Single Core Aluminum Conductor XLPE Insulation Covered Line Wire
More product about Aluminum ConductorProduct Description
Construction:
Conductors are aluminum alloy 1350 H19, 6201-T81, or ACSR Conductors, concentrically Stranded and covered for weather proofing with Polyethylene, High Density Polyethylene (HDPE) or Cross-linked Polyethylene (XLPE)
Applications:
Covered line wire is used for primarily for overhead secondary distribution lines. It is not an electrically insulated conductor and is treated as bare conductor when installed.
Standards:
Covered line wire meets or exceeds the following ASTM specifications:
ASTM B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
ASTM B-231 Aluminum Conductors, Concentric-Lay-Stranded.
ASTM B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
ASTM B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors.
Covered line wire meets or exceeds all applicable requirement of ANSI/ ICEA-S-70-547:
Covered Line Wire, ACSR/AAC/AAAC, Aluminum Conductor with XLPE/PE Insulated.
Item # |
Size
|
Strand |
Insulation
|
Outside
|
Rated
|
Weight
|
Weight
|
Ampacity
|
---|---|---|---|---|---|---|---|---|
Walnut | 6 | 6/1 | 30 mls | .258 Inches | 1131 Lbs | 49 Lbs | 47 Lbs | 105 Amps |
Butternut | 4 | 6/1 | 30 mls | .303 Inches | 1170 Lbs | 71.8 Lbs | 70.0 Lbs | 135 Amps |
Hickory | 4 | 7/1 | 30 mls | .309 Inches | 2240 Lbs | 81.6 Lbs | 79.8 Lbs | 135 Amps |
Pignut | 2 | 6/1 | 45 mls | .397 Inches | 2710 Lbs | 118.1 Lbs | 114.8 Lbs | 180 Amps |
Beech | 2 | 7/1 | 45 mls | .405 Inches | 3460 Lbs | 134.1 Lbs | 130.7 Lbs | 180 Amps |
Chestnut | 1 | 6/1 | 45 mls | .434 Inches | 3370 Lbs | 145.5 Lbs | 141.8 Lbs | 210 Amps |
Almond | 1/0 | 6/1 | 60 mls | .506 Inches | 4160 Lbs | 190.4 Lbs | 184.9 Lbs | 235 Amps |
Pecan | 2/0 | 6/1 | 60 mls | .554 Inches | 5040 Lbs | 234.2 Lbs | 227.9 Lbs | 270 Amps |
Filbert | 3/0 | 6/1 | 60 mls | .607 Inches | 6290 Lbs | 288.5 Lbs | 281.4 Lbs | 305 Amps |
Buckeye | 4/0 | 6/1 | 60 mls | .666 Inches | 7930 Lbs | 356.5 Lbs | 348.5 Lbs | 345 Amps |
Hackberry | 266.8 | 18/1 | 60 mls | .711 Inches | 6540 Lbs | 354.8 Lbs | 346.8 Lbs | 435 Amps |
- The code words as given apply to conventional polyethylene line wire.
- For 6201 aluminum conductors diameter equivalent to ACSR construction or 1350 aluminum equivalent.
- Ampacity ratings based on 75 ºC conductor temperature, 25 ºC ambient temperature elevation – sea level. Emissivity 0.91 coefficient of absorption 0.95. Thermal reisitivity of covering -3ºC-Cm2/Watt-CM. Wind speed 2ft/sec in sun.
- To determine correct ampacity by conductor size, please consult the National Electric Code.
Similar Or Related