Cu/XLPE/PVC/Sta/PVC, 0.6/1 Kv, Steel Tape Armored Power Cable (IEC 60502-1)
More product about Electric CableProduct Description
CONSTRUCTION
Conductor: Plain annealed stranded circular copper conductor, as per Class 2 of IEC 60228.
Insulation: An extruded layer of Cross linked polyethylene (XLPE) insulation, rated 90 º C at normal operation to IEC 60502-1.
Bedding: An extruded layer of Polyvinyl chloride (PVC).
Armour: Double layer of galvanized steel tapes.
Outer Sheath: An extruded layer of Polyvinyl chloride (PVC) sheathing compound type ST2 to IEC 60502-1.
APPLICATION
For outdoor installations in power stations, industrial plants and switchgears if mechanical
Protection is required or in applications where mechanical damages are expected to occur.
TECHNICAL DATA
– Nominal voltage Uo/U = 0.6/1 kV
– Power frequency test voltage 3.5 kV for 5 minutes
– Max. Admissible temperature of conductor at normal operation 90 º C
– Max. Admissible temperature of conductor at short circuit 250 º C for 5 seconds
Section | Max. Conductor Resistance | Current Rating | Overall Diamter | Cable Weight | ||||
DC at 20 | AC at 90 | Laid in ground | Laid in ducts | Laid in free air | ||||
mm2 | Ω/km | A | mm | kg/km | ||||
Two Core Cables | ||||||||
6 | rm | 3.0800 | 3.9300 | 62 | 51 | 59 | 15.5 | 405 |
10 | rm | 1.8300 | 2.3300 | 81 | 68 | 78 | 17.5 | 530 |
16 | rm | 1.1500 | 1.4700 | 105 | 82 | 103 | 19.5 | 685 |
25 | rm | 0.7270 | 0.9270 | 138 | 106 | 137 | 22.1 | 930 |
35 | rm | 0.5240 | 0.6690 | 164 | 132 | 164 | 23.8 | 1245 |
Three Core Cables | ||||||||
6 | rm | 3.0800 | 3.9300 | 56 | 44 | 49 | 16.2 | 465 |
10 | rm | 1.8300 | 2.3300 | 74 | 59 | 67 | 18.4 | 650 |
16 | rm | 1.1500 | 1.4700 | 96 | 74 | 88 | 20.5 | 870 |
25 | rm | 0.7270 | 0.9270 | 127 | 100 | 120 | 24.2 | 1235 |
35 | sm | 0.5240 | 0.6690 | 153 | 119 | 143 | 22.8 | 1370 |
Four Core Cables | ||||||||
6 | rm | 3.0800 | 3.9300 | 56 | 44 | 49 | 17.4 | 555 |
10 | rm | 1.8300 | 2.3300 | 74 | 59 | 67 | 19.8 | 795 |
16 | rm | 1.1500 | 1.4700 | 96 | 74 | 88 | 22.2 | 1075 |
25 | rm | 0.7270 | 0.9270 | 127 | 100 | 120 | 26.3 | 1540 |
35 | sm | 0.5240 | 0.6690 | 153 | 119 | 143 | 26.4 | 1830 |
50 | sm | 0.3870 | 0.4940 | 185 | 145 | 178 | 30.1 | 2415 |
70 | sm | 0.2680 | 0.3430 | 220 | 180 | 215 | 34.6 | 3335 |
95 | sm | 0.1930 | 0.2480 | 265 | 210 | 268 | 39.7 | 4815 |
120 | sm | 0.1530 | 0.1970 | 305 | 245 | 310 | 43.8 | 5910 |
150 | sm | 0.1240 | 0.1600 | 335 | 275 | 352 | 48.7 | 7195 |
185 | sm | 0.0991 | 0.1290 | 375 | 310 | 404 | 53.7 | 8830 |
240 | sm | 0.0754 | 0.0990 | 435 | 365 | 483 | 60.0 | 11285 |
300 | sm | 0.0601 | 0.0810 | 490 | 405 | 562 | 65.5 | 13835 |
Four Core Cables with Reduced Neutral | ||||||||
35 sm | 16 rm | 0.5240 / 1.1500 | 0.6690 / 1.4700 | 153 | 119 | 143 | 25.3 | 1640 |
50 sm | 25 rm | 0.3870 / 0.7270 | 0.4940 / 0.9270 | 185 | 145 | 178 | 28.7 | 2160 |
70 sm | 35 sm | 0.2680 / 0.5240 | 0.3430 / 0.6690 | 220 | 180 | 215 | 33.1 | 2960 |
95 sm | 50 sm | 0.1930 / 0.3870 | 0.2480 / 0.4940 | 265 | 210 | 268 | 38.0 | 4280 |
120 sm | 70 sm | 0.1530 / 0.2680 | 0.1970 / 0.3430 | 305 | 245 | 310 | 42.1 | 5365 |
150 sm | 70 sm | 0.1240 / 0.2680 | 0.1600 / 0.3430 | 335 | 275 | 352 | 46.3 | 6355 |
185 sm | 95 sm | 0.0991 / 0.1930 | 0.1290 / 0.2480 | 375 | 310 | 404 | 51.2 | 7865 |
240 sm | 120 sm | 0.0754 / 0.1530 | 0.0990 / 0.1970 | 435 | 365 | 483 | 57.1 | 10000 |
300 sm | 150 sm | 0.0601 / 0.1240 | 0.0810 / 0.1600 | 490 | 405 | 562 | 62.2 | 12205 |
Similar Or Related
0.6/1kv Electric Aluminum Conductor PVC/XLPE/PE Insulated PVC Sheathed Low/Medium Voltag Electrical Power Cable
Read More
Fire Resistant Marine Insulated PVC Sheath Jacket Underground Armoured Overhead Electrical Cables XLPE Copper Aluminum Electric Wire Power Cable
Read More
Low Voltage Unarmored Yjv Cable 0.6/1kv
Read More