Cu/XLPE/Cts/PVC/Swa/PVC, Power Cable, 19/33 Kv, 3/C (BS 6622)

Cu/XLPE/Cts/PVC/Swa/PVC, Power Cable, 19/33 Kv, 3/C (BS 6622)

Cu/XLPE/Cts/PVC/Swa/PVC, Power Cable, 19/33 Kv, 3/C (BS 6622)

CU/XLPE/CTS/PVC/SWA/PVC

Construction, Underground, Industrial, Power Station

Low and Medium Voltage Cable

DC Cable

XLPE

PVC

Round Wire

Bare Copper Wire

ISO, CCC, CE

Cu/XLPE/Cts/PVC/Swa/PVC

Boan

BS 6622

19/33 Kv

3

2

50-400 mm2

Copper Tape

Galvanized Steel Wire Armour

DingAn

Fumigated Steel-Wooden Drum/Steel Drum

SGS, CE

Jiangsu Yixing, China

8544601300

Product Description

Cu/XLPE/CTS/PVC/SWA/PVC, Power Cable, 19/33 Kv, 3/C (BS 6622)

Application
Power cables for power networks, underground and in cable ducting.

Standards
BS6622

Technical Data

Conductor
Class 2 stranded plain copper conductor to BS EN 60228:2005 (previously BS6360)

Conductor Screen
Semi-conducting material

Insulation
XLPE (Cross-Linked Polyethylene) Type GP8 to BS7655
Insulation Screen
Semi-conducting material

Metallic Screen
Individual and overall copper tape screen to BS6622

Filler
PETP (Polyethylene Terephthalate) fibres

Separator
Binding tape

Bedding
PVC (Polyvinyl Chloride) Type TM1 to BS7655

Armouring
Multi-Core: SWA (Steel Wire Armoured)

Sheath
PVC (Polyvinyl Chloride) Type TM1 to BS7655

Sheath Colour
Red or Black

Voltage Rating
19000/33000V

Temperature Rating
0°C to +90°C

Minimum Bending Radius
Three Cores: 12 x overall diameter
No. of Cores x Nominal Cross Sectional Area Nominal Diameter Nominal Weight
Under Armour Over Armour Overall
# x mm² mm kg/Km
3 x 50 65.1 71.4 78.2 9150
3 x 70 68.8 75.1 82.1 10300
3 x 95 72.6 78.9 86.1 11600
3 x 120 76.3 82.6 90.0 12800
3 x 150 79.3 85.6 93.2 14050
3 x 185 83.4 89.7 97.5 15650
3 x 240 88.8 95.1 103.3 18200
3 x 300 93.9 100.2 108.8 21100
3 x 400 100.8 107.1 116.1 24200

Tags: , ,

Contact us

 

 

 

Success! Thanks for Your Request.
Error! Please Try Again.