Mv-90, Power Cable, 15 Kv, 3/C, Cu/Epr/Cts/PVC (ICEA S-93-639/NEMA WC71/UL 1072)

Mv-90, Power Cable, 15 Kv, 3/C, Cu/Epr/Cts/PVC (ICEA S-93-639/NEMA WC71/UL 1072)

Mv-90, Power Cable, 15 Kv, 3/C, Cu/Epr/Cts/PVC (ICEA S-93-639/NEMA WC71/UL 1072)

MV-90

Construction, Underground, Industrial, Power Station

Low and Medium Voltage Cable

DC Cable

Rubber

PVC

Round Wire

Bare Copper Wire

ISO, CCC

Mv-90

Boan

15 Kv

3

2 AWG-1000 Mcm

B

Copper Tape

DingAn

Heated Steel-Wooden Drum/Steel Drum

SGS

Jiangsu Yixing, China

8544601200

Product Description

MV-90, Power Cable, 15 KV, 3/C, Cu/EPR/CTS/PVC (ICEA S-93-639/NEMA WC71/UL 1072)

Features
UL Listed as MV-105. Rated as Sunlight Resistance for CT use, 1/0 AWG and larger. Oil Resistance I jacket. True Triple extrusion system and closed handling raw materials system, to eliminate any contact with ambient, until extrusion process ends.

Application
Primary power and distribution circuits in industrial and commercial installations, power circuits in generating plants where line to ground fault current are within shield capabilities. May be used in wet or dry locations, installed in raceways, duct, and open air, aerially or directly buried where permitted by NEC.

Standards
UL 1072: Medium Voltage Power Cables.
ICEA S-93-639/NEMA WC74: 5 – 46 kV Shielded Power Cables.
ICEA S-97-682: Standard for Utility Shielded. Power Cables Rated 5 – 46 kV.
AEIC CS8: Specification for Extruded Dielectric, Shielded Power Cables Rated 5 – 46 kV.

Specifications
Maximum operating voltage: 5 kV to 35 kV 100% and 133% IL.
Maximum conductor operation temperatures: Wet and dry locations: Normal: 105 °C, Emergency: 140 °C, Short Circuit: 250 °C

Engineering Information
1. Conductor: Soft annealed uncoated copper compacted Class B per ASTM B496 or hard drawn Aluminum-1350 compacted Class B per ASTM B400.
2. Conductor Shield: Semi conducting cross-linked polyethylene (XLPE).
3. Insulation: Thermoset ethylene propylene rubber (EPR). On request, Amorphous EPR.
4. Insulation Shield: Semi conducting cross-linked polyethylene (XLPE).
5. Phase ID: Colored strings (black, red and blue yarns.)
6. Metallic Shield: Soft annealed uncoated copper tape, 5 mil thick, 25% minimum overlap.
7. Grounding (Optional): One or three soft annealed bare copper or covered conductors cabled with phase conductors.
8. Assembly: Conductors cabled with non hygroscopic fillers, as required and binder tape.
9. Jacket: Black sunlight resistance and flame retardant polyvinyl chloride (PVC) compound.

100% Insulation Levels (175 mil) 133% Insulation Levels (220 mil)
Size Number of Strands Conductor Nominal Jacket Thickness Approximate Outside Diameter Approximate Net Weight Jacket Thickness Approximate Outside Diameter Approximate Net Weight
Copper Aluminum Copper Aluminum
AWG of kcmil in mil in lb/kft mil in lb/kft
2 7 0.27 110 1.89 2084 1643 110 2.09 2385 1944
1 19 0.3 110 1.95 2362 1807 110 2.16 2672 2116
1/0 19 0.34 110 2.03 2662 1961 110 2.24 2982 2281
2/0 19 0.38 110 2.12 3025 2142 110 2.32 3357 2473
3/0 19 0.42 110 2.22 3504 2389 110 2.42 3850 2735
4/0 19 0.48 110 2.33 4056 2652 110 2.53 4433 3021
250 37 0.52 110 2.45 4604 2942 110 2.70 5090 3434
300 37 0.57 110 2.61 5299 3307 110 2.88 5911 3910
350 37 0.62 140 2.77 6079 3753 140 2.98 6535 4193
400 37 0.66 140 2.87 6723 4067 140 3.07 7204 4528
500 37 0.74 140 3.03 7904 4583 140 3.24 8420 5062
600 61 0.81 140 3.22 9121 5134 140 3.43 9668 5641
750 61 0.91 140 3.43 10824 5847 140 3.63 11422 6457
1000 61 1.06 140 3.82 13907 7273 140 4.02 14584 7885