LV ABC Amka-T Cable 3X95+16+70 (0.6/1kV) with Insulated Almelec Messenger

LV ABC Amka-T Cable 3X95+16+70 (0.6/1kV) with Insulated Almelec Messenger

LV ABC Amka-T Cable 3X95+16+70 (0.6/1kV) with Insulated Almelec Messenger

AMKA-T Cable

Hongda

Amka-T

ISO, CCC, CE

Aluminum

Round Wire

Crosslinking

XLPE

DC Cable

Low and Medium Voltage Cable

Construction, Overhead, Industrial, Power Station

2, 3 or 4 Longitudinal Ridges

No Ridges

Hongda, accept OEM

Wooden Drum

6sqmm to 150sqmm

China

8544492100

Product Description

AMKA 1 kV
1 Kv Self Supporting Bundle Assembled Aerial ABC Amka Cable

AMK-X, AMK-T, AMKA-X, AMKA-T

Installation Information
• Economical • Flexible • Safe • Vandal proof • Durable • Aesthetically pleasing • Adaptable

RATED VOLTAGE
U0/U = 0,6/1 kV, Um = 1,2 kV

APPLICATION
For overhead distribution as a part of AMKA-system, where the messenger is used as PEN-conductor. The cable can have one optional conductor for street lighting.

Highest permissible conductor temperature:
• continuous operation 70 °C
• short circuit (duration up to 5 s) 135 °C
Lowest recommended temperature during laying: -20 °C

CONSTRUCTION

Conductor 16 mm²: solid aluminium wire
25-120 mm²: stranded aluminium wire
Insulation Black weather-resistant PE / XLPE compound
Messenger Stranded aluminium alloy wire
Laying up Insulated conductors are laid up around the messenger

IDENTIFICATION OF CORES
Phase conductors: 2, 3 or 4 longitudinal ridges
Optional conductor: no ridges

STANDARDS
SFS 2200
HD 626-5D
NFC 33-209

CUSTOMS CODE: 8544492100

Mechanical Properties

BUNDLE MAIN CHARACTERISTICS TO SABS 1418 – 1986

Bundle Size mm²

Phase Neutral Lighting

Bundle

Phase
conductor
approx. Ø

mm
 

Neutral
conductor
approx. Ø

mm
 

Lighting
conductor
approx. Ø

mm
 

Max 
current
rating
air at
30°C

 

3 volt
drop
PF=1.0
at 30°C
V/A/km

 

Max Liner
resistance
per phase
conductor
at 30°C-km

Approx
overall
Ø
mm

 

Approx
weight
kg/m

3×25 + 54.6 + 1×25

29

0.70

9

12.4

9

98

2.62

1.200

3×35 + 54.6 + 1×25

31

0.82

10.2

12.4

9

120

1.89

0.868

3×50 + 54.6 + 1×25

33

0.95

11.6

12.4

9

150

1.40

0.641

3×70 + 54.6 + 1×25

37

1.25

13.7

12.4

9

200

0.97

0.443

3×95 + 54.6 + 1×25

41

1.45

15.2

12.4

9

240

0.71

0.320

3×120 + 70 + 1×25

45

1.70

16.5

13.5

9

280

0.57

0.253

3×35 + 35BN

23

0.47

9.65

7.05

N/A

130

1.08

0.868

3×70 + 50BN

30

0.84

11.05

8.05

N/A

205

0.55

0.443

Cable
Description

Size (mm²)

Current Rating
(Amp)

Weight
(kg/m)

2×25

25

98

0.23

4×25

25

92

0.46

2x16AI

16

80

0.15

4x16AI

16

74

0.30

4 Airdac

4-Phase & Neutral,
2.5 Earth

50

0.16

6 Airdac

6-Phase & Neutral,
4 Earth

65

0.22

10 Airdac

10-Phase & Neutral,
7.5 Earth

90

0.32

16 Airdac

16-Phase & Neutral,
10 Earth

125

0.49

4 Airdac II

4

50

0.12

10 Airdac II

10

86

0.25

16 Airdac II

16

125

0.41

(1) Approximate value.
(2) See the basic assumptions at general information of products.
(3) Final installation with careful single bending into final position.
(4) The effective diameter in wind is equal to the length of measuring tape wrapped around the cable divided by the value 3,1416 (pi).
(5) Initial temperature of conductor before short circuit 70°C, final temperature of conductor after short circuit 135°C.
(6) Initial temperature of messenger before short circuit 70°C, final temperature of messenger after short circuit 135°C.