Mv-90, Power Cable, 5 Kv, 3/C, Cu/XLPE/Cts/PVC (ICEA S-93-639/NEMA WC71/UL 1072)

Mv-90, Power Cable, 5 Kv, 3/C, Cu/XLPE/Cts/PVC (ICEA S-93-639/NEMA WC71/UL 1072)
MV-90
Construction, Underground, Industrial, Power Station
Low and Medium Voltage Cable
DC Cable
XLPE
PVC
Round Wire
Bare Copper Wire
ISO, CCC
Mv-90
Boan
5 Kv
3
8 AWG-1000 Mcm
B
Copper Tape
DingAn
Heated Steel-Wooden Drum/Steel Drum
SGS
Jiangsu Yixing, China
8544601200

Product Description

MV-90, Power Cable, 5 KV, 3/C, Cu/XLPE/CTS/PVC (ICEA S-93-639/NEMA WC71/UL 1072)

Features

UL Listed as MV-90. Rated as Sunlight Resistance for CT use, 1/0 AWG and larger. Oil Resistance I jacket. True Triple extrusion system and closed handling raw materials system, to eliminate any contact with ambient, until extrusion process ends.

Application

Primary power and distribution circuits in industrial and commercial installations, power circuits in generating plants where line to ground fault current are within shield capabilities. May be used in wet or dry locations, installed in raceways, duct, and open air, aerially or directly buried where permitted by NEC.

Standards

UL 1072: Medium Voltage Power Cables.
ICEA S-93-639/NEMA WC74: 5 kV – 46 kV Shielded Power Cables.
ICEA S-97-682: Standard for Utility Shielded Power Cables Rated 5 kV- 46 kV.
AEIC CS8: Specification for Extruded Dielectric, Shielded Power Cables Rated 5 kV – 46 kV.

Specifications

Maximum operating voltage: 5 kV to 35 kV 100% and 133% IL
Maximum conductor operation temperatures:
Wet and dry locations: Normal: 90 °C, Emergency: 130 °C, Short Circuit: 250 °C

Engineering Information
1. Conductor: Soft annealed uncoated copper compacted Class B per ASTM B496 or hard drawn Aluminum-1350 compacted Class B per ASTM B400.
2. Conductor Shield: Semi conducting cross-linked polyethylene (XLPE).
3. Insulation: Thermoset crosslinked polyethylene (XLPE).
4. Insulation Shield: Semi conducting cross-linked polyethylene (XLPE).
5. Metallic Shield: Soft annealed uncoated copper tape, 5 mil thick, 25% minimum overlap.
6. Assembly: Conductors cabled with non-hygroscopic fillers, as required and binder tape.
7. Jacket: Black sunlight resistance and flame retardant thermoplastic polyvinyl chloride (PVC) compound.

100% and 133% Insulation Levels (90 mil)
Size Number of Strands Conductor Nominal Jacket Thickness Approximate Outside Diameter Approximate Net Weight
Copper Aluminum
AWG of kcmil in mil in lb/kft
8 7 0.13 80 1.15 735
6 7 0.17 80 1.23 908 734
4 7 0.21 80 1.32 1126 849
2 7 0.27 80 1.44 1451 1010
1 19 0.3 80 1.51 1704 1149
1/0 19 0.34 80 1.59 1974 1273
2/0 19 0.38 110 1.74 2442 1559
3/0 19 0.42 110 1.84 2862 1746
4/0 19 0.48 110 1.95 3379 1974
250 37 0.52 110 2.07 3852 2191
300 37 0.57 110 2.18 4460 2468
350 37 0.62 110 2.28 5033 2707
400 37 0.66 110 2.37 5595 2939
500 37 0.74 110 2.59 6844 3524
600 61 0.81 140 2.84 8111 4124
750 61 0.91 140 3.05 9808 4831
1000 61 1.06 140 3.37 12536 5902

Tags: , ,

Similar Or Related





Please enter your first and last name separated by a space (e.g. Jane Miller)




Success! Thanks for Your Request.
Error! Please Try Again.