Fkkj, Power Cable, 0.6/1 Kv, Cu/PVC/Cws/Cts/PVC (HD 603.3/IEC 60502-1)

Fkkj, Power Cable, 0.6/1 Kv, Cu/PVC/Cws/Cts/PVC (HD 603.3/IEC 60502-1)

Fkkj, Power Cable, 0.6/1 Kv, Cu/PVC/Cws/Cts/PVC (HD 603.3/IEC 60502-1)

FKKJ

Insulated

Stranded

Underground

Copper

PVC

PVC

Round Wire

Distribution

ISO9001, CCC

Boan

0.6/1 Kv

16-240 Mm2

1-4

Copper Wire+Copper Tape

DingAn or OEM

Heated Steel-Wooden Drum/Steel Drum

SGS

Jiangsu Yixing, China

8544492100

Product Description

FKKJ, Power Cable, 0.6/1 KV, CU/PVC/CWS/CTS/PVC (HD 603.3/IEC 60502-1)
CONSTRUCTION
Conductors: copper annealed circular compacted stranded conductor class 2 (RM) or stranded sector – shaped conductor class 2 (SM) acc. to EN 60228
Insulation: special PVC compound type DIV11 acc. to HD 603.1
Cable core: Insulated conductors are twisted together with eventually central filler
Inner covering: PVC tape
Concentric conductor: round copper wires and copper tape
Sheath: special PVC compound type DMV19 acc. to HD 603.1

CHARACTERISTIC
Colour of sheath: black
1-core: black
2-core: blue, brown
3-core: brown, black, grey
4-core: blue, brown, black, grey
5-core: blue, brown, black, grey, black

Maximum conductor operating temperature: +70oC
Lowest ambient temperature for fixed installation: -30oC
Lowest installation temperature: 0oC
Maximum short-circuit conductor temperature: + 160oC

Minimum bending radius: 15 x D single core cables, 12 x D multicore cables, D – overall diameter
Max. permissible tensile stress with cable grip for Cu-conductor: 50 N/mm2
Test voltage: 3,5kV AC 50Hz, 5min

Current of short-circuit (1 sec): up to 300mm2 115 x nominal cross section conductor (A)
above 300mm2 103 x nominal cross section conductor (A)
Flame retardant: IEC 60332-1-2

APPLICATIONS
PVC insulated and sheathed power cables for the supply of electrical energy. Special for installations in the open air, in underground and water, indoors, in cable ducts. The concentric conductor is allowed to use as neutral, protective or earthed conductor. Simultaneously, this also is permitted to apply as a screen for example earth-connected protection against contact.

Number and cross-section Approximate overall diameter Approximate net weight of cables Maximum conductor resistance at temperature 20oC
n x mm2 mm kg/km Ω/km
1x16RM/16 11,8 380 1,15/1,15
1x25RM/16 13,5 485 0,727/1,15
1x35RM/16 14,6 583 0,524/1,15
1x50RM/25 16,3 804 0,387/0,727
1x70RM/35 17,9 1108 0,268/0,524
1x95RM/50 20,5 1523 0,193/0,387
1x120RM/50 21,9 1758 0,153/0,387
1x150RM/50 24,1 2057 0,124/0,387
1x185RM/50 26,2 2438 0,0991/0,387
2x16RM/16 21,2 715 1,15/1,15
2x25RM/16 24.6 967 0,727/1,15
2x35RM/16 26,7 1191 0,524/1,15
3x16RM/16 22,2 879 1,15/1,15
3x25RM/16 25,9 1222 0,727/1,15
3x25RM/25 25,9 1307 0,727/0,727
3x35RM/16 28,1 1533 0,524/1,15
3x35RM/35 28,1 1710 0,524/0,524
3x35SM/16 25,4 1433 0,524/1,15
3x35SM/35 25,6 1622 0,524/0,524
3x50SM/25 28,6 1950 0,387/0,727
3x50SM/50 28,6 2174 0,387/0,387
3x70SM/35 31,9 2681 0,268/0,524
3x70SM/70 32,6 3010 0,268/0,268
3x95SM/50 35,8 3647 0,193/0,387
3x95SM/95 36,7 4079 0,193/0,193
3x120SM/120 40,3 5070 0,153/0,153
3x120SM/70 39,4 4600 0,153/0,268
3x150SM/70 43,4 5501 0,124/0,268
3x185SM/95 48,5 6896 0,0991/0,193
3x240SM/120 54,8 8938 0,0754/0,153
4x16RM/16 23,9 1058 1,15/1,15
4x25RM/16 28 1498 0,727/1,15
4x35RM/16 30,6 1902 0,524/1,15
4x35SM/16 28,3 1828 0,524/1,15
4x50SM/25 32 2486 0,387/0,727
4x70SM/35 35,6 3414 0,268/0,524
4x95SM/50 40,5 4678 0,193/0,387
4x120SM/70 44,6 5856 0,153/0,268
4x150SM/70 49,8 7066 0,124/0,268