600/1000V 10mm Airdac XLPE Insulated Concentric Service Cables
Product Description
Polyethylene Sheath, SANS 1507, NRS 063 & NRS 017
Conductor: Hard Drawn Copper Conductor – Class 2
Insulation: LV-XLPE
Phase Color Code(SNE): Red, Black & Bare Copper
Phase Color Code (CNE): Red & Bare Copper
Application: Used for house connections , with or without coms wire.
Technical Data
4mm², AIRDAC II CNE Cable
Electrical Properties Cable size: 4mm² Phase Conductor Resistance (Ohm/km) DC @ 20 °C: 4,80 Phase Core Impedance (Z) (Ohm/km): 5,88 Current Rating (A)*: 30 Symmetrical Short Circuit Rating for 1s in kA: 0,572 * Note: – In air, with 30 °C ambient with maximum conductor temperature 90 °C Mechanical Properties Cable size: 4mm² Phase Conductor (No.xOD): 7×0.92mm Nominal Insulation Thickness: 1.0mm Earth size: 4mm² Earth Conductor (No.xOD): 8×0.85mm Nominal Sheath Thickness: 1.4mm Approximate Cable OD: 9.0mm Approximate Cable Mass: 121 kg/km Installation Data (SAG* mm): Span 10(mm) :40 Span 20(mm) :165 Span 30(mm) :370 Span 40(mm) :650 Span 50(mm) :1020 Based on UTS** :1480 MWT*** :370 |
10mm², AIRDAC II CNE Cable
Electrical Properties Cable size: 10mm² Phase Conductor Resistance (Ohm/km) DC @ 20 °C: 1,90 Phase Core Impedance (Z) (Ohm/km): 2,34 Current Rating (A)*: 50 Symmetrical Short Circuit Rating for 1s in kA: 1,431 * Note: – In air, with 30 °C ambient with maximum conductor temperature 90 °C Mechanical Properties Cable size: 10mm² Phase Conductor (No.xOD): 7×1.45mm Nominal Insulation Thickness: 1.0mm Earth size: 10mm² Earth Conductor (No.xOD): 18×0.85mm Nominal Sheath Thickness: 1.4mm Approximate Cable OD: 11.0mm Approximate Cable Mass: 249 kg/km Installation Data (SAG* mm): Span 10(mm) :35 Span 20(mm) :140 Span 30(mm) :310 Span 40(mm) :550 Span 50(mm) :870 Based on UTS** :3600 MWT*** :900 |
Separate Neutral and Earth (SNE) Airdac 600/1000V
Cable Size |
Neutral Size |
Earth Size |
Pilot Cores |
Overall Diameter |
Cable Mass |
Current Rating |
Phase Core Impedance |
mm² | mm² | mm² | mm | mm | kg/m | amps | ohms/km |
10 | 10 | 7.5 | 2 x 0.5 | 12.8 | 0.32 | 90 | 2.34 |
16 | 16 | 10 | 2 x 0.5 | 14.5 | 0.485 | 125 | 1.47 |
Combined Neutral and Earth (CNE) Airdac 600/1000V
Cable Size |
Earth Size |
Overall Diameter |
Cable Mass |
Current Rating |
Phase Core Impedance |
mm² | mm² | mm | kg/m | amps | ohms/km |
4 | 4 | 8.7 | 0.121 | 47 | 5.88 |
10 | 10 | 11 | 0.249 | 86 | 2.34 |
Contact us
Similar Or Related
-
Copper XLPE Copper Wire Neutral 6mm 10mm 16mm Airdac Cable Concentric Cable
-
600V 16mm2 Stranded Aluminum Conductor SEU Concentric Neutral Cable
-
7 Strands Al/PVC/PVC Aluminum Service Entrance Cable Concentric Cables
-
Copper Conductor XLPE Insulated Copper Wire Neutral 6mm 10mm 16mm Airdac Cable Concentric Cable
-
600/1000V 10mm Airdac XLPE Insulated Concentric Service Cables