AL/XLPE/CTS/PVC/SWA/PVC, Power Cable, 12/20 (24) KV, 3/C (IEC 60502-2)
The cable design conforms to IEC 60502 part 2. However if requested, we can separately offer guaranteed technical particulars for cables as per different international specifications or specific customer needs.

CONSTRUCTIONAL FEATURES

Conductor
Aluminum Conductors upto 1000 sq mm will be circular compacted & stranded and shall comply with IEC-60228 Class 2.

Conductor screen
This will be an extruded layer of semiconducting XLPE applied under simultaneous triple extrusion process over the conductor along with the insulation and the insulation screen.

Insulation
This will be an extruded layer of insulating grade XLPE applied over conductor screen under triple extrusion process along with conductor screen and insulation screen.

Insulation screen
This will be a layer of semiconducting XLPE which will be applied by tripe extrusion process over the insulation.

Metallic screen
It will consist of a layer of copper wires applied helically with overlap over insulation screen. Other combinations of metallic screens as per customer’s requirement can also be provided on request.

Inner Sheath (Bedding)
Extruded layer of PVC or PE is applied over the laid-up cores. PVC is normally of grade ST2 or PE of grade ST7 as per IEC 60502 Part 2.

Armour

The armour is applied over inner sheath. For Single core cables this is of aluminium wires and for multicore cables the armour can be of one among the following options: –
A) Galvanized steel wire.
B) Galvanized steel tape.
C) Galvanised steel strip.
The armour is applied helically over the bedding.

Outer sheath
An extruded layer is applied over the armour in case of armoured cables and over the laid up cores in case of unarmoured cables. Outer sheath material can be either PVC of grade ST2 or PE of grade ST7 as per IEC-60502 Part 2.

Section Conductor diameter Conductor weight Insulation thickness Bedding thickness Armour wire diameter Outer sheath thickness Cable overall diameter Cable weight Minimum bending radius of cable DC resistance of conductor at 20 °C Armour DC resistance at 20 °C Short circuit current rating of armour for 1 second
mm2 mm kg/km mm mm mm mm mm kg/km mm ohm/km ohm/km kA
35 6.9 280 5.5 1.5 2.5 2.8 58.0 4865 696 0.868 0.584 11.84
50 8.1 381 5.5 1.6 2.5 2.9 61.0 5305 732 0.641 0.552 12.53
70 9.7 553 5.5 1.6 2.5 3.1 65.0 5925 780 0.443 0.515 13.44
95 11.4 764 5.5 1.7 2.5 3.2 69.0 6605 828 0.320 0.482 14.35
120 12.9 965 5.5 1.7 3.15 3.3 73.5 8100 882 0.253 0.361 19.16
150 14.3 1186 5.5 1.8 3.15 3.4 77.0 8725 924 0.206 0.348 19.89
185 16.0 1500 5.5 1.9 3.15 3.6 81.5 9670 978 0.164 0.324 21.33
240 18.4 1967 5.5 2.0 3.15 3.7 87.0 10935 1044 0.125 0.299 23.14
300 20.6 2445 5.5 2.0 3.15 3.9 92.0 12125 1104 0.100 0.281 24.59
400 23.3 3126 5.5 2.2 3.15 4.1 99.5 13915 1194 0.0778 0.258 26.76