Cu/XLPE/Cts/PVC/Sta/PVC, Power Cable, 12/20 (24) Kv, 3/C (IEC 60502-2)

Cu/XLPE/Cts/PVC/Sta/PVC, Power Cable, 12/20 (24) Kv, 3/C (IEC 60502-2)
CU/XLPE/CTS/PVC/STA/PVC
Underground, Industrial, Power Station
Low and Medium Voltage Cable
DC Cable
XLPE
PVC
Round Wire
Bare Copper Wire
ISO, CCC, CE
Cu/XLPE/Cts/PVC/Sta/PVC
Boan
12/20 (24) Kv
2
3
35-400 mm2
Steel Tape Armour
DingAn
Heated Steel-Wooden Drum/Steel Drum
SGS
Jiangsu Yixing, China
8544601200

Product Description

CU/XLPE/CTS/PVC/STA/PVC, Power Cable, 12/20 (24) KV, 3/C (IEC 60502-2)
The cable design conforms to IEC 60502 part 2. However if requested, we can separately offer guaranteed technical particulars for cables as per different international specifications or specific customer needs.

CONSTRUCTIONAL FEATURES

Conductor
Copper Conductors upto 1000 sq mm will be circular compacted & stranded and shall comply with IEC-60228 Class 2.

Conductor screen
This will be an extruded layer of semiconducting XLPE applied under simultaneous triple extrusion process over the conductor along with the insulation and the insulation screen.

Insulation
This will be an extruded layer of insulating grade XLPE applied over conductor screen under triple extrusion process along with conductor screen and insulation screen.

Insulation screen
This will be a layer of semiconducting XLPE which will be applied by tripe extrusion process over the insulation.

Metallic screen
It will consist of a layer of copper wires applied helically with overlap over insulation screen. Other combinations of metallic screens as per customer’s requirement can also be provided on request.

Inner Sheath (Bedding)
Extruded layer of PVC or PE is applied over the laid-up cores. PVC is normally of grade ST2 or PE of grade ST7 as per IEC 60502 Part 2.

Armour

The armour is applied over inner sheath. For Single core cables this is of aluminium wires and for multicore cables the armour can be of one among the following options: –
A) Galvanized steel wire.
B) Galvanized steel tape.
C) Galvanised steel strip.
The armour is applied helically over the bedding.

Outer sheath
An extruded layer is applied over the armour in case of armoured cables and over the laid up cores in case of unarmoured cables. Outer sheath material can be either PVC of grade ST2 or PE of grade ST7 as per IEC-60502 Part 2.

Section Conductor diameter Conductor weight Insulation thickness Bedding thickness Steel tape thickness Outer sheath thickness Cable overall diameter Cable weight Minimum bending radius of cable (During installation) DC resistance of conductor at 20 °C (Maximum)
mm2 mm kg/km mm mm mm mm mm kg/km mm ohm/km
35 6.9 922 5.5 1.5 0.5 2.7 55.0 3905 825 0.524
50 8.1 1242 5.5 1.6 0.5 2.8 58.0 4460 870 0.387
70 9.7 1800 5.5 1.6 0.5 2.9 61.5 5320 923 0.268
95 11.4 2500 5.5 1.7 0.5 3.1 66.0 6410 990 0.193
120 12.9 3152 5.5 1.7 0.5 3.2 69.0 7365 1035 0.153
150 14.3 3888 5.5 1.8 0.5 3.3 72.5 8420 1088 0.124
185 16.0 4875 5.5 1.9 0.5 3.4 76.5 9800 1148 0.0991
240 18.4 6410 5.5 2.0 0.8 3.6 83.5 12740 1253 0.0754
300 20.6 8039 5.5 2.0 0.8 3.8 89.0 14935 1335 0.0601
400 23.3 10301 5.5 2.2 0.8 4.0 96.5 18140 1448 0.0470