450/750V Cable Aluminum Conductor PVC Insulated Cable to Bs Standards
Product Description
Application:
Designed for use in the switch control, relay and instrumentation panels of power switchgear and for purposes such as internal connectors in rectifier equipment, motor starters and controllers.
Standards: BS6004
Conductor: Aluminum conductors to BS EN 60228: 2005 (previously BS6360)
Insulation: PVC (Polyvinyl Chloride) Type TI 1 to BS7655
Insulation Colour: Black, Blue, Green/Yellow, Red, Yellow, White, Violet, Brown, Grey, Orange, Pink
Temperature Rating: 0° C to +70° C
Minimum Bending Radius: 6 X overall diameter
Size of conductor | Nominal thickness of insulation (mm) |
Mean overall diameter Upper limit (mm) |
Max. D.C resistance @ 20ºC (Ω/km) |
|
Nominal cross-sectional area mm2 (Single core cable) |
Number and diameter of wires (no./mm) |
|||
2.5 | 1/1.78 | 0.8 | 3.9 | 12.1 |
4 | 1/2.25 | 0.8 | 4.4 | 7.41 |
6 | 1/2.76 | 0.8 | 4.9 | 4.61 |
10 | 7/1.35 | 1.0 | 6.8 | 3.08 |
16 | 7/1.70 | 1.0 | 8.0 | 1.91 |
25 | 7/2.14 | 1.2 | 9.8 | 1.20 |
35 | 7/2.52 | 1.2 | 11.0 | 0.868 |
50 | 19/1.78 | 1.4 | 13.0 | 0.641 |
70 | 19/2.14 | 1.4 | 15.0 | 0.443 |
95 | 19/2.52 | 1.6 | 17.0 | 0.320 |
120 | 37/2.03 | 1.6 | 19.0 | 0.253 |
150 | 37/2.25 | 1.8 | 21.0 | 0.206 |
185 | 37/2.52 | 2.0 | 23.5 | 0.164 |
240 | 61/2.25 | 2.2 | 26.5 | 0.125 |
300 | 61/2.52 | 2.4 | 29.5 | 0.100 |
400 | 61/2.85 | 2.6 | 33.5 | 0.0778 |
500 | 61/3.20 | 2.8 | 37.0 | 0.0605 |
- Next: ACSR Conductor Aluminum Conductor for Overhtead Transmission Line
- Previous: Bare Conductor ACSR Aluminum Conductor Steel Reinforced to DIN48204
Contact us
Similar Or Related
-
10X1.5mm2 Flame Retardant Copper Tape Screen Steel Tape Armored PVC Sheathed Control Cable 0.6/1kV
-
JZ-500 Flexible Copper Control Cable PVC Insulated 300/500V DIN VDE 0285-525
-
0.3/0.5kV 4X4mm2 Copper Wire Braiding PVC Insulation Low Voltage Control Power Cable
-
24X2.5mm2 XLPE Insulated Steel Tape Armoured Control/Instrumentation Cable IEC 60502-1
-
450/750V Cable Aluminum Conductor PVC Insulated Cable to Bs Standards