2kv VFD Rubber Insulated Power Cable
2kv VFD Rubber Insulated Power Cable
VFD
VFD
Low and Medium Voltage Cable
DC & AC
Rubber
Rubber CPE
Round Wire
Tinned Wire
ISO, CCC
VFD
Yifang
YIFANG
Steel Drum
4AWG TO 750MCM
China
8544492100
Product Description
VFD Power Cable, 2kV
Application
These 2kV power cables specifically engineered for use in variable frequency AC motor drive (VFD) applications. Suitable for use in Class I, Division 1 and Zone1 environments (armored and sheathed).
Construction
Conductor | Soft annealed flexible stranded tinned copper per IEEE 1580Table 11. |
Insulation | Cross linked flame retardant polyolefin, meeting the requirements for Type P of IEEE 1580 and Type X110 of UL 1309/CSA 245. |
Color | Gray with printed phase I.D. (Black-White-Red) |
Filers | Non-hygroscopic filler tape. |
Shield | Overall tinned copper braid plus aluminum/polyester tape providing 100% coverage. |
Inner Sheath | A black, arctic grade, flame retardant, oil, abrasion, chemical and sunlight resistant thermosetting compound meeting UL 1309/CSA 245 and IEEE 1580.(otional) |
Armor | Tinned copper basket weave wire armor per IEEE 1580and UL 1309/CSA 245(otional) |
Outer Sheath | A black, arctic grade, flame retardant, oil, abrasion, chemical and sunlight resistant thermosetting compound meeting UL1309/CSA 245 and IEEE 1580. |
Technical Information
Rated voltage 2kV |
Maximum conductor temperature + 90 °C |
Minimum recommended installation temperature -15 °C |
Severe cold durability: exceeds CSA coldbend/cold impact (-40°C/-35°C) |
Flame-retardant: IEC 60332-3-22 -test for bunched wires and cables, category A |
Cable Parameter
Unarmored | Armored | Ampacity | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Size AWG/ kcmil | Number of Conductors | Nominal Diameter Inches* | Weight Lbs./ 1000 Ft. | Nominal Diameter Inches* | Weight Lbs./ 1000 Ft. | Voltage Drop at 90°C Volts/Amp/ 1000 Ft. | Grounding Conductor Size (AWG) | 110°C | 100°C | 90°C | 75°C |
4 | 3 | 1.094 | 925 | 1.262 | 1128 | 0.584 | 3 x 12 | 99 | 92 | 83 | 70 |
2 | 3 | 1.235 | 1271 | 1.393 | 1512 | 0.368 | 3 x 10 | 131 | 122 | 111 | 93 |
1 | 3 | 1.341 | 1585 | 1.509 | 1836 | 0.301 | 3 x 10 | 153 | 143 | 131 | 110 |
1/0 | 3 | 1.450 | 1869 | 1.615 | 2137 | 0.246 | 3 x 10 | 176 | 164 | 150 | 126 |
2/0 | 3 | 1.580 | 2311 | 1.792 | 2660 | 0.202 | 3 x 10 | 201 | 188 | 173 | 145 |
4/0 | 3 | 1.900 | 3457 | 2.101 | 3864 | 0.139 | 3 x 8 | 270 | 252 | 232 | 194 |
262 | 3 | 2.050 | 4177 | 2.258 | 4661 | 0.120 | 3 x 6 | 315 | 294 | 273 | 228 |
313 | 3 | 2.130 | 4786 | 2.354 | 5288 | 0.105 | 3 x 6 | 344 | 321 | 298 | 249 |
373 | 3 | 2.275 | 5521 | 2.483 | 6052 | 0.092 | 3 x 6 | 387 | 361 | 332 | 277 |
444 | 3 | 2.425 | 6440 | 2.633 | 6994 | 0.083 | 3 x 6 | 440 | 411 | 382 | 319 |
535 | 3 | 2.643 | 7848 | 2.931 | 8478 | 0.075 | 3 x 6 | 498 | 443 | 407 | 340 |
646 | 3 | 2.920 | 9213 | 3.178 | 9888 | 0.068 | 3 x 4 | 553 | 516 | 474 | 396 |
777 | 3 | 3.102 | 10909 | 3.390 | 11803 | 0.062 | 3 x 4 | 602 | 562 | 516 | 431 |