AAC Conductor, Type ACP Wire, Greased All Aluminium Conductor (GOST 839-80)
Product Description
AAC conductor is widely used in power transmission lines with various voltage levels.
Since they have such good characteristics as simple structure, convenient installation and maintenance, low cost for the line, large transmission capacity and are also suitable for laying across rivers and valleys where special geographical teatures exist.
Specification:
All aluminium conductor (AAC)
Relative manufacturing standards:
GOST 839-80
Construction:
Aluminum alloy 1350-H-19 wires. Additional corrosion protection is available through the application of grease to the corrosion or infusion of the complete cable with grease.
Nominal Corss-section | Number of Wires | Wire Diameter | Calculated Cross-section | Overall Diameter | D.C. Resistance at 20 | Min. Breaking Load | Conductor Weight | Grease Weight |
mm2 | mm | mm2 | mm | Ω/km | kg/km | kg/km | ||
10 | 7 | 1,35 | 10,0 | 4,05 | 2,8631 | 1950 | 27,4 | – |
16 | 7 | 1,70 | 15,9 | 5,10 | 1,8007 | 3021 | 43,0 | 0,5 |
25 | 7 | 2,13 | 24,9 | 6,40 | 1,1498 | 4500 | 68,0 | 0,5 |
35 | 7 | 2,50 | 34,3 | 7,50 | 0,8347 | 5913 | 94,0 | 0,5 |
40 | 7 | 2,70 | 40,0 | 8,09 | 0,7157 | 6800 | 109,4 | – |
50 | 7 | 3,00 | 49,5 | 9,00 | 0,5784 | 8198 | 135,0 | 0,5 |
63 | 7 | 3,39 | 63,0 | 10,16 | 0,4544 | 10390 | 172,3 | – |
70 | 7 | 3,55 | 69,3 | 10,70 | 0,4131 | 11288 | 189,0 | 1,0 |
95 | 7 | 4,10 | 92,4 | 12,30 | 0,3114 | 14784 | 252,0 | 1,0 |
100 | 19 | 2,59 | 100,0 | 12,94 | 0,2877 | 17000 | 274,9 | – |
120 | 19 | 2,80 | 117,0 | 14,00 | 0,2459 | 19890 | 321,0 | 16 |
125 | 19 | 2,89 | 125,0 | 14,47 | 0,2301 | 21250 | 343,6 | – |
150 | 19 | 3,15 | 148,0 | 15,80 | 0,1944 | 24420 | 406,0 | 20 |
160 | 19 | 3,27 | 160,0 | 16,37 | 0,1798 | 26400 | 439,8 | – |
185 | 19 | 3,50 | 182,8 | 17,50 | 0,1574 | 29832 | 502,0 | 25 |
200 | 19 | 3,66 | 200,0 | 18,30 | 0,1438 | 32000 | 549,7 | – |
240 | 19 | 4,00 | 238,7 | 20,00 | 0,1205 | 38192 | 655,0 | 33 |
250 | 19 | 4,09 | 250,0 | 20,47 | 0,1150 | 40000 | 687,1 | – |
300 | 37 | 3,15 | 288,3 | 22,10 | 0,1000 | 47569 | 794,0 | 54 |
315 | 37 | 3,29 | 315,0 | 23,05 | 0,0915 | 51970 | 867,5 | – |
350 | 37 | 3,45 | 345,8 | 24,20 | 0,0833 | 57057 | 952,0 | 65 |
400 | 37 | 3,66 | 389,2 | 25,60 | 0,0740 | 63420 | 1072,0 | 73 |
450 | 37 | 3,90 | 449,1 | 27,30 | 0,0642 | 71856 | 1206,0 | 84 |
500 | 37 | 4,15 | 500,4 | 29,10 | 0,0576 | 80000 | 1378,0 | 94 |
550 | 61 | 3,37 | 544,0 | 30,30 | 0,0529 | 89760 | 1500,0 | 117 |
560 | 37 | 4,39 | 560,0 | 30,73 | 0,0531 | 89600 | 1542,2 | – |
600 | 61 | 3,50 | 586,8 | 31,50 | 0,0491 | 95632 | 1618,0 | 126 |
630 | 61 | 3,63 | 630,0 | 32,64 | 0,0458 | 100800 | 1738,4 | – |
650 | 61 | 3,66 | 641,7 | 32,90 | 0,0450 | 104575 | 1771,0 | 138 |
700 | 61 | 3,80 | 691,7 | 34,20 | 0,0417 | 112725 | 1902,0 | 149 |
710 | 61 | 3,85 | 710,0 | 34,65 | 0,0406 | 113600 | 1959,2 | – |
750 | 61 | 3,95 | 747,4 | 35,60 | 0,0386 | 119584 | 2062,0 | 161 |
- Next: ACSR/Tp, ACSR Twisted Pair Conductor (ASTM B 911)
- Previous: Ynaky, Power Cable, 0.6/1 Kv, High Flame Retardant Al/PVC/PVC (IEC 60502-1)
Contact us
Similar Or Related
-
AAC 95mm2 19/2.52 Conductor TIS 85-2548 for Transmission and distribution line
-
CU/XLPE/CTS/PVC 6.35/11kV Single Core Aluminum Power Cable IEC 60502-2
-
Al/XLPE/CTS/PVC 19/33kV 36kV Single Core Aluminum Power Cable IEC 60502-2
-
Yjlv XLPE Insulated and PVC Sheathed Power Cable Alu/XLPE/PVC
-
(AL/XLPE//SWA/PVC) Aluminum Conductor XLPE Insulated PVC Sheathed Yjlv22 Power Cable
-
AAC Conductor, Type ACP Wire, Greased All Aluminium Conductor (GOST 839-80)