0.6/1kv Low Voltage Aluminum PVC Insulated PVC Sheath Electrical Power Cable
Product Description
1. Operating Characteristics
Rated voltage: 0.6/1(1.2)kV
Max. Permissible continuous operating temperature of conductor: 70° C
Max. Temperature of conductor during short-circuit (5s max. Duration) shall not exceed:
Nominal cross section of conductor ≤ 300mm2: 160° C;
Nominal cross section of conductor >300mm2: 140° C
The ambient temperature under installation should not be lower than: 0 ° C
The bending radius of cable is recommended as following:
For single core cable: Not less than 20 times of the diameter of cable
For multi-core cable: Not less than 15 times of the diameter of cable
2. Application
The cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid indoors, in tunnel, in cable trench or in conduit, unable to bear external mechanical force.
3. Manufacturing Standards
IEC 60502-1 & Chinese national standard GB/T 12706-2008 We can produce above cables according to popular international standards such as ASTM, BS, DIN, NF &AS/NZ also.
Main technical data of 0.6/1KV, Single core, Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables, CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
Cable size | Conductor type | Nominal thickness of PVC insulation (mm) |
Nominal thickness of steel tape(mm) |
Nominal thickness of PVC sheath(mm) |
Approx. cable overall diameter (mm) |
Max. D.C resistance @ 200C (Ω/km) |
1x10mm2 | RM | 1.0 | 0.2 | 1.8 | 12.9 | 3.08 |
1x16mm2 | RM | 1.0 | 0.2 | 1.8 | 13.9 | 1.91 |
1x25mm2 | RM | 1.2 | 0.2 | 1.8 | 14.3 | 1.20 |
1x35mm2 | RM | 1.2 | 0.2 | 1.8 | 15.5 | 0.868 |
1x50mm2 | RM | 1.4 | 0.2 | 1.8 | 17.2 | 0.641 |
1x70mm2 | RM | 1.4 | 0.2 | 1.8 | 19.0 | 0.443 |
1x95mm2 | RM | 1.6 | 0.2 | 1.8 | 21.3 | 0.320 |
1x120mm2 | RM | 1.6 | 0.2 | 1.8 | 22.9 | 0.253 |
1x150mm2 | RM | 1.8 | 0.2 | 1.8 | 24.9 | 0.206 |
1x185mm2 | RM | 2.0 | 0.2 | 1.8 | 27.1 | 0.164 |
1x240mm2 | RM | 2.2 | 0.2 | 1.8 | 30.2 | 0.125 |
1x300mm2 | RM | 2.4 | 0.5 | 2.0 | 35.2 | 0.100 |
1x400mm2 | RM | 2.6 | 0.5 | 2.1 | 38.8 | 0.0778 |
1x500mm2 | RM | 2.8 | 0.5 | 2.2 | 43.0 | 0.0605 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
Main technical data of 0.6/1KV, two cores, Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables, CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
Cable size | Conductor type | Nominal thickness of PVC insulation (mm) | Nominal thickness of steel tape(mm) | Nominal thickness of PVC sheath(mm) | Approx. cable overall diameter (mm) | Max. D.C resistance @ 200C (Ω/km) |
2×1.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 12.9 | 18.1 |
2×2.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 13.7 | 12.1 |
2x4mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 15.5 | 7.41 |
2x6mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 16.5 | 4.61 |
2x10mm2 | RM | 1.0 | 0.2 | 1.8 | 19.1 | 3.08 |
2x16mm2 | RM | 1.0 | 0.2 | 1.8 | 21.2 | 1.91 |
2x25mm2 | SM | 1.2 | 0.2 | 1.8 | 18.6 | 1.20 |
2x35mm2 | SM | 1.2 | 0.2 | 1.8 | 20.1 | 0.868 |
2x50mm2 | SM | 1.4 | 0.2 | 1.8 | 22.4 | 0.641 |
2x70mm2 | SM | 1.4 | 0.5 | 2.0 | 26.9 | 0.443 |
2x95mm2 | SM | 1.6 | 0.5 | 2.1 | 30.3 | 0.320 |
2x120mm2 | SM | 1.6 | 0.5 | 2.2 | 32.6 | 0.253 |
2x150mm2 | SM | 1.8 | 0.5 | 2.3 | 35.5 | 0.206 |
2x185mm2 | SM | 2.0 | 0.5 | 2.5 | 39.1 | 0.164 |
2x240mm2 | SM | 2.2 | 0.5 | 2.7 | 43.6 | 0.125 |
2x300mm2 | SM | 2.4 | 0.5 | 2.8 | 47.6 | 0.100 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
Main technical data of 0.6/1KV, three cores, Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables, CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
Cable size | Conductor type | Nominal thickness of PVC insulation (mm) |
Nominal thickness of steel tape(mm) |
Nominal thickness of PVC sheath(mm) |
Approx. cable overall diameter (mm) |
Max. D.C resistance @ 200C (Ω/km) |
3×1.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 13.4 | 18.1 |
3×2.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 14.3 | 12.1 |
3x4mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 16.1 | 7.41 |
3x6mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 17.2 | 4.61 |
3x10mm2 | RM | 1.0 | 0.2 | 1.8 | 20.0 | 3.08 |
3x16mm2 | RM | 1.0 | 0.2 | 1.8 | 22.3 | 1.91 |
3x25mm2 | SM | 1.2 | 0.2 | 1.8 | 21.3 | 1.20 |
3x35mm2 | SM | 1.2 | 0.2 | 1.8 | 23.2 | 0.868 |
3x50mm2 | SM | 1.4 | 0.2 | 1.9 | 26.2 | 0.641 |
3x70mm2 | SM | 1.4 | 0.5 | 2.0 | 31.1 | 0.443 |
3x95mm2 | SM | 1.6 | 0.5 | 2.2 | 35.4 | 0.320 |
3x120mm2 | SM | 1.6 | 0.5 | 2.3 | 38.2 | 0.253 |
3x150mm2 | SM | 1.8 | 0.5 | 2.4 | 41.7 | 0.206 |
3x185mm2 | SM | 2.0 | 0.5 | 2.6 | 46.0 | 0.164 |
3x240mm2 | SM | 2.2 | 0.5 | 2.8 | 51.4 | 0.125 |
3x300mm2 | SM | 2.4 | 0.5 | 3.0 | 56.5 | 0.100 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
Main technical data of 0.6/1KV, 3+1 cores, Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables, CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
Cable size |
Conductor type | Nominal thickness of PVC insulation(mm) |
Nominal thickness of steel tape(mm) |
Nominal thickness of PVC sheath (mm) |
Approx. cable overall diameter (mm) |
Max. D.C resistance @ 200C (Ω/km) |
|||
Phase core |
Earth core |
Phase core |
Earth core |
Phase core |
Earth core |
||||
3×2.5+1.5mm2 | RE | RE | 0.8 | 0.8 | 0.2 | 1.8 | 14.9 | 12.1 | 18.1 |
3×4+2.5mm2 | RE | RE | 1.0 | 0.8 | 0.2 | 1.8 | 16.7 | 7.41 | 12.1 |
3×6+4mm2 | RE | RE | 1.0 | 1.0 | 0.2 | 1.8 | 18.2 | 4.61 | 7.41 |
3×10+6mm2 | RM | RE | 1.0 | 1.0 | 0.2 | 1.8 | 20.8 | 3.08 | 4.61 |
3×16+10mm2 | RM | RM | 1.0 | 1.0 | 0.2 | 1.8 | 23.5 | 1.91 | 3.08 |
3×25+16mm2 | SM | RM | 1.2 | 1.0 | 0.2 | 1.8 | 24.2 | 1.20 | 1.91 |
3×35+16mm2 | SM | RM | 1.2 | 1.0 | 0.2 | 1.8 | 25.9 | 0.868 | 1.91 |
3×50+25mm2 | SM | SM | 1.4 | 1.2 | 0.5 | 2.0 | 30.5 | 0.641 | 1.20 |
3×70+35mm2 | SM | SM | 1.4 | 1.2 | 0.5 | 2.1 | 33.9 | 0.443 | 0.868 |
3×95+50mm2 | SM | SM | 1.6 | 1.4 | 0.5 | 2.3 | 38.5 | 0.320 | 0.641 |
3×120+70mm2 | SM | SM | 1.6 | 1.4 | 0.5 | 2.4 | 41.8 | 0.253 | 0.443 |
3×150+70mm2 | SM | SM | 1.8 | 1.4 | 0.5 | 2.5 | 45.0 | 0.206 | 0.443 |
3×185+95mm2 | SM | SM | 2.0 | 1.6 | 0.5 | 2.7 | 49.9 | 0.164 | 0.320 |
3×240+120mm2 | SM | SM | 2.2 | 1.6 | 0.5 | 2.9 | 55.5 | 0.125 | 0.253 |
3×300+150mm2 | SM | SM | 2.4 | 1.8 | 0.5 | 3.1 | 61.0 | 0.100 | 0.206 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
Main technical data of 0.6/1KV, four cores, Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables
CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
Cable size | Conductor type | Nominal thickness of PVC insulation (mm) | Nominal thickness of steel tape(mm) | Nominal thickness of PVC sheath(mm) | Approx. cable overall diameter (mm) | Max. D.C resistance @ 200C (Ω/km) |
4×1.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 14.2 | 18.1 |
4×2.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 15.1 | 12.1 |
4x4mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 17.2 | 7.41 |
4x6mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 18.5 | 4.61 |
4x10mm2 | RM | 1.0 | 0.2 | 1.8 | 21.6 | 3.08 |
4x16mm2 | RM | 1.0 | 0.2 | 1.8 | 24.1 | 1.91 |
4x25mm2 | SM | 1.2 | 0.2 | 1.8 | 23.8 | 1.20 |
4x35mm2 | SM | 1.2 | 0.2 | 1.8 | 25.9 | 0.868 |
4x50mm2 | SM | 1.4 | 0.5 | 2.0 | 31.4 | 0.641 |
4x70mm2 | SM | 1.4 | 0.5 | 2.1 | 35.0 | 0.443 |
4x95mm2 | SM | 1.6 | 0.5 | 2.3 | 39.9 | 0.320 |
4x120mm2 | SM | 1.6 | 0.5 | 2.4 | 43.1 | 0.253 |
4x150mm2 | SM | 1.8 | 0.5 | 2.6 | 47.3 | 0.206 |
4x185mm2 | SM | 2.0 | 0.5 | 2.8 | 52.3 | 0.164 |
4x240mm2 | SM | 2.2 | 0.5 | 3.0 | 58.4 | 0.125 |
4x300mm2 | SM | 2.4 | 0.5 | 3.2 | 64.3 | 0.100 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
Main technical data of 0.6/1KV, five cores, Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables , CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
Cable size | Conductor type | Nominal thickness of PVC insulation (mm) |
Nominal thickness of steel tape(mm) |
Nominal thickness of PVC sheath(mm) |
Approx. cable overall diameter (mm) |
Max. D.C resistance @ 200C (Ω/km) |
5×1.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 15.0 | 18.1 |
5×2.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 16.1 | 12.1 |
5x4mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 18.5 | 7.41 |
5x6mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 19.8 | 4.61 |
5x10mm2 | RM | 1.0 | 0.2 | 1.8 | 23.3 | 3.08 |
5x16mm2 | RM | 1.0 | 0.2 | 1.8 | 26.2 | 1.91 |
5x25mm2 | SM | 1.2 | 0.2 | 1.8 | 26.1 | 1.20 |
5x35mm2 | SM | 1.2 | 0.5 | 2.0 | 30.7 | 0.868 |
5x50mm2 | SM | 1.4 | 0.5 | 2.1 | 34.6 | 0.641 |
5x70mm2 | SM | 1.4 | 0.5 | 2.3 | 38.9 | 0.443 |
5x95mm2 | SM | 1.6 | 0.5 | 2.5 | 44.4 | 0.320 |
5x120mm2 | SM | 1.6 | 0.5 | 2.6 | 47.9 | 0.253 |
5x150mm2 | SM | 1.8 | 0.5 | 2.8 | 52.6 | 0.206 |
5x185mm2 | SM | 2.0 | 0.5 | 2.9 | 57.9 | 0.164 |
5x240mm2 | SM | 2.2 | 0.5 | 3.2 | 65.0 | 0.125 |
5x300mm2 | SM | 2.4 | 0.5 | 3.4 | 71.6 | 0.100 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
Main technical data of 0.6/1KV, 4+1 cores, Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables, CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
Cable size |
Conductor type | Nominal thickness of PVC insulation(mm) |
Nominal thickness of steel tape(mm) |
Nominal thickness of PVC sheath (mm) |
Approx. cable overall diameter (mm) |
Max. D.C resistance @ 200C (Ω/km) |
|||
Phase core |
Earth core |
Phase core |
Earth core |
Phase core |
Earth core |
||||
4×2.5+1.5mm2 | RE | RE | 0.8 | 0.8 | 0.2 | 1.8 | 15.9 | 12.1 | 18.1 |
4×4+2.5mm2 | RE | RE | 1.0 | 0.8 | 0.2 | 1.8 | 18.0 | 7.41 | 12.1 |
4×6+4mm2 | RE | RE | 1.0 | 1.0 | 0.2 | 1.8 | 19.6 | 4.61 | 7.41 |
4×10+6mm2 | RM | RE | 1.0 | 1.0 | 0.2 | 1.8 | 22.6 | 3.08 | 4.61 |
4×16+10mm2 | RM | RM | 1.0 | 1.0 | 0.2 | 1.8 | 25.6 | 1.91 | 3.08 |
4×25+16mm2 | SM | RM | 1.2 | 1.0 | 0.2 | 1.8 | 26.6 | 1.20 | 1.91 |
4×35+16mm2 | SM | RM | 1.2 | 1.0 | 0.2 | 1.9 | 28.7 | 0.868 | 1.91 |
4×50+25mm2 | SM | SM | 1.4 | 1.2 | 0.5 | 2.1 | 33.8 | 0.641 | 1.20 |
4×70+35mm2 | SM | SM | 1.4 | 1.2 | 0.5 | 2.3 | 37.8 | 0.443 | 0.868 |
4×95+50mm2 | SM | SM | 1.6 | 1.4 | 0.5 | 2.4 | 42.8 | 0.320 | 0.641 |
4×120+70mm2 | SM | SM | 1.6 | 1.4 | 0.5 | 2.6 | 46.6 | 0.253 | 0.443 |
4×150+70mm2 | SM | SM | 1.8 | 1.4 | 0.5 | 2.7 | 50.4 | 0.206 | 0.443 |
4×185+95mm2 | SM | SM | 2.0 | 1.6 | 0.5 | 2.9 | 55.9 | 0.164 | 0.320 |
4×240+120mm2 | SM | SM | 2.2 | 1.6 | 0.5 | 3.1 | 62.2 | 0.125 | 0.253 |
4×300+150mm2 | SM | SM | 2.4 | 1.8 | 0.5 | 3.3 | 68.4 | 0.100 | 0.206 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
- Next: 0.6/1kv Nyy-J Nyy-O Copper PVC Insulation PVC Sheath Power Cable
- Previous: DIN VDE0276-603 Standard Copper Electrical Kabel Nyy Power Cable
Contact us
Similar Or Related
-
Low Voltage Aluminum Power Cable 4X50mm2 4X35mm2 Al/XLPE/Swa/PVC Yjlv22 Power Cable
-
Aluminum Cable Zr Yjlv22 0.6/1kv XLPE Insulated Steel Tape Armoured Underground Power Cable
-
0.6/1kv 150mm2 Copper Conductor XLPE Insulation PVC Sheath Power Cable
-
0.6/1kv Low Voltage Aluminum PVC Insulated PVC Sheath Electrical Power Cable