Hv ABC Cable, Aerial Bundled Cable, Al/XLPE/HDPE+AAAC, 3/C+1/C, 6.35/11 Kv (AS/NZS 3599.2)

Hv ABC Cable, Aerial Bundled Cable, Al/XLPE/HDPE+AAAC, 3/C+1/C, 6.35/11 Kv (AS/NZS 3599.2)

Hv ABC Cable, Aerial Bundled Cable, Al/XLPE/HDPE+AAAC, 3/C+1/C, 6.35/11 Kv (AS/NZS 3599.2)

Hv ABC Cable

Insulated

Stranded

Overhead

Aluminum

HDPE

XLPE

Round Wire

Distribution

ISO9001, CCC

Boan

6.35/11 Kv

3+1

35-185 Mm2

2

AAAC 1120

DingAn

Heated Steel-Wooden Drum/Steel Drum

SGS

Jiangsu Yixing, China

8544601200

Product Description

HV ABC Cable, Aerial Bundled Cable, Non Metallic, 6.35/11 kV (AS/NZS 3599.2)
Non Metallic Screened HV ABC

Conductors
Phase conductors are stranded circular compacted aluminium alloy 1350 to H68 condition. The standard catenary is bare stranded circular compacted aluminium alloy 1120 conductor. For special applications, such as high wind locations, aluminium-clad steel-reinforced catenaries are available.

Conductor Screen, Insulation and Insulation Screen
Semiconductive conductor screen, XLPE insulation and semiconductive insulation screen are triple extruded. The insulation screen is hand strippable without preheating and complies with strippability and adhesion tests given in AS/NZS 3599.2. Figures and words "1 ONE," "2 TWO" and "3 THREE" are marked on the insulation screen to identify the three phase cores.

We has developed a special Non Metallic Screened HV ABC with far greater resistance to damage from abrasion during installation or due to brushing with trees. This special cable has a semiconductive HDPE layer over the hand-strippable insulation screen, providing less risk of damage during installation and service.

The cable bundle
The three single core cables are bundled around the aluminium alloy 1120 catenary in a right hand lay. Operating temperatures
(a) Normal operation 90°C
(b) Emergency operation 105°C
(c) Short circuit operation 250°C (5s max)

HV XLPE Insulated Non-metallic Screend ABC 6.35/11 KV (Cross-linked Screen with Semi-conductive HDPE)
Units 6.35/11 KV
Nominal Conductor Area mm2 35 50 70 95 120 150 185
Average Insulation Thickness mm 3.4 3.4 3.4 3.4 3.4 3.4 3.4
Average Insulation Screen Thickness mm 1.8 1.8 1.8 1.8 1.8 1.8 1.8
AAAC/1120 Support Conductor Size no/mm 7/4.75 7/4.75 7/4.75 7/4.75 19/3.50 19/3.50 19/3.50
Nominal Overall Diameter mm 52.0 54.2 57.4 60.9 66.9 69.7 72.7
Approx. Mass kg/km 1320 1490 1740 2050 2480 2780 3120
DC Resistance at 20°C Ω/km 0.868 0.641 0.443 0.320 0.253 0.206 0.164
AAAC/1120 Support Conductors
Units
Stranding & Nom. Wire Dia. no/mm 7/4.75 19/3.50
Nominal Overall Diameter mm 14.3 17.5
DC Resistance at 20°C Ω/km 0.239 0.163
Minimum Breaking Load kN 27.1 41.7

Tags: , ,