Mv-90, Power Cable, 15 Kv, 3/C, Cu/XLPE/Cts/PVC (ICEA S-93-639/NEMA WC71/UL 1072)

Mv-90, Power Cable, 15 Kv, 3/C, Cu/XLPE/Cts/PVC (ICEA S-93-639/NEMA WC71/UL 1072)

Mv-90, Power Cable, 15 Kv, 3/C, Cu/XLPE/Cts/PVC (ICEA S-93-639/NEMA WC71/UL 1072)

MV-90

Construction, Underground, Industrial, Power Station

Low and Medium Voltage Cable

DC Cable

XLPE

PVC

Round Wire

Bare Copper Wire

ISO, CCC

Mv-90

Boan

8 Kv

3

2 AWG-1000 Mcm

B

Copper Tape

DingAn

Heated Steel-Wooden Drum/Steel Drum

SGS

Jiangsu Yixing, China

8544601200

Product Description

MV-90, Power Cable, 15 KV, 3/C, Cu/XLPE/CTS/PVC (ICEA S-93-639/NEMA WC71/UL 1072)

Features

UL Listed as MV-90. Rated as Sunlight Resistance for CT use, 1/0 AWG and larger. Oil Resistance I jacket. True Triple extrusion system and closed handling raw materials system, to eliminate any contact with ambient, until extrusion process ends.

Application

Primary power and distribution circuits in industrial and commercial installations, power circuits in generating plants where line to ground fault current are within shield capabilities. May be used in wet or dry locations, installed in raceways, duct, and open air, aerially or directly buried where permitted by NEC.

Standards

UL 1072: Medium Voltage Power Cables.
ICEA S-93-639/NEMA WC74: 5 kV – 46 kV Shielded Power Cables.
ICEA S-97-682: Standard for Utility Shielded Power Cables Rated 5 kV- 46 kV.
AEIC CS8: Specification for Extruded Dielectric, Shielded Power Cables Rated 5 kV – 46 kV.

Specifications

Maximum operating voltage: 5 kV to 35 kV 100% and 133% IL
Maximum conductor operation temperatures:
Wet and dry locations: Normal: 90 °C, Emergency: 130 °C, Short Circuit: 250 °C

Engineering Information
1. Conductor: Soft annealed uncoated copper compacted Class B per ASTM B496 or hard drawn Aluminum-1350 compacted Class B per ASTM B400.
2. Conductor Shield: Semi conducting cross-linked polyethylene (XLPE).
3. Insulation: Thermoset crosslinked polyethylene (XLPE).
4. Insulation Shield: Semi conducting cross-linked polyethylene (XLPE).
5. Metallic Shield: Soft annealed uncoated copper tape, 5 mil thick, 25% minimum overlap.
6. Assembly: Conductors cabled with non-hygroscopic fillers, as required and binder tape.
7. Jacket: Black sunlight resistance and flame retardant thermoplastic polyvinyl chloride (PVC) compound.

100% Insulation Levels (175 mil) 133% Insulation Levels (220 mil)
Size Number of Strands Conductor Nominal Jacket Thickness Approximate Outside Diameter Approximate Net Weight Jacket Thickness Approximate Outside Diameter Approximate Net Weight
Copper Aluminum Copper Aluminum
AWG of kcmil in mil in lb/kft mil in lb/kft
2 7 0.27 110 1.89 1974 1533 110 2.09 2233 1792
1 19 0.3 110 1.95 2245 1689 110 2.16 2511 1956
1/0 19 0.34 110 2.03 2536 1835 110 2.24 2811 2109
2/0 19 0.38 110 2.12 2919 2036 110 2.32 3203 2320
3/0 19 0.42 110 2.22 3359 2244 110 2.42 3654 2539
4/0 19 0.48 110 2.33 3899 2495 110 2.53 4206 2802
250 37 0.52 110 2.45 4397 2736 110 2.70 4811 3150
300 37 0.57 110 2.61 5118 3126 140 2.88 5635 3644
350 37 0.62 140 2.77 5887 3562 140 2.98 6248 3923
400 37 0.66 140 2.87 6477 3821 140 3.07 6848 4192
500 37 0.74 140 3.03 7685 4365 140 3.24 8074 4754
600 61 0.81 140 3.22 8825 4838 140 3.43 9235 5248
750 61 0.91 140 3.43 10564 5587 140 3.63 10995 6018
1000 61 1.06 140 3.82 13536 6902 140 4.02 14012 7377

Tags: , ,