Primary Ud Cable, Power Cable, 8 Kv, Al/Tr-XLPE/Neutral/PVC (AEIC CS 8/ICEA S-94-649)

Primary Ud Cable, Power Cable, 8 Kv, Al/Tr-XLPE/Neutral/PVC (AEIC CS 8/ICEA S-94-649)

Primary Ud Cable, Power Cable, 8 Kv, Al/Tr-XLPE/Neutral/PVC (AEIC CS 8/ICEA S-94-649)

Primary UD Cable

Low and Medium Voltage Cable

DC Cable

XLPE

PVC

Round Wire

Aluminum 1350

ISO, CCC

Primary Ud Cable

Boan

Aeic CS 8/Icea S-94-649

8 Kv

2-1000 AWG or Kcmil

100%

1/3 or Full

Copper Wire

14/12/10/9 AWG

DingAn or OEM

Fumigated Steel-Wooden Drum/Steel Drum

AEIC/ICEA

Jiangsu Yixing, China

8544492100

Product Description

Primary UD Cable, 8 KV, AL/TR-XLPE/Neutral/PVC (AEIC CS 8/ICEA S-94-649)
Applications:

Predominantly used for primary underground distribution; Suitable for use in wet or dry locations, direct burial, underground duct, and where exposed to sunlight. To be used at 15, 000 volts or less and at conductor temperatures not to exceed 90° C for normal operation.

Specifications:
Primary UD Cable meets or exceeds the following ASTM specifications:
B-3 Soft Annealed Copper Wire.
B-8 Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard or Soft.
B-230 Aluminum, 1350-H19 Wire for Electrical Purposes.
B-231 Aluminum 1350 Conductors, Concentric-Lay-Stranded.
B-609 Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes.
Primary UD Cable is manufactured to the latest edition of the following specifications, and in case of specification conflicts, in the order listed:
ANSI/ICEA S-94-649
AEIC CS-8
RUS U-1

Construction:
The phase conductor is concentrically stranded, compressed soft copper or 1350-H16/26 aluminum alloy. The cable is composed of the conductor with moisture block in the strands, covered by a semi-conducting cross-linked polyethylene strand shield, a tree-retardant cross-linked polyethylene primary insulation, and a semi-conducting cross-linked polyethylene insulation shield. Conductors are available with either 100% or 133% insulation levels. A concentric neutral of bare copper wires and an insulating polyethylene jacket is applied over the insulation shield. The cable is identified by surface print on the jacket and with the lightning bolt symbol for supply cables indented in the jacket. A semi-conducting polyethylene jacket is available upon request.

Maximum Conductor Normal Operation: – 90O C;
Emergency Overload: – 130O C
Temperatures: Short Circuit – 250 C
Application: Medium voltage power cable for single phase underground distribution (UD), including getaway systems in low profile substations.

Size AWG or kcmil Number of Strands Nominal OD Over Insulation in 1/3 Neutral Full Neutral
Number of Wires Size AWG Jacket Thickness mil Approximate Outside Diameter in Approximate Net Weight lb/kft Number of Wires Size AWG Jacket Thickness mil Approximate Outside Diameter in Approximate Net Weight lb/kft
Aluminum 100% Insulation Level (115 mil)
2 7 0.55 6 14 80 0.92 393 10 14 80 0.92 447
1 19 0.59 6 14 80 0.96 424 13 14 80 0.96 518
1/0 19 0.63 6 14 80 1.00 461 16 14 80 1.00 595
2/0 19 0.68 7 14 80 1.05 520 13 12 80 1.08 708
3/0 19 0.73 9 14 80 1.10 600 16 12 80 1.13 825
4/0 19 0.78 11 14 80 1.15 693 13 10 80 1.23 998
250 37 0.84 13 14 80 1.21 778 16 10 80 1.29 1158
350 37 0.94 18 14 80 1.31 983 16 9 80 1.41 1440
500 37 1.07 16 12 80 1.50 1307 29 10 80 1.54 1954
750 61 1.27 15 10 110 1.81 1927
1000 61 1.42 16 9 110 1.98 2419

Tags: , ,

Contact us

 

 

 

Success! Thanks for Your Request.
Error! Please Try Again.