0.1321 |
Greely | 927.2 | 469.8 | 795.0 | 26/7 | 37/4.02 | 28.14 | 1295 | 135.47 | 550 | 278.6 | 37/3.096 | 21.67 | 768 | 83.8 | 0.1202 |
600 | 303.8 | 37/3.233 | 22.63 | 838 | 91.38 | 0.1102 | |||||||||
650 | 329.25 | 37/3.366 | 23.56 | 908 | 97.94 | 0.1016 | |||||||||
700 | 354.55 | 37/3.493 | 24.45 | 978 | 102.2 | 0.0944 | |||||||||
750 | 380.2 | 37/3.617 | 25.32 | 1049 | 109.6 | 0.088 | |||||||||
800 | 405.15 | 37/3.734 | 26.14 | 1117 | 116.8 | 0.0826 | |||||||||
900 | 456.16 | 37/3.962 | 27.73 | 1258 | 131.5 | 0.0733 | |||||||||
1000 | 506.71 | 37/4.176 | 29.23 | 1399 | 146.1 |
- Next: High Quality Good Price Copper Flat Wire
- Previous: Medium Voltage XLPE Insulated Swa Armoured Power Cable.
Contact us
Similar Or Related
-
Aster Cable 366mm2 37 Strands AAAC Bare Conductor for 90kV HV Substation
-
AAAC Bare Conductor 100mm2 7/4.26mm for Uganda 33kV Distribution Line
-
AAAC Bare Conductor 50mm2 7/3.02mm for Uganda 11kV Distribution Line
-
Aerial Bundled Conductor 70mm2 Hard drawn Aluminum ABC Cable for 400V Distribution Line
-
50mm2;AAAC PVC Covered Hazel Conductor BS 3242 for 11kV Distribution Line