Aacsr, Aluminium Alloy Conductors Steel Reinforced (DIN 48206)
Product Description
AACSR DIN 48206
Applications
Used as bare overhead transmission cable and as primary and secondary distribution cable. AACSR offers optimal strength for line design. Variable steel core stranding enables desired strength to be achieved without sacrificing ampacity.
Construction
AACSR is a concentrically stranded conductor composed of one or more layers of 6201 -T81 aluminum alloy wire stranded with a high-strength coated steel core. The core may be single wire or stranded depending on the size.
The proportions of aluminum alloy and steel can be varied to obtain the relation between currentcarrying capacity and mechanical strength best suited to each application.
Core wire for AACSR is available with Class A, B or C galvanizing; "aluminized" aluminum coated (AZ): Or aluminum clad (AW).
Additional corrosion protection is available through the application of grease to the core or infusion of the complete cable with grease.
GERMAN CONDUCTOR SIZES | ||||||||||
Conductor Size | Alloy Area | Steel Area | No. of Alloy | Diameter ofAlloy Wire | No. of Steel | Diameter Overall of Steel Wire | Diameter of Conductor | Linear Weight | Rated Strength | Max DO Resistance at 20 |
mm2 | mm2 | mm2 | Wires | mm | Wires | mm | mm | Kg/km | daN | Ω/km |
16/2.5 | 15.27 | 2.54 | 6 | 1.80 | 1 | 1.80 | 5.4 | 62 | 748 | 2.1800 |
25/4 | 23.86 | 3.98 | 6 | 2.25 | 1 | 2.25 | 6.8 | 97 | 1171 | 1.3952 |
35/6 | 34.35 | 5.73 | 6 | 2.70 | 4 | 2.70 | 8.1 | 140 | 1685 | 0.9689 |
44/32 | 43.98 | 31.67 | 14 | 2.00 | 7 | 2.40 | 11.2 | 373 | 5027 | 0.7625 |
50/8 | 48.25 | 8.04 | 6 | 3.20 | 1 | 3.20 | 9.6 | 196 | 2366 | 0.6898 |
50/30 | 51.17 | 29.85 | 12 | 2.33 | 7 | 2.33 | 11.7 | 378 | 5024 | 0.6547 |
70/12 | 69.89 | 11.40 | 26 | 1.85 | 7 | 1.44 | 11.7 | 284 | 3399 | 0.4791 |
95/15 | 94.39 | 15.33 | 26 | 2.15 | 7 | 1.67 | 13.6 | 383 | 4582 | 0.3547 |
95/55 | 96.51 | 56.30 | 12 | 3.20 | 7 | 3.20 | 16.0 | 714 | 9475 | 0.3471 |
105/75 | 105.67 | 75.55 | 14 | 3.10 | 19 | 2.25 | 17.5 | 899 | 12014 | 0.3174 |
120/20 | 121.57 | 19.85 | 26 | 2.44 | 7 | 1.90 | 15.5 | 494 | 5914 | 0.2754 |
120170 | 122.15 | 71.25 | 12 | 3.60 | 7 | 3.60 | 18.0 | 904 | 11912 | 0.2742 |
125/30 | 127.92 | 29.85 | 30 | 2.33 | 7 | 2.33 | 16.3 | 590 | 7280 | 0.2621 |
150/25 | 148.86 | 24.25 | 26 | 2.70 | 7 | 2.10 | 17.1 | 604 | 7236 | 0.2249 |
170/40 | 171.77 | 40.08 | 30 | 2.70 | 7 | 2.70 | 18.9 | 794 | 9775 | 0.1952 |
185/30 | 183.78 | 29.85 | 26 | 3.00 | 7 | 2.33 | 19.0 | 744 | 8922 | 0.1822 |
210/35 | 209.10 | 34.09 | 26 | 3.20 | 7 | 2.49 | 20.3 | 848 | 10167 | 0.1601 |
210/50 | 212.06 | 49.48 | 30 | 3.00 | 7 | 3.00 | 21.0 | 979 | 12068 | 0,1581 |
230/30 | 230.91 | 29.85 | 24 | 3.50 | 7 | 2.33 | 21.0 | 874 | 10308 | 0.1449 |
240/40 | 243.05 | 39.49 | 26 | 3.45 | 7 | 2.68 | 21.8 | 985 | 11802 | 0.1378 |
265/35 | 263.66 | 34.09 | 24 | 3.74 | 7 | 2.49 | 22.4 | 998 | 11771 | 0.1269 |
300/50 | 304.26 | 49.48 | 26 | 3.86 | 7 | 3.00 | 24.5 | 1233 | 14779 | 0.1101 |
305/40 | 304.62 | 39.49 | 54 | 2.68 | 7 | 2.68 | 24.1 | 1155 | 13612 | 0.1101 |
340/30 | 339.29 | 29.85 | 48 | 3.00 | 7 | 2.33 | 25.0 | 1174 | 13494 | 0.0988 |
380/50 | 381.70 | 49.48 | 54 | 3.00 | 7 | 3.00 | 27.0 | 1448 | 17056 | 0.0879 |
385/35 | 386.04 | 34.09 | 48 | 3.20 | 7 | 2.49 | 26.7 | 1336 | 15369 | 0.0868 |
435/55 | 434.29 | 56.30 | 54 | 3.20 | 7 | 3.20 | 28.8 | 1647 | 19406 | 0.0772 |
450/40 | 448.71 | 39.49 | 48 | 3.45 | 7 | 2.68 | 28.7 | 1553 | 17848 | 0.0747 |
490/65 | 490.28 | 63.55 | 54 | 3.40 | 7 | 3.40 | 30.6 | 1860 | 21907 | 0.0684 |
550/70 | 549.65 | 71.25 | 54 | 3.60 | 7 | 3.60 | 32.4 | 2085 | 24560 | 0.0610 |
560/50 | 561.70 | 49.48 | 48 | 3.86 | 7 | 3.00 | 32.2 | 1943 | 22348 | 0.0597 |
680/85 | 678.58 | 85.95 | 54 | 4.00 | 19 | 2.40 | 36.0 | 2564 | 30084 | 0.0494 |
- Next: Cu/PVC/PVC, LV Power Cable, 0.6/1 Kv (IEC 60502-1)
- Previous: E-Yy, Low Voltage Power Cable, 0.6/1 Kv, Cu/PVC/PVC (HD 603)
Contact us
Similar Or Related
-
Aster Cable 366mm2 37 Strands AAAC Bare Conductor for 90kV HV Substation
-
AAAC Bare Conductor 100mm2 7/4.26mm for Uganda 33kV Distribution Line
-
AAAC Bare Conductor 50mm2 7/3.02mm for Uganda 11kV Distribution Line
-
Aerial Bundled Conductor 70mm2 Hard drawn Aluminum ABC Cable for 400V Distribution Line
-
50mm2;AAAC PVC Covered Hazel Conductor BS 3242 for 11kV Distribution Line
-
Aacsr, Aluminium Alloy Conductors Steel Reinforced (DIN 48206)