Aluminum Alloy Overhead AAAC Conductor
More product about Aluminum Alloy CableProduct Description
1.Application
The AAAC is used for overhead power transmission lines , especially the electric power augmentation of old transmission lines. We specialized in the research and application of AAAC for almost ten years. When replacing the aluminium conductor steel reinforced , the AAAC can save 5-8% of the construction cost. This AAAC covers aluminium alloy (hard solution, heat-treated, cold worked, and artifically aged) round wires for electrical purposes to be used as component wires of aluminium alloy conductor and aluminium alloy conductor steel reinforced.
2.Standard:
ASTM B399,BS EN50183 ,BS 3242,DIM 48201,IEC 61089
3.Specification
All Aluminum Alloy Conductors ASTM B 399
Area | Stranding | Approx. Dia. | Weight | Nominal Breaking Load | D.C. Resistance at 20ºC | Standard Length | |
Nominal | Actual | ||||||
AWG or MCM | mm2 | mm | mm | kg/km | kN | ohm/km | m±5% |
6 | 13.30 | 7/1.554 | 4.67 | 37 | 4.22 | 2.5199 | 3500 |
4 | 21.15 | 1/1.961 | 5.89 | 58 | 6.71 | 1.5824 | 3000 |
2 | 33.63 | 7/2.474 | 7.42 | 93 | 10.68 | 0.9942 | 2500 |
1/0 | 53.48 | 7/3.119 | 9.36 | 148 | 16.97 | 0.6256 | 2000 |
2/0 | 67.42 | 7/3.503 | 10.51 | 186 | 20.52 | 0.4959 | 3500 |
3/0 | 85.03 | 7/3.932 | 11.80 | 234 | 25.86 | 0.3936 | 3000 |
4/0 | 107.23 | 7/4.417 | 13.26 | 296 | 32.63 | 0.3119 | 2000 |
250 | 126.66 | 19/2.913 | 14.57 | 349 | 38.93 | 0.2642 | 2000 |
300 | 152.10 | 19/63.193 | 15.97 | 419 | 46.77 | 0.2199 | 3000 |
350 | 177.35 | 19/3.447 | 17.24 | 489 | 52.25 | 0.1887 | 3000 |
400 | 202.71 | 19/3.686 | 18.43 | 559 | 59.74 | 0.1650 | 2500 |
450 | 228.00 | 19/3.909 | 19.55 | 629 | 67.19 | 0.1467 | 2000 |
500 | 253.35 | 19/4.120 | 20.60 | 698 | 74.64 | 0.1321 | 2000 |
550 | 278.60 | 37/3.096 | 21.67 | 768 | 83.80 | 0.1202 | 2000 |
600 | 303.80 | 37/3.233 | 22.63 | 838 | 91.38 | 0.1102 | 2000 |
650 | 329.25 | 37/3.366 | 23.56 | 908 | 97.94 | 0.1016 | 2000 |
700 | 354.55 | 37/3.493 | 24.45 | 978 | 102.20 | 0.0944 | 3500 |
750 | 380.20 | 37/3.617 | 25.32 | 1049 | 109.60 | 0.0880 | 3000 |
800 | 405.15 | 37/3.734 | 26.14 | 1117 | 116.80 | 0.0826 | 3000 |
900 | 456.16 | 37/3.962 | 27.73 | 1258 | 131.50 | 0.0733 | 3000 |
1000 | 506.71 | 37/4.176 | 26.23 | 1300 | 146.10 | 0.0660 | 2500 |
6201 All Aluminum Alloy Conductor ASTM B399 | |||||||
Code Name | Area | Size&Stranding of ACSR with equal diameter |
No. and diameter |
Overall diameter |
Weight | Nominal breaking load |
|
Nominal | Actual | ||||||
MCM | mm2 | AWG or MCM | mm | mm | kg/km | kN | |
AKRON | 30.58 | 15.48 | 6 | 7/1.68 | 5.04 | 42.7 | 4.92 |
ALTON | 48.69 | 24.71 | 4 | 7/2.12 | 6.35 | 68 | 7.84 |
AMES | 77.47 | 39.22 | 2 | 7/2.67 | 8.02 | 108 | 12.45 |
AZUSA | 123.3 | 62.38 | 1/0 | 7/3.37 | 10.11 | 172 | 18.97 |
ANAHEIM | 155.4 | 78.65 | 2/0 | 7/3.78 | 11.35 | 217 | 23.93 |
AMHERST | 195.7 | 99.22 | 3/0 | 7/4.25 | 12.75 | 273 | 30.18 |
ALLIANCE | 246.9 | 125.1 | 4/0 | 7/4.77 | 14.31 | 345 | 38.05 |
BUTTE | 312.8 | 158.6 | 266.8 | 19/3.26 | 16.3 | 437 | 48.76 |
CANTON | 394.5 | 199.9 | 336.4 | 19/3.66 | 18.3 | 551 | 58.91 |
CAIRO | 465.4 | 235.8 | 397.5 | 19/3.98 | 19.88 | 650 | 69.48 |
DARIEN | 559.5 | 283.5 | 477 | 19/4.36 | 21.79 | 781 | 83.52 |
ELGIN | 652.4 | 330.6 | 556.5 | 19/4.71 | 23.54 | 911 | 97.42 |
FLINT | 740.8 | 375.3 | 636 | 37/3.59 | 25.16 | 1035 | 108.21 |
GREELEY | 927.2 | 469.8 | 795 | 37/4.02 | 28.14 | 1295 | 135.47 |
AAAC (Characteristics of A3 Conductors) IEC 61089 | |||||||
Code number | Area | Number of wires | Diameter | Linear mass | Rated strength | D.C resistance | |
Wire | Cond | ||||||
mm2 | mm | mm | kg/km | kN | Ohm/km | ||
16 | 18.6 | 7 | 1.84 | 5.52 | 50.8 | 6.04 | 1.7896 |
25 | 29 | 7 | 2.3 | 6.9 | 79.5 | 9.44 | 1.1453 |
40 | 46.5 | 7 | 2.91 | 8.72 | 127.1 | 15.1 | 0.7158 |
63 | 73.2 | 7 | 3.65 | 10.9 | 200.2 | 23.06 | 0.4545 |
100 | 116 | 19 | 2.79 | 14 | 319.3 | 37.76 | 0.2877 |
125 | 145 | 19 | 3.12 | 15.6 | 399.2 | 47.2 | 0.2302 |
160 | 186 | 19 | 3.53 | 17.6 | 511 | 58.56 | 0.1798 |
200 | 232 | 19 | 3.95 | 19.7 | 638.7 | 73.2 | 0.1439 |
250 | 290 | 19 | 4.41 | 22.1 | 798.4 | 91.5 | 0.1151 |
315 | 366 | 37 | 3.55 | 24.8 | 1008.4 | 115.29 | 0.0916 |
400 | 465 | 37 | 4 | 28 | 1280.5 | 146.4 | 0.0721 |
450 | 523 | 37 | 4.24 | 29.7 | 1440.5 | 164.7 | 0.0641 |
500 | 581 | 37 | 4.47 | 31.3 | 1600.6 | 183 | 0.0577 |
560 | 651 | 61 | 3.69 | 33.2 | 1795.3 | 204.96 | 0.0516 |
630 | 732 | 61 | 3.91 | 35.2 | 2019.8 | 230.58 | 0.0458 |
710 | 825 | 61 | 4.15 | 37.3 | 2276.2 | 259.86 | 0.0407 |
800 | 930 | 61 | 4.4 | 39.6 | 2564.8 | 292.8 | 0.0361 |
900 | 1046 | 91 | 3.83 | 42.1 | 2888.3 | 329.4 | 0.0321 |
1000 | 1162 | 91 | 4.03 | 44.4 | 3209.3 | 366 | 0.0289 |
1120 | 1301 | 91 | 4.27 | 46.9 | 3594.4 | 409.92 | 0.0258 |
All Aluminium Alloy Conductors (AAAC) BS EN 50183 | |||||||
Designation | Area | Stranding wire Dia. | Overall Diameter |
Nominal Breaking Load |
Nominal DC Resistance at 20ºC |
Standard Weight | |
mm2 | No | Φ | mm | kN | Ohm/km | kg/km | |
ASTER 22 | 22 | 7 | 2 | 6 | 7.15 | 1.4989 | 60 |
ASTER 34.4 | 34.4 | 7 | 2.5 | 7.5 | 11.17 | 0.9593 | 93.8 |
ASTER 54.6 | 54.6 | 7 | 3.15 | 9.45 | 17.73 | 0.6042 | 148.9 |
ASTER 75.5 | 75.5 | 19 | 2.25 | 11.3 | 24.55 | 0.4388 | 207.4 |
ASTER 117 | 117 | 19 | 2.8 | 14 | 38.02 | 0.2833 | 321.2 |
ASTER 148 | 148.1 | 19 | 3.15 | 15.8 | 48.12 | 0.2239 | 406.5 |
ASTER 181.6 | 181.6 | 37 | 2.5 | 17.5 | 59.03 | 0.1831 | 500.3 |
ASTER 228 | 227.8 | 37 | 2.8 | 19.6 | 74.04 | 0.146 | 627.6 |
ASTER 288 | 288.3 | 37 | 3.15 | 22.1 | 93.71 | 0.1154 | 794.3 |
ASTER 366 | 366.2 | 37 | 3.55 | 24.9 | 115.36 | 0.0908 | 1008.9 |
ASTER 570 | 570.2 | 61 | 3.45 | 31.1 | 185.33 | 0.0585 | 1576 |
ASTER 851 | 850.7 | 91 | 3.45 | 38 | 276.47 | 0.0394 | 2360.7 |
ASTER 1144 | 1143.5 | 91 | 4 | 44 | 360.22 | 0.0293 | 3173.4 |
ASTER 1600 | 1595.9 | 127 | 4 | 52 | 502.72 | 0.021 | 4427.5 |
4.Packing
Packing in wooden drums,steel wooden drums or as customer’s requirement.
5.Customer Visit
We have a professional sales team with each of them has engaged in this job for 3-10 years, so that we can provide the comprehensive and professional technology for you. With the perfect quality and after sales service, till now we have exported to more than 80 countries, welcome to visit us and establish win-win establish relationship!
6.Production process:
AAAC conductor producing process is drawing stranding and cabling,our factory possess 2 subsidiaries,Zhulin factory is professional bare conductor workshop with 20 production line.
7.Certificate
As first rank of the cable supplier in China, we have obtained CCC, ISO9001, ISO14001, OHSAS certificates, passed the SGS and BV test, and our brand "RMJT" be given China famous brand.
8.About us:
People’s Cable Group Co., Ltd. was founded in 2007, located in Zhengzhou Gongyi economic development zone. Our company has 2 factories (Zhitian factory and Zhulin factory), occupies total area of more than 300,000 square meters, with building area 230,000 square meters.
Similar Or Related