8-15kv XLPE Insulated PVC Sheathed Unarmoured Power Cable

8-15kv XLPE Insulated PVC Sheathed Unarmoured Power Cable
15kv cable BM45
Construction, Underground
Low and Medium Voltage Cable
DC & AC
XLPE
PVC
Round Wire
Bare Copper Wire
ISO, CCC, CE, RoHS, UL, VDE
YJV
Yifang
Aluminum
Yifang Cable
Wooden or Wooden-Steel Drum
multicores
Zhengzhou, China
8544601200

Product Description

8-15kV XLPE Insulated PVC Sheathed Unarmoured Power Cable 100/133% Insulation Levels

100% Insulation Levels (single conductor)

Conductor

Insulation
thickness

( mm )

Sheath
thickness

( mm )

Overall Dia.
approx.

( mm )

AC Test
voltage

( kV / 5 min )

Cable weight
approx.

( kg / km )

Size

(AWG or MCM)

Construction

( No. / mm )

Outside Dia.

( mm )

2
1
1/0
2/0
3/0

7/2.47
19/1.69
C.C.
C.C.
C.C.

7.42
8.43
8.53
9.55
10.74

4.45
4.45
4.45
4.45
4.45

2.03
2.03
2.03
2.03
2.03

24.8
25.8
25.9
26.9
28.1

27
27
27
27
27

882
999
1101
1261
1461

4/0
250
300
350
400

C.C.
C.C.
C.C.
C.C.
C.C.

12.07
13.21
14.48
15.65
16.74

4.45
4.45
4.45
4.45
4.45

2.03
2.03
2.03
2.03
2.03

29.5
30.6
31.9
33.0
34.1

27
27
27
27
27

1707
1925
2194
2460
2733

500
550
750
1000

C.C.
C.C.
C.C.
C.C.

18.69
20.65
23.06
26.92

4.45
4.45
4.45
4.45

2.03
2.03
2.03
2.79

36.1
38.0
40.5
46.1

27
27
27
27

3252
3807
4585
6068

100% Insulation Levels (Three conductor)

Conductor

Insulation
thickness

( mm )

Sheath
thickness

( mm )

Overall Dia.
approx.

( mm )

AC Test
voltage

( kV / 5 min )

Cable weight
approx.

( kg / km )

Size

(AWG or MCM)

Construction

( No. / mm )

Outside Dia.

( mm )

2
1
1/0
2/0
3/0

7/2.47
19/1.69
C.C.
C.C.
C.C.

7.42
8.43
8.53
9.55
10.74

4.45
4.45
4.45
4.45
4.45

2.79
2.79
2.79
2.79
2.79

49.8
52.1
52.3
54.5
57.0

27
27
27
27
27

2895
3282
3589
4104
4750

4/0
250
300
350
400

C.C.
C.C.
C.C.
C.C.
C.C.

12.07
13.21
14.48
15.65
16.74

4.45
4.45
4.45
4.45
4.45

2.79
2.79
2.79
2.79
2.79

59.9
62.4
65.1
67.6
71.7

27
27
27
27
27

5537
6225
7083
7930
9088

133% Insulation Levels (single conductor)

Conductor

Insulation
thickness

( mm )

Sheath
thickness

( mm )

Overall Dia.
approx.

( mm )

AC Test
voltage

( kV / 5 min )

Cable weight
approx.

( kg / km )

Size

(AWG or MCM)

Construction

( No. / mm )

Outside Dia.

( mm )

1
1/0
2/0
3/0
4/0

19/1.69
C.C.
C.C.
C.C.
C.C.

8.43
8.53
9.55
10.74
12.07

5.46
5.46
5.46
5.46
5.46

2.03
2.03
2.03
2.03
2.03

28.1
28.1
29.2
30.4
31.7

33
33
33
33
33

1103
1205
1369
1572
1822

250
300
350
400
500

C.C.
C.C.
C.C.
C.C.
C.C.

13.21
14.48
15.65
16.74
18.69

5.46
5.46
5.46
5.46
5.46

2.03
2.03
2.03
2.03
2.03

32.8
34.1
35.3
36.4
38.3

33
33
33
33
33

2044
2317
2587
2863
3388

550
750
1000

C.C.
C.C.
C.C.

20.65
23.06
26.92

5.46
5.46
5.46

2.03
2.79
2.79

40.3
44.5
48.3

33
33
33

3951
4919
6240

133% Insulation Levels (Three conductor)

Conductor

Insulation
thickness

( mm )

Sheath
thickness

( mm )

Overall Dia.
approx.

( mm )

AC Test
voltage

( kV / 5 min )

Cable weight
approx.

( kg / km )

Size

(AWG or MCM)

Construction

( No. / mm )

Outside Dia.

( mm )

1
1/0
2/0
3/0
4/0

19/1.69
C.C.
C.C.
C.C.
C.C.

8.43
8.53
9.55
10.74
12.07

5.46
5.46
5.46
5.46
5.46

2.79
2.79
2.79
2.79
2.79

56.9
57.1
59.3
61.8
64.7

33
33
33
33
33

3652
3974
4498
5156
5956

250
300
350
400

C.C.
C.C.
C.C.
C.C.

13.21
14.48
15.65
16.74

5.46
5.46
5.46
5.46

2.79
2.79
2.79
2.79

67.1
69.9
74.1
76.4

33
33
33
33

6669
7536
8699
9601

Tags: , ,

Similar Or Related





Please enter your first and last name separated by a space (e.g. Jane Miller)




Success! Thanks for Your Request.
Error! Please Try Again.