N2xs2y, 6/10 Kv, Power Cable, 1/C, Cu/XLPE/Cws/PE (HD 620 10C/VDE 0276-620)

N2xs2y, 6/10 Kv, Power Cable, 1/C, Cu/XLPE/Cws/PE (HD 620 10C/VDE 0276-620)
N2XS2Y
Construction, Industrial, Power Station
Low and Medium Voltage Cable
DC Cable
XLPE
PE
Round Wire
Bare Copper Wire
ISO, CCC
N2xs2y
Boan
HD 620 10c/VDE 0276-620
6/10 Ky
1
35-500 mm2
Copper Wire
DingAn
Fumigated Steel-Wooden Drum/Steel Drum
SGS
Jiangsu Yixing, China
8544601200

Product Description

N2XS2Y, 6/10 KV, 1/C, CU/XLPE/CWS/PE (HD 620 10C/VDE 0276-620)
Application:
To be laid directly in ground, outdoors, indoors and in cable ducts.

Standards:
DIN VDE 0276-620
HD 620 S1: 1996
DIN EN 60228 class 2 (construction)

Technical data:
Test voltage 21 / 5 min.
Temperature range in motion -20°C till +90°C
fixed -20°C till +90°C
Operating temperature short circuit °C 250
Short circuit time max. [sec] 5
Bending radius min. x diameter 15
Flammability standard EN 60332-1-2

Number of cores and cross-section Shape of conductor Conductor diameter (approx.) Nominal insulation thickness Diameter over insulation (approx.) Nominal thickness sheath Outer diameter (approx.) Bending radius (min.) Cable mass (approx.)
mm2 mm mm mm mm mm mm kg/km
1×35/16 RM 7.2 3.4 15.3 2.5 24 360 803
1×50/16 RM 8.2 3.4 16.3 2.5 25 375 928
1×70/16 RM 9.8 3.4 17.9 2.5 26 390 1154
1×95/16 RM 11.3 3.4 19.4 2.5 28 420 1410
1×120/16 RM 12.8 3.4 20.9 2.5 30 450 1682
1×150/25 RM 14.2 3.4 22.3 2.5 31 465 2025
1×185/25 RM 15.8 3.4 23.9 2.5 32 480 2383
1×240/25 RM 18.3 3.4 26.4 2.5 35 525 2965
1×300/25 RM 20.7 3.4 28.8 2.5 37 555 3624
1×400/35 RM 23.3 3.4 31.4 2.5 40 600 4574
1×500/35 RM 26.5 3.4 34.6 2.5 43 645 5597