16mm Power Cable
Product Description
1.Application
1)XLPE insulated power cable has a number of advantages compared with paper insulated and PVC insulate cables.
2)XLPE cable has high electric property, mechanical property, heat aging performance, environmental stress crack resistance, chemical corrosion resistance, and it also has simple structure, convenient operation and it is not restricted by laying in large difference of level.
3) It can be applied in high temperature of 90 degree for a long time.
4)Flame-retardant and non-flame-retardant XLPE cables can be manufactured by three kinds of technological processes: peroxidation, silanization and irradiation.
5)The flame-retardant cable covers three classes of A, B, C and low-smoke low-halogen, low-smoke non-halogen cables.
2.Standard
Our XLPE cable are produced according to IEC 60502, IEC60332, and IEC 60754, even some of our indexes are superior to the above international IEC standards. Meanwhile, we can produce cables according to other standards and can design the XLPE cables with some certain special properties according to customers’ requirements.
XLPE cable can be applied in high temperature for a long time and has bigger current capacity. In the same environment conditions, compared with paper insulated and PVC insulated cables, XLPE cable can lessen the cross section by 1 or 2 grades.
3.Specification
We can make it according to: IEC,BS,VDE,AS/NZS,ICEA,JIS and so on;
1)0.6/1kV, Single Core, Cu or Al/XLPE/PVC Power Cable;
0.6/1kV, Single Core, Cu or Al/XLPE/PVC/AWA/PVC Power Cable
Nominal Cross Section | Approx. Overall Diameter of Conductor | Nominal Thickness of XLPE Insulation | Nominal Thickness of PVC Inner Sheath | Diameter of Al Wires | Nominal Thickness of PVC Outer Sheath | Approx.Overall Diameter | Approx. Weight | |||||
Cu Conductor | Al Conductor | |||||||||||
AWA | AWA | UnAr | AWA | UnAr | AWA | UnAr | AWA | UnAr | AWA | |||
mm2 | mm | mm | mm | mm | mm | mm | mm | mm | kg/km | kg/km | kg/km | kg/km |
1.5 | 1.6 | 0.7 | – | – | 1.4 | – | 5.7 | – | 44 | – | – | – |
2.5 | 2.0 | 0.7 | – | – | 1.4 | – | 6.2 | – | 57 | – | – | – |
4 | 2.6 | 0.7 | – | – | 1.4 | – | 6.7 | – | 74 | – | – | – |
6 | 3.1 | 0.7 | – | – | 1.4 | – | 7.3 | – | 96 | – | – | – |
10 | 3.8 | 0.7 | 1.0 | 0.8 | 1.4 | 1.4 | 7.9 | 12.4 | 134 | 235 | 74 | 175 |
16 | 4.8 | 0.7 | 1.0 | 0.8 | 1.4 | 1.4 | 8.9 | 13.4 | 196 | 307 | 99 | 209 |
25 | 6.0 | 0.9 | 1.0 | 0.8 | 1.4 | 1.4 | 10.6 | 15.1 | 289 | 417 | 139 | 267 |
35 | 7.1 | 0.9 | 1.0 | 0.8 | 1.4 | 1.4 | 11.7 | 16.2 | 382 | 522 | 172 | 309 |
50 | 8.4 | 1.0 | 1.0 | 1.25 | 1.4 | 1.5 | 13.2 | 18.7 | 503 | 710 | 220 | 427 |
70 | 10.0 | 1.1 | 1.0 | 1.25 | 1.4 | 1.5 | 15.0 | 20.5 | 702 | 936 | 293 | 522 |
95 | 11.7 | 1.1 | 1.0 | 1.25 | 1.5 | 1.5 | 16.8 | 22.4 | 950 | 1209 | 384 | 638 |
120 | 13.3 | 1.2 | 1.0 | 1.6 | 1.5 | 1.6 | 18.6 | 25.1 | 1186 | 1531 | 469 | 806 |
150 | 14.5 | 1.4 | 1.0 | 1.6 | 1.5 | 1.6 | 20.4 | 26.7 | 1458 | 1820 | 567 | 923 |
185 | 16.4 | 1.6 | 1.0 | 1.6 | 1.5 | 1.7 | 22.7 | 29.2 | 1810 | 2219 | 698 | 1105 |
240 | 18.7 | 1.7 | 1.0 | 1.6 | 1.6 | 1.8 | 25.4 | 31.9 | 2348 | 2802 | 889 | 1335 |
300 | 20.4 | 1.8 | 1.0 | 1.6 | 1.7 | 1.8 | 27.4 | 33.7 | 2917 | 3393 | 1091 | 1568 |
400 | 23.2 | 2.0 | 1.2 | 2.0 | 1.8 | 2.0 | 30.9 | 38.5 | 3713 | 4377 | 1379 | 2043 |
500 | 26.4 | 2.2 | 1.2 | 2.0 | 1.9 | 2.1 | 34.7 | 42.3 | 4770 | 5512 | 1767 | 2510 |
630 | 30.0 | 2.4 | 1.2 | 2.0 | 2.1 | 2.2 | 39.1 | 46.5 | 6105 | 6914 | 2248 | 3058 |
800 | 34.0 | 2.6 | 1.4 | 2.5 | 2.2 | 2.4 | 43.6 | 52.6 | 7893 | 9008 | 2867 | 3981 |
1000 | 41.4 | 2.8 | 1.4 | 2.5 | 2.3 | 2.5 | 51.6 | 60.8 | 10189 | 11524 | 3690 | 5025 |
2.)0.6/ 1kV ,3C+E Cores, Cu or Al/XLPE/PVC Power Cable;
0.6/ 1kV ,3C+E Cores, Cu or Al/XLPE/PVC/STA/PVC Power Cable;
0.6/ 1kV ,3C+E Cores, Cu or Al/XLPE/PVC/SWA/PVC Power Cable;
Nominal Cross Section | Approx. Overall Diameter of Conductor | Nominal Thickness of XLPE Insulation | Nominal Cross Section of Earth Conductor | Thickness of PVC Inner Sheath | Thickness of Steel Tape or Diameter of Steel Wire | Thickness of PVC Outer Sheath | Approx.Overall Diameter | Approx. Weight Cable | |||||||||||
Cu Conductor | Al Conductor | ||||||||||||||||||
STA | SWA | STA | SWA | UnAr | STA | SWA | UnAr | STA | SWA | kg/km | kg/km | kg/km | kg/km | kg/km | kg/km | ||||
mm2 | mm | mm | mm2 | mm | mm | mm | mm | mm | mm | mm | mm | mm | mm | mm | mm | mm | mm | mm | mm |
1.5 | 1.6 | 0.7 | 1.5 | 1.2 | 1.0 | 0.2 | 0.8 | 1.7 | 1.5 | 1.7 | 11.5 | 14.3 | 16.0 | 156 | 288 | 398 | – | – | – |
2.5 | 2.0 | 0.7 | 2.5 | 1.2 | 1.0 | 0.2 | 0.8 | 1.7 | 1.5 | 1.7 | 12.7 | 15.4 | 17.2 | 211 | 355 | 478 | – | – | – |
4 | 2.6 | 0.7 | 4 | 1.2 | 1.0 | 0.2 | 1.25 | 1.7 | 1.5 | 1.7 | 13.9 | 16.7 | 19.3 | 279 | 438 | 704 | – | – | – |
6 | 3.1 | 0.7 | 6 | 1.2 | 1.0 | 0.2 | 1.25 | 1.7 | 1.5 | 1.7 | 15.4 | 18.1 | 20.8 | 370 | 544 | 831 | – | – | – |
10 | 3.8 | 0.7 | 10 | 1.2 | 1.0 | 0.2 | 1.25 | 1.7 | 1.5 | 1.7 | 17.1 | 19.8 | 22.5 | 527 | 720 | 1036 | 286 | 479 | 795 |
16 | 4.8 | 0.7 | 16 | 1.2 | 1.0 | 0.2 | 1.6 | 1.7 | 1.5 | 1.7 | 19.5 | 22.3 | 25.6 | 778 | 999 | 1509 | 386 | 607 | 1116 |
25 | 6.0 | 0.9 | 16 | 1.2 | 1.0 | 0.2 | 1.6 | 1.7 | 1.5 | 1.7 | 22.6 | 25.4 | 28.7 | 1064 | 1318 | 1890 | 514 | 769 | 1340 |
35 | 7.1 | 0.9 | 16 | 1.2 | 1.0 | 0.2 | 1.6 | 1.7 | 1.5 | 1.7 | 24.6 | 27.4 | 30.7 | 1340 | 1617 | 2241 | 610 | 883 | 1509 |
50 | 8.4 | 1.0 | 25 | 1.2 | 1.0 | 0.2 | 1.6 | 1.7 | 1.6 | 1.8 | 28.4 | 31.4 | 34.7 | 1808 | 2139 | 2870 | 807 | 1134 | 1851 |
70 | 10.0 | 1.1 | 35 | 1.2 | 1.2 | 0.2 | 2.0 | 1.8 | 1.7 | 2.0 | 29.7 | 32.6 | 37.3 | 2446 | 2789 | 3831 | 988 | 1309 | 2280 |
95 | 11.7 | 1.1 | 50 | 1.2 | 1.2 | 0.5 | 2.0 | 2.0 | 1.9 | 2.1 | 33.7 | 38.1 | 41.1 | 3313 | 4049 | 4865 | 1307 | 2000 | 2764 |
120 | 13.3 | 1.2 | 70 | 1.3 | 1.2 | 0.5 | 2.0 | 2.1 | 2.0 | 2.3 | 36.3 | 40.9 | 43.9 | 4223 | 5033 | 5913 | 1631 | 2396 | 3223 |
150 | 14.5 | 1.4 | 70 | 1.3 | 1.4 | 0.5 | 2.5 | 2.2 | 2.1 | 2.4 | 41.3 | 46.0 | 50.2 | 5061 | 5993 | 7415 | 1940 | 2826 | 4190 |
185 | 16.4 | 1.6 | 95 | 1.4 | 1.4 | 0.5 | 2.5 | 2.4 | 2.2 | 2.5 | 46.6 | 51.4 | 55.6 | 6400 | 7446 | 9076 | 2453 | 3454 | 4983 |
240 | 18.7 | 1.7 | 120 | 1.5 | 1.5 | 0.5 | 2.5 | 2.5 | 2.4 | 2.7 | 52.4 | 57.3 | 61.8 | 8291 | 9484 | 11337 | 3137 | 4284 | 6032 |
300 | 20.4 | 1.8 | 150 | 1.5 | 1.5 | 0.5 | 2.5 | 2.7 | 2.6 | 2.8 | 58.0 | 63.0 | 67.1 | 10322 | 11659 | 13632 | 3864 | 5155 | 7058 |
Product Pictures:
Packing and Delivery:
Our Company:
People’s Cable Group Co., Ltd, a professional wires and cables manufacturer for 27 years in China. we mainly produce power cables, control cables, aerial overhead cables(ABC, AAC ACSR and AAAC cables) etc. Standards Supported: ASTM, BS, CSA, IEC, DIN and GB etc.
1. Factory: 160000 square meters, available for OEM;
2. Lead time: 5-7 working days after payment received;
3. Authentication: TUV, OHSAS, CCC, ISO9001:2008;
4. Guarantee: 20 years;
5. QC inspection: Strict inspection before delivery;
After-sales Service:
1. All our cables will be tested well in production and before delivery.
2. Please contact us if any problem, we will respond within 24 hours.
FAQ:
(1)When can I get the price?
We usually quote within 6 hours after we get your inquiry. If you are very urgent to get the price, please call us or tell us in your e-mail so that we will regard your inquiry priority.
(2)How can I get a sample to check your quality?
After price confirmation, you can require for samples to check our quality. Sample is free, but the freight charge should be paid.
(3)How long can I expect to get the sample?
After you pay the freight charge and send us confirmed files, the samples will be ready for delivery in 3-7days. The samples will be sent to you via express and arrive in 3-5 days. You can use your own express account or prepay us if you do not have an account.
(4)What about the lead time for mass production?
Honestly, it depends on the order quantity and the season you place the order. The best record we keep is delivering 10 kilometers cable within a week. Generally speaking, we suggest that you start inquiry two months before the date you would like to get the products at your country.
Contact Information:
Ivan Fan | Sales Manager | People’s Cable Group
Web: www.vwcable.com
Web: www.vwcable.com
If you have any questions, please contact me, I will reply you as soon as possible.
Welcome your inquiry.
- Next: Copper/Aluminum Conductor PE/XLPE/PVC Insulation Electric Power Twisted Overhead Service Drop ABC Cable
- Previous: Overhead Cable XLPE ABC Cable 0.6/1 Kv ABC Cable
Contact us
Similar Or Related
-
10X1.5mm2 Flame Retardant Copper Tape Screen Steel Tape Armored PVC Sheathed Control Cable 0.6/1kV
-
0.3/0.5kV 4X4mm2 Copper Wire Braiding PVC Insulation Low Voltage Control Power Cable
-
24X2.5mm2 XLPE Insulated Steel Tape Armoured Control/Instrumentation Cable IEC 60502-1
-
Low Voltage Single Core Power Cable 1X300 mm2 N2XCH CU/XLPE/CWS/LSF 0.6/1kV