0.6/1kv XLPE Insulated Quadruplex Service Drop Conductor Aluminum Cable

0.6/1kv XLPE Insulated Quadruplex Service Drop Conductor Aluminum Cable
Insulated
Stranded
Overhead
Aluminum
No Jacket
XLPE
Round Wire
Overhead
ISO9001, CE, CCC
Jinshui
JInshui
wooden drum, coil
ASTM, IEC, BS
China
8544492100

Product Description

0.6/1kv XLPE Insulated Quadruplex Service Drop Conductor Aluminum Cable
 

1. Applications

Quadruplex Service Drop-Aluminum Conductors is used to supply 3 phase power, usually from a pole-mounted transformer, to the users service head where connection to the service entrance cable is made. To be used at voltages of 600 volts or less phase and at conductor temperatures not to exceed 75oC for polyethylene insulated conductors or 90 oC for crosslinked polyethylene(XLPE) insulated conductors.

2. Construction

Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or XLPE crosslinked polyethylene. Neutral messengers are concentrically stranded 6201, AAC or ACSR. One conductor is manufactured with an extruded ridge for phase identification.

3. Specifications

Quadruplex service drop cable meets or exceeds the following ASTM specifications;

B-230 Aluminum Wire, 1350-H19 for electrical Purposes.

B-231 Aluminum conductors, Concentric-Lay-Stranded.

B-232 Aluminum conductors, Concentric-Lay-Stranded, Coated Steel Reinforced(ACSR).

B-399 Concentric-Lay-Stranded, 6210-T81-Aluminum

Service Drop cable meets or exceeds all applicable requirements of ICEA-S-76-474

4. The Diagram of Structure:

NOTE: Designated sizes are: ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTM B-399 for 6201.

Conductor temperature of 90 oC XLPE, 75 oC for Poly; Ambient temperatures of 40 oC; Emissivity 0.9; 2ft/sec/wind in sun. To determine current ampacity by conductor size, please consult The National Electric Code, latest edition.

duplex service drop
1, Application
Aerial Bundle Cable is used to supply 120 volt aerial service for temporary serivce at construction sites , outdoor or street lighting . For service at 600 volt or lower at a conductor temperature of 75 degree maximum

2, Construction
Concentric strand or compressed 1350-H19 conductor , polyethylene or crosslinked polyethylene insulation , aerial bundle cable concentric strand AAC , ACSR , or 6201 alloy neutral messenger

3, Standards
ASTM B-230, B-231, B-232 and B-399
ICEA S-76-474

4, Note
The Designed sizes of aerial bundle cable are ACSR 6/1 diameter equivalent resistivity per ASTM-B-399 for 6201Conductor temperature of 75 degree, ambient temperature of 40 degree, emissivity 0.9, 2ft/sec wind in sun
Packaging: available in 500ft coils and in long lengths on reels
The data is approximate and subject to mormal manufacturing tolerances
To determine current ampacity by conductor size, please consult the national electric code, latest edition

triplex service drop
1, Application
Aerial Bundle Cable is used to supply power from the utility’s lines to consumer’s weatherhead, for service at 600 volt or less (phase to phase) at a conductor temperature of 75 degree maximum for polyethylene insulation or 90 degree maximum for crosslinked insulation

2, Construction
Concentric strand or compressed 1350-H19 conductor, polyethylene or crosslinked polyethylene insulation, aerial bundle cable concentric strand AAC, ACSR or 6210 alloy neutral messenger

3, Standards
ASTM B-230, B-231, B-232 and B-339
ICEA S-76-474