Cable Na2X2y 0, 6/1 Kv Single Core UV. Resist

Cable Na2X2y 0, 6/1 Kv Single Core UV. Resist

Cable Na2X2y 0, 6/1 Kv Single Core UV. Resist

Cable NA2X2Y

OEM

Cable Na2X2y

ISO, CCC

Red Copper Wire

Round Wire

LLDPE

XLPE

AC Cable

Low and Medium Voltage Cable

Construction, Underground, Industrial, Power Station

Single Core

OEM

Wooden Drum

China(Mainland)

8544492100

Product Description

 STANDARDS

International :  IEC 60228; IEC 60332-1; IEC 60502-1; IEC 60684-2; IEC 60754-1; IEC 60754-2; IEC 60811-4-1; IEC 61034
National :  ICEA S-95-658; NTP-IEC 60228; NTP-IEC 60502-1

DESCRIPTION

Application:

General application as power cable. In low voltage distribution power networks, industrial installations, in buildings and operation stations. In fixed installations, indoor and outdoor areas (trays, gutters, staples). It can be installed in ducts, in dry or wet locations.

Construction:

1. Conductor: Compact aluminium 1350, class 2.

2. Insulation: XLPE cross linked polyethylene.

3. Outer sheath: Low Linear Dendsity Polyethylene LLDPE-UV.

Main characteristics:

Good electrical and mechanical properties. Cross-linked polyethylene insulation allows greater power capacity under any operating condition, minimum dielectric losses, high insulation resistance. The outer sheath has the following characteristics: low emission dense smoke and halogen free. Resistance to abrasion, moisture and sunlight. Adequate resistance to greases and oils. Flame restardant.

Section:

From 10 mm2 up to 400 mm2.

Colour:

Insulation: Natural.

Outer sheath: Black.

National standards

NTP-IEC 60228: Conductors of insulated cables.

NTP-IEC 60502-1: Power cables with extruded insulation and their accessories for rated voltages from 1 kV and 3 kV.

Conductor material aluminum Alloy 1350
Insulating material XLPE
Outer sheath LLDPE-UV
Sheath colour Black
Halogen free IEC 60754-1
Lead free Yes
Dielectric strength 3.5kV
Time of application Dielectric strength core to screen DC 5min.
U.V resistance UL 2556 – Sunlight Resistance
Oil resistance ICEA S-95-658
Gases toxicity Low toxicity to IEC 60684-2
Gases corrosivity Low pH Corrosivity IEC 60754-2
Smoke density IEC 61034-2
Flame retardant IEC 60332-1-2; FT1
Maximum operating temperature 90°C
Overload maximum core temperature 130°C
Short-circuit max. conductor temperature 250°C

Packing shipping

  

Why Choose Us ?
1. We have a large production base, and advanced production equipment 
2. Have an competitive price and high quality
3. Excellent after-sale service
4. Free issue:packaging list,invoice
5. Powerful technology team
6. Strict quality assurance system and perfect testing means
7. Advanced process equipment
8. Delivery on time
9. Our cable sales to Middle East,Africa,Russia,Southeast Asia, etc.
10.We have a good reputation in the overseas

Any problem and inquiry pls contact with Tina
Phone number: +86-18339931106

Tags: , ,

Contact us

 

 

 

Success! Thanks for Your Request.
Error! Please Try Again.

Similar Or Related