Mv-90, Epr Insulated Power Cable, 8 Kv, 3/C, Cu/Epr/Cts/PVC (ICEA S-93-639/NEMA WC71/UL 1072)

Mv-90, Epr Insulated Power Cable, 8 Kv, 3/C, Cu/Epr/Cts/PVC (ICEA S-93-639/NEMA WC71/UL 1072)

Mv-90, Epr Insulated Power Cable, 8 Kv, 3/C, Cu/Epr/Cts/PVC (ICEA S-93-639/NEMA WC71/UL 1072)

MV-90

Construction, Underground, Industrial, Power Station

Low and Medium Voltage Cable

DC Cable

Rubber

PVC

Round Wire

Bare Copper Wire

ISO, CCC

Mv-90

Boan

Icea S-93-639/NEMA Wc71/UL 1072

8 Kv

3

6 AWG-1000 Mcm

B

Copper Tape

DingAn

Fumigated Steel-Wooden Drum/Steel Drum

SGS

Jiangsu Yixing, China

8544601200

Product Description

MV-90, Power Cable, 8 KV, 3/C, Cu/EPR/CTS/PVC (ICEA S-93-639/NEMA WC71/UL 1072)

Features
UL Listed as MV-105. Rated as Sunlight Resistance for CT use, 1/0 AWG and larger. Oil Resistance I jacket. True Triple extrusion system and closed handling raw materials system, to eliminate any contact with ambient, until extrusion process ends.

Application
Primary power and distribution circuits in industrial and commercial installations, power circuits in generating plants where line to ground fault current are within shield capabilities. May be used in wet or dry locations, installed in raceways, duct, and open air, aerially or directly buried where permitted by NEC.

Standards
UL 1072: Medium Voltage Power Cables.
ICEA S-93-639/NEMA WC74: 5 – 46 kV Shielded Power Cables.
ICEA S-97-682: Standard for Utility Shielded. Power Cables Rated 5 – 46 kV.
AEIC CS8: Specification for Extruded Dielectric, Shielded Power Cables Rated 5 – 46 kV.

Specifications
Maximum operating voltage: 5 kV to 35 kV 100% and 133% IL.
Maximum conductor operation temperatures: Wet and dry locations: Normal: 105 °C, Emergency: 140 °C, Short Circuit: 250 °C

Engineering Information
1. Conductor: Soft annealed uncoated copper compacted Class B per ASTM B496 or hard drawn Aluminum-1350 compacted Class B per ASTM B400.
2. Conductor Shield: Semi conducting cross-linked polyethylene (XLPE).
3. Insulation: Thermoset ethylene propylene rubber (EPR). On request, Amorphous EPR.
4. Insulation Shield: Semi conducting cross-linked polyethylene (XLPE).
5. Phase ID: Colored strings (black, red and blue yarns.)
6. Metallic Shield: Soft annealed uncoated copper tape, 5 mil thick, 25% minimum overlap.
7. Grounding (Optional): One or three soft annealed bare copper or covered conductors cabled with phase conductors.
8. Assembly: Conductors cabled with non hygroscopic fillers, as required and binder tape.
9. Jacket: Black sunlight resistance and flame retardant polyvinyl chloride (PVC) compound.

100% Insulation Levels (115 mil) 133% Insulation Levels (140 mil)
Size Number of Strands Conductor Nominal Jacket Thickness Approximate Outside Diameter Approximate Net Weight Jacket Thickness Approximate Outside Diameter Approximate Net Weight
Copper Aluminum Copper Aluminum
AWG of kcmil in mil in lb/kft mil in lb/kft
6 7 0.17 80 1.34 1055 881 80 1.45 1176 1001
4 7 0.21 80 1.43 1285 1008 80 1.55 1413 1136
2 7 0.27 80 1.55 1625 1185 80 1.67 1762 1321
1 19 0.30 80 1.62 1887 1332 110 1.80 2140 1585
1/0 19 0.34 110 1.76 2277 1576 110 1.88 2432 1730
2/0 19 0.38 110 1.85 2625 1741 110 1.96 2786 1902
3/0 19 0.42 110 1.95 3086 1971 110 2.06 3255 2139
4/0 19 0.48 110 2.06 3618 2213 110 2.18 3794 2390
250 37 0.52 110 2.19 4143 2482 110 2.30 4329 2668
300 37 0.57 110 2.29 4728 2737 110 2.40 4922 2931
350 37 0.62 110 2.39 5314 2989 110 2.50 5516 3190
400 37 0.66 110 2.48 5933 3278 110 2.65 6234 3578
500 37 0.74 140 2.76 7334 4014 140 2.88 7566 4246
600 61 0.81 140 2.95 8518 4531 140 3.07 8763 4777
750 61 0.91 140 3.16 10184 5207 140 3.27 10445 5467
1000 61 1.06 140 3.49 13031 6397 140 3.60 13316 6682

Tags: , ,