Mv-90, Power Cable, 35 Kv, 3/C, Cu/Epr/Cts/PVC (ICEA S-93-639/NEMA WC71/UL 1072)

Mv-90, Power Cable, 35 Kv, 3/C, Cu/Epr/Cts/PVC (ICEA S-93-639/NEMA WC71/UL 1072)

Mv-90, Power Cable, 35 Kv, 3/C, Cu/Epr/Cts/PVC (ICEA S-93-639/NEMA WC71/UL 1072)

MV-90

Construction, Underground, Industrial, Power Station

Low and Medium Voltage Cable

DC Cable

Rubber

PVC

Round Wire

Bare Copper Wire

ISO, CCC

Mv-90

Boan

35 Kv

3

1/0 AWG-750 Mcm

B

Copper Tape

DingAn

Heated Steel-Wooden Drum/Steel Drum

SGS

Jiangsu Yixing, China

8544601200

Product Description

MV-90, Power Cable, 35 KV, 3/C, Cu/EPR/CTS/PVC (ICEA S-93-639/NEMA WC71/UL 1072)

Features
UL Listed as MV-105. Rated as Sunlight Resistance for CT use, 1/0 AWG and larger. Oil Resistance I jacket. True Triple extrusion system and closed handling raw materials system, to eliminate any contact with ambient, until extrusion process ends.

Application
Primary power and distribution circuits in industrial and commercial installations, power circuits in generating plants where line to ground fault current are within shield capabilities. May be used in wet or dry locations, installed in raceways, duct, and open air, aerially or directly buried where permitted by NEC.

Standards
UL 1072: Medium Voltage Power Cables.
ICEA S-93-639/NEMA WC74: 5 – 46 kV Shielded Power Cables.
ICEA S-97-682: Standard for Utility Shielded. Power Cables Rated 5 – 46 kV.
AEIC CS8: Specification for Extruded Dielectric, Shielded Power Cables Rated 5 – 46 kV.

Specifications
Maximum operating voltage: 5 kV to 35 kV 100% and 133% IL.
Maximum conductor operation temperatures: Wet and dry locations: Normal: 105 °C, Emergency: 140 °C, Short Circuit: 250 °C

Engineering Information
1. Conductor: Soft annealed uncoated copper compacted Class B per ASTM B496 or hard drawn Aluminum-1350 compacted Class B per ASTM B400.
2. Conductor Shield: Semi conducting cross-linked polyethylene (XLPE).
3. Insulation: Thermoset ethylene propylene rubber (EPR). On request, Amorphous EPR.
4. Insulation Shield: Semi conducting cross-linked polyethylene (XLPE).
5. Phase ID: Colored strings (black, red and blue yarns.)
6. Metallic Shield: Soft annealed uncoated copper tape, 5 mil thick, 25% minimum overlap.
7. Grounding (Optional): One or three soft annealed bare copper or covered conductors cabled with phase conductors.
8. Assembly: Conductors cabled with non hygroscopic fillers, as required and binder tape.
9. Jacket: Black sunlight resistance and flame retardant polyvinyl chloride (PVC) compound.

100% Insulation Levels (260 mil) 133% Insulation Levels (320 mil)
Size Number of Strands Conductor Nominal Jacket Thickness Approximate Outside Diameter Approximate Net Weight Jacket Thickness Approximate Outside Diameter Approximate Net Weight
Copper Aluminum Copper Aluminum
AWG of kcmil in mil in lb/kft mil in lb/kft
1/0 19 0.34 140 2.91 4294 3593 140 3.25 5046 4344
2/0 19 0.38 140 3 4709 3826 140 3.33 5480 4596
3/0 19 0.42 140 3.1 5250 4135 140 3.43 6043 4928
4/0 19 0.48 140 3.21 5869 4465 140 3.55 6688 5283
250 37 0.52 140 3.33 6489 4828 140 3.67 7335 5674
300 37 0.57 140 3.44 7159 5167 140 3.77 8029 6037
350 37 0.62 140 3.54 7822 5497 140 3.94 8897 6571
400 37 0.66 140 3.63 8514 5858 140 4.03 9614 6958
500 37 0.74 140 3.86 9958 6638 140 4.20 10923 7602
600 61 0.81 140 4.05 11280 7293 140 4.39 12288 8301
750 61 0.91 140 4.26 13096 8119 140 4.59 14149 9172