Mv-90, Power Cable, 8 Kv, 1/C, Cu/XLPE/Cws/PVC (ICEA S-93-639/NEMA WC74/UL 1072)

Mv-90, Power Cable, 8 Kv, 1/C, Cu/XLPE/Cws/PVC (ICEA S-93-639/NEMA WC74/UL 1072)

Mv-90, Power Cable, 8 Kv, 1/C, Cu/XLPE/Cws/PVC (ICEA S-93-639/NEMA WC74/UL 1072)

MV-90

Construction, Underground, Industrial, Power Station

Low and Medium Voltage Cable

DC Cable

XLPE

PVC

Round Wire

Bare Copper Wire

ISO, CCC

Mv-90

Boan

8 Kv

1

6 AWG-1000 Mcm

B

100% or 133%

DingAn

Heated Steel-Wooden Drum/Steel Drum

SGS

Jiangsu Yixing, China

8544601200

Product Description

MV-90, Power Cable, 8 KV, 1/C, Cu/XLPE/CWS/PVC (ICEA S-93-639/NEMA WC74/UL 1072)

Features
UL Listed as MV-90. Rated as Sunlight Resistance. Oil Resistance I jacket. True Triple extrusion system and
closed handling raw materials system, to eliminate any contact with ambient, until extrusion process ends.

Application

Primary power and distribution circuits in industrial and commercial installations, power circuits in generating plants where line to ground fault current are within shield capabilities. May be used in wet or dry
locations, installed in raceways, duct, and open air, aerially or directly buried as permitted by NEC.

Standards

UL 1072: Medium Voltage Power Cables.
ICEA S-93-639/NEMA WC74: 5 kV – 46 kV Shielded Power Cables.
ICEA S-97-682: Standard for Utility Shielded Power Cables Rated 5 kV – 46 kV.
AEIC CS8: Specification for Extruded Dielectric, Shielded Power Cables Rated 5 kV – 46 kV.

Specifications

Maximum operating voltage: 5 kV to 35 kV 100% and 133% IL
Maximum conductor operation temperatures: Wet and dry locations: Normal: 90 °C, Emergency: 130 °C, Short Circuit: 250 °C

Engineering Information
1. Conductor: Soft annealed uncoated copper compacted Class B per ASTM B496 or hard drawn Aluminum-1350 compacted Class B per ASTM B400. On request, strand filled or compressed strand. Sizes: 8 AWG (6 AWG Aluminum) up to 1000 kcmil.
2. Conductor Shield: Semi conducting cross-linked polyethylene (XLPE).
3. Insulation: Thermoset crosslinked polyethylene (XLPE). On request, TR-XLPE.
4. Insulation Shield: Semi conducting cross-linked polyethylene (XLPE).
5. Metallic Shield: Solid soft annealed uncoated copper wires per ASTM B3, helically applied and uniformly spaced.
6. Binder Tape: A suitable tape, as required.
7. Jacket: Black sunlight resistance and flame retardant polyvinyl chloride (PVC) compound.

100% Insulation Levels (115 mil) 133% Insulation Levels (140 mil)
Size Number of Strands Conductor Nominal Diameter Over Insulation Jacket Thickness Approximate Outside Diameter Approximate Net Weight Diameter Over Insulation Jacket Thickness Approximate Outside Diameter Approximate Net Weight
Copper Aluminum Copper Aluminum
AWG of kcmil in in mil in lb/kft in mil in lb/kft
6 7 0.17 0.43 60 0.68 257 200 0.48 60 0.73 280 224
4 7 0.21 0.48 60 0.73 321 231 0.53 60 0.78 345 256
2 7 0.27 0.53 60 0.78 422 279 0.58 80 0.87 482 339
1 19 0.30 0.56 60 0.81 485 305 0.61 80 0.90 548 368
1/0 19 0.34 0.6 80 0.89 601 374 0.65 80 0.94 631 405
2/0 19 0.38 0.64 80 0.93 703 416 0.69 80 0.98 734 448
3/0 19 0.42 0.69 80 0.98 829 469 0.74 80 1.03 863 502
4/0 19 0.48 0.74 80 1.03 986 532 0.79 80 1.08 1021 566
250 37 0.52 0.8 80 1.08 1136 598 0.85 80 1.13 1172 635
300 37 0.57 0.85 80 1.13 1310 666 0.90 80 1.18 1349 704
350 37 0.62 0.89 80 1.18 1485 732 0.94 80 1.23 1524 771
400 37 0.66 0.93 80 1.22 1657 797 0.98 80 1.27 1698 838
500 37 0.74 1.01 80 1.32 2021 946 1.06 80 1.37 2066 990
600 61 0.81 1.10 80 1.41 2376 1085 1.15 80 1.46 2423 1132
750 61 0.91 1.19 80 1.5 2880 1267 1.24 80 1.55 2930 1317
1000 61 1.06 1.35 80 1.66 3718 1568 1.40 110 1.77 3876 1726