Covered Line Wire AAC /AAAC /ACSR Conductor UV-XLPE Insulated Cable

Covered Line Wire AAC /AAAC /ACSR Conductor UV-XLPE Insulated Cable

Covered Line Wire AAC /AAAC /ACSR Conductor UV-XLPE Insulated Cable

Insulated

Stranded

Overhead

Aluminum

Crosslinking

XLPE

Round Wire

Overhead

ISO9001, CCC

Hongda

2, 3 or 4 Longitudinal Ridges

No Ridges

Hongda, accept OEM

Wooden Drum

6sqmm to 150sqmm

China

8544492100

Product Description

600 Volts ABC Insulated Wire Self Supporting Aerial Bundle Cable

Installation Information
• Economical • Flexible • Safe • Vandal proof • Durable • Aesthetically pleasing • Adaptable

RATED VOLTAGE
U0/U = 0,6/1 kV, Um = 1,2 kV

APPLICATION
For overhead distribution as a part of AMKA-system, where the messenger is used as PEN-conductor. The cable can have one optional conductor for street lighting.

Highest permissible conductor temperature:
• continuous operation 90 °C
• short circuit (duration up to 5 s) 250 °C
Lowest recommended temperature during laying: -20 °C

CONSTRUCTION

Conductor 16 mm²: solid aluminium wire
25-120 mm²: stranded aluminium wire
Insulation Black weather-resistant PE / XLPE compound
Messenger Stranded aluminium alloy wire
Laying up Insulated conductors are laid up around the messenger

IDENTIFICATION OF CORES
Phase conductors: 2, 3 or 4 longitudinal ridges
Optional conductor: no ridges

STANDARDS
SFS 2200
HD 626-5D
NFC 33-209

Mechanical Properties

Cable
Size
Conductor
Diameter
Core
Diameter
Self Supporting System Supporting Core System
Approx.
Assembly
Diameter
Approx.
Assembly
Mass
Maximum
Design
Load
Supporting
Core Size
Approx.
Assembly
Diameter
Approx.
Assembly
Mass
Maximum
Design
Load
Phase Cores Min Max Min Max
mm² (mm) (mm) (A) kA (mm) (kg/km) (kN) mm² (mm) (kg/km) (kN)
25 5,6 6,5 8,4 9,6 25 400 5 54,6 26 507 6
35 6,6 7,5 9,8 11,1 27 540 7 54,6 28 612 6
50 7,7 8,6 10,9 12,3 29 697 9 54,6 32 730 6
70 9,3 10,2 12,9 14,3 33 982 14 54,6 34 944 6
95 11,0 12,0 14,6 16,2 37 1302 19 54,6 38 1183 6
120 12,5 13,5 16,1 17,5 41 1470 24 70 40 1600 8
150 13,9 15,0 17,5 19,2 45 2011 30 95,0 44 1870 13
Above Plus 25mm² Auxiliary Core
25 N/A N/A N/A N/A 25 505 N/A N/A 32 612 N/A
35 32 645 34 717
50 34 802 36 835
70 38 1087 38 1049
95 42 1407 42 1288
120 44 1575 50 1705
150 48 2116 56 1975

(1) Approximate value.
(2) See the basic assumptions at general information of products.
(3) Final installation with careful single bending into final position.
(4) The effective diameter in wind is equal to the length of measuring tape wrapped around the cable divided by the value 3,1416 (pi).
(5) Initial temperature of conductor before short circuit 70°C, final temperature of conductor after short circuit 135°C.
(6) Initial temperature of messenger before short circuit 70°C, final temperature of messenger after short circuit 135°C.

PACKAGE AND FACTORY: