U-1000 Arvfv, Power Cable, 0.6/1 Kv, Al/XLPE/PVC/Sta/PVC (NF C 32-322)
More product about Electric CableProduct Description
Application
With a sheath and armor, U-1000 ARVFV is an enhanced version of the cables and U-1000 AR2V. They can
Be used in all industrial installations requiring mechanical protection. These cables can be provided in hard
And SH C1 (NF C 32-323) and HR (resistant to aliphatic hydrocarbons). The design and characteristics of
The materials comply with IEC 60502-1.
Cable Construction
Aluminum conductor
– Strands to IEC 60228 class 2
– XLPE insulation according to NF C 32-321
– Color codes to HD 308 S2(NF C32-321)
– Not fibrous and not hygroscopic filler
– PVC inner jacket
– Two steel tapes helically wraped armour
– Flexible black PVC outer jacket
Technical Characteristics
– Working Voltage: 600/1000 volts
– Test voltage: 1000 volts
– Minimum bending radius: 6 x Ø
– Operation temperature rage: -10 ° C to 60 ° C
– Short-circuit temperature: 250 ° C
– Flame retardant: NF C 32-070 C2
– Insulation resistance: 20 MΩ X km
AWG | Cross Section | Insulation thickness | Amour thickness | Minimum Sheath thickness | Maximum Overall diameter | Approx Cable weight |
mm2 | mm | mm | mm | mm | kg/km | |
8 | 2×10 | 0.7 | 0.2 | 1.4 | 18.5 | 420 |
6 | 2×16 | 0.7 | 0.2 | 1.5 | 20.5 | 540 |
4 | 2×25 | 0.9 | 0.2 | 1.6 | 24.5 | 760 |
2 | 2×35 | 0.9 | 0.2 | 1.7 | 27 | 930 |
8 | 3×10 | 0.7 | 0.2 | 1.5 | 19 | 470 |
6 | 3×16 | 0.7 | 0.2 | 1.5 | 22 | 590 |
4 | 3×25 | 0.9 | 0.2 | 1.6 | 26 | 830 |
2 | 3×35 | 0.9 | 0.2 | 1.7 | 29 | 1030 |
1 | 3×50 | 0.9 | 0.2 | 1.8 | 32.5 | 1290 |
2/0 | 3×70 | 1.1 | 0.2 | 2 | 37.5 | 1710 |
3/0 | 3×95 | 1.1 | 0.5 | 2.1 | 43.5 | 2610 |
4/0 | 3×120 | 1.2 | 0.5 | 2.3 | 47.5 | 3110 |
300MCM | 3×150 | 1.4 | 0.5 | 2.4 | 53 | 3770 |
500MCM | 3×185 | 1.6 | 0.5 | 2.5 | 58 | 4540 |
750MCM | 3×240 | 1.7 | 0.5 | 2.7 | 65.5 | 5620 |
– | 3×300 | 1.8 | 0.5 | 2.9 | 72 | 6830 |
1 | 3×50+35 | 1.0/09 | 0.2 | 1.9 | 34.5 | 1500 |
2/0 | 3×70+50 | 1.1/0.9 | 0.2 | 2 | 40 | 2000 |
3/0 | 3×95+50 | 1.1/1.0 | 0.5 | 2.2 | 45 | 2870 |
4/0 | 3×120+70 | 1.2/1.1 | 0.5 | 2.3 | 50 | 3460 |
300MCM | 3×150+70 | 1.4/1.1 | 0.5 | 2.5 | 54 | 4090 |
500MCM | 3×185+70 | 1.6/1.1 | 0.5 | 2.6 | 59 | 4980 |
750MCM | 3×240+95 | 1.7/1.1 | 0.5 | 2.8 | 66 | 6210 |
8 | 4×10 | 0.7 | 0.2 | 1.5 | 20.5 | 540 |
6 | 4×16 | 0.7 | 0.2 | 1.6 | 23.5 | 700 |
4 | 4×25 | 0.9 | 0.2 | 1.7 | 28 | 1000 |
2 | 4×35 | 0.9 | 0.2 | 1.8 | 31.5 | 1230 |
1 | 4×50 | 1 | 0.2 | 1.9 | 35.5 | 1550 |
2/0 | 4×70 | 1.1 | 0.5 | 2.1 | 42.5 | 2490 |
3/0 | 4×95 | 1.1 | 0.5 | 2.3 | 47.5 | 3120 |
4/0 | 4×120 | 1.2 | 0.5 | 2.4 | 53 | 3780 |
300MCM | 4×150 | 1.4 | 0.5 | 2.6 | 58.5 | 4550 |
500MCM | 4×185 | 1.6 | 0.5 | 2.7 | 64.5 | 5490 |
750MCM | 4×240 | 1.7 | 0.5 | 2.9 | 72.5 | 6860 |
– | 4×300 | 1.8 | 0.5 | 3.1 | 79.5 | 8250 |
8 | 5×10 | 0.7 | 0.2 | 1.6 | 22.5 | 640 |
6 | 5×16 | 0.7 | 0.2 | 1.8 | 26 | 820 |
4 | 5×25 | 0.9 | 0.2 | 1.8 | 31 | 1190 |
Similar Or Related
0.6/1kv Electric Aluminum Conductor PVC/XLPE/PE Insulated PVC Sheathed Low/Medium Voltag Electrical Power Cable
Read More
Fire Resistant Marine Insulated PVC Sheath Jacket Underground Armoured Overhead Electrical Cables XLPE Copper Aluminum Electric Wire Power Cable
Read More
Low Voltage Unarmored Yjv Cable 0.6/1kv
Read More