Overhead Transmission ABC Cable to Sans 1418 Size 3X95+54.6
Overhead Transmission ABC Cable to Sans 1418 Size 3X95+54.6
abc 3×95+54.6
Phase Insulated with Bare Neutral
Solid or Stranded
Overhead
Aluminum or Aluminum Alloy or Aluminum & Steel
No
PE or XLPE
Round Wire
Overhead
ISO9001, CE, CCC
Jytop
Black,Red,Yellow,Blue,Brown,Green
16mm 25mm 35mm
0.6/1kv
2,3,4,5
Aluminum or Aluminum Alloy or ACSR
Henan
3X70+54.6
3X95+54.6
JYTOP
Packed in Reels
as per Sans 1418 Standards
Zhengzhou, China
8544492100
Product Description
Aerial Bundle Conductor-ABC(South Africa Standard Sizes)-SANS 1418-1
Table 01
Type of conductor or core | Norminal cross-sectional area mm2 | Nubmer of wires Min. |
Diameter of conductormm | Resistanceat 20ºC Ω/km Max. | Breaking force(N) | Thickness of insulation (mm) | Outer diameter of core(mm) | |||
Min. | Max. | Min. | Average | Min. | Min. | Max. | ||||
Phase or auxiliary or non-strain-bearing netural(aluminium) | +16 | 6 | 4.6 | 5.1 | 1.91 | 2070 | 1.2 | 0.98 | 7.0 | 7.8 |
25 | 6 | 5.8 | 6.3 | 1.2 | 3300 | 1.4 | 1.16 | 8.6 | 9.4 | |
35 | 6 | 6.8 | 7.3 | 0.868 | 4500 | 1.6 | 1.34 | 10.0 | 10.9 | |
50 | 6 | 7.9 | 8.4 | 0.641 | 6200 | 1.6 | 1.34 | 11.1 | 12.0 | |
70 | 12 | 9.7 | 10.2 | 0.443 | 8900 | 1.8 | 1.52 | 13.3 | 14.2 | |
95 | 15 | 11.0 | 12.0 | 0.320 | 12300 | 1.8 | 1.52 | 14.6 | 16.0 | |
120 | 15 | 12.5 | 13.5 | 0.253 | 15600 | 1.8 | 1.52 | 16.3 | 17.5 | |
150 | 15 | 13.9 | 15.0 | 0.206 | 19200 | 1.8 | 1.52 | 17.1 | 18.6 | |
Service connection(aluminium) | 16 | 6 | 4.6 | 5.2 | 1.91 | 2070 | 1.2 | 0.98 | 7.0 | 8.0 |
25 | 6 | 5.6 | 6.5 | 1.2 | 3300 | 1.4 | 1.16 | 8.6 | 9.6 | |
Service connection(copper) | 10 | 6 | – | 4.2 | 1.83 | 3600 | 1.2 | 0.98 | 6.2 | 7.0 |
16 | 6 | – | 5.3 | 1.15 | 5760 | 1.2 | 0.98 | 7.2 | 8.0 | |
25 | 6 | – | 6.6 | 0.727 | 8750 | 1.4 | 1.16 | 8.6 | 9.6 | |
Number and nominal diameter of wires mm |
||||||||||
Supporting core(aluminium alloy) |
54.6 | 7×3.15 | 9.2 | 9.6 | 0.630 | 16600 | 1.6 | 1.34 | 12.3 | 13.0 |
70 | 7×3.50 | 10.0 | 10.4 | 0.500 | 20100 | 1.6 | 1.34 | 12.9 | 13.6 | |
+Auxiliary conductors or cores only |
When a supporting core is specified in a tender invitation,the combinations listed in Table 02 below:
Table 02
1 | 2 |
Nominal cross sectional area of supporting conductor mm2 | Nominal cross-sectional areas of phase conductors mm2 |
54.6 | 25,35,50,70,95 |
70 | 70,95,120 |
95 | 95,120,150 |
—————————————————————————————————————————–
Aerial Bundle Conductor-ABC(South Africa Custimized Size Specification)
Table 03
Type of conductor or core | Norminal cross-sectional area mm2 | Nubmer of wires | Diameter of conductormm | Resistanceat 20ºC Ω/km Max. | Breaking force(N) | Thickness of insulation (mm) | Outer diameter of core(mm) | |||
Min. | Max. | Min. | Average | Min. | Min. | Max. | ||||
Phase or auxiliary or non-strain-bearing netural(aluminium) | 16 | 7/1.65 | 4.6 | 5.1 | 1.91 | 2070 | 1.2 | 0.98 | 7.0 | 7.8 |
25 | 7/2.15 | 5.8 | 6.3 | 1.2 | 3300 | 1.4 | 1.16 | 8.6 | 9.4 | |
35 | 7/2.55 | 6.8 | 7.3 | 0.868 | 4500 | 1.6 | 1.34 | 10.0 | 10.9 | |
50 | 7/2.99 | 7.9 | 8.4 | 0.641 | 6200 | 1.6 | 1.34 | 11.1 | 12.0 | |
70 | 14/2.59 | 9.7 | 10.2 | 0.443 | 8900 | 1.8 | 1.52 | 13.3 | 14.2 | |
95 | 19/2.59 | 11.0 | 12.0 | 0.320 | 12300 | 1.8 | 1.52 | 14.6 | 16.0 | |
120 | 19/2.99 | 12.5 | 13.5 | 0.253 | 15600 | 1.8 | 1.52 | 16.3 | 17.5 | |
150 | 30/2.59 | 13.9 | 15.0 | 0.206 | 19200 | 1.8 | 1.52 | 17.1 | 18.6 | |
Service connection(aluminium) | 16 | 7/1.65 | 4.6 | 5.2 | 1.91 | 2070 | 1.2 | 0.98 | 7.0 | 8.0 |
25 | 7/2.15 | 5.6 | 6.5 | 1.2 | 3300 | 1.4 | 1.16 | 8.6 | 9.6 | |
Service connection(copper) | 10 | 7/1.35 | – | 4.2 | 1.83 | 3600 | 1.2 | 0.98 | 6.2 | 7.0 |
16 | 7/1.69 | – | 5.3 | 1.15 | 5760 | 1.2 | 0.98 | 7.2 | 8.0 | |
25 | 7/2.19 | – | 6.6 | 0.727 | 8750 | 1.4 | 1.16 | 8.6 | 9.6 | |
Supporting core(aluminium alloy) | 16 | 7/1.71 | 5.1 | 5.2 | 2.053 | 5070 | 1.4 | 1.16 | 7.9 | 8.0 |
25 | 7/2.15 | 6.4 | 6.5 | 1.314 | 8000 | 1.4 | 1.16 | 9.2 | 9.3 | |
35 | 7/2.48 | 6.6 | 7.5 | 0.986 | 10300 | 1.6 | 1.34 | 10.7 | 10.8 | |
50 | 7/2.89 | 7.7 | 8.4 | 0.720 | 14200 | 1.6 | 1.34 | 11.9 | 12.0 | |
54.6 | 7/3.15 | 9.2 | 9.6 | 0.630 | 16600 | 1.6 | 1.34 | 12.3 | 13.0 | |
70 | 7/3.50 | 10.0 | 10.4 | 0.500 | 20100 | 1.6 | 1.34 | 12.9 | 13.6 |