0.6/1kv Copper Conductor PVC Insulated PVC Jacket Electric Cable
More product about Electrical CableProduct Description
Rated Voltage: 0.6/1kv Conductor material: copper
Insulation material: PVC Sheath Material: PVC
Core: 1,2,3, 4,5, 3+1,3+2,4+1 Certificate: ISO, CCC,BV
Standard: GB/T12706-2002
Trademark: jytop or OEM
Installation temperature: not lower than 0°C
Operating Temperature: 70°C Max
Short-circuit Max. Conductor Temperature: 160°C
Short-circuit Max : 5s
Bending radius: not be less than 15 times of cable outer diameter
Application: Being laid indoors, in tunnels or in ducts, unable to bear mechanical external force.
Technical data of 0.6/1KV, Single core, Copper or Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables, CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
Cable size | Conductor type | Nominal thickness of PVC insulation (mm) |
Nominal thickness of steel tape(mm) |
Nominal thickness of PVC sheath(mm) |
Approx. cable overall diameter (mm) |
Max. D.C resistance @ 200C (Ω/km) |
1x10mm2 | RM | 1.0 | 0.2 | 1.8 | 12.9 | 3.08 |
1x16mm2 | RM | 1.0 | 0.2 | 1.8 | 13.9 | 1.91 |
1x25mm2 | RM | 1.2 | 0.2 | 1.8 | 14.3 | 1.20 |
1x35mm2 | RM | 1.2 | 0.2 | 1.8 | 15.5 | 0.868 |
1x50mm2 | RM | 1.4 | 0.2 | 1.8 | 17.2 | 0.641 |
1x70mm2 | RM | 1.4 | 0.2 | 1.8 | 19.0 | 0.443 |
1x95mm2 | RM | 1.6 | 0.2 | 1.8 | 21.3 | 0.320 |
1x120mm2 | RM | 1.6 | 0.2 | 1.8 | 22.9 | 0.253 |
1x150mm2 | RM | 1.8 | 0.2 | 1.8 | 24.9 | 0.206 |
1x185mm2 | RM | 2.0 | 0.2 | 1.8 | 27.1 | 0.164 |
1x240mm2 | RM | 2.2 | 0.2 | 1.8 | 30.2 | 0.125 |
1x300mm2 | RM | 2.4 | 0.5 | 2.0 | 35.2 | 0.100 |
1x400mm2 | RM | 2.6 | 0.5 | 2.1 | 38.8 | 0.0778 |
1x500mm2 | RM | 2.8 | 0.5 | 2.2 | 43.0 | 0.0605 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
Technical data of 0.6/1KV, two cores, Copper or Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables, CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
Cable size | Conductor type | Nominal thickness of PVC insulation (mm) | Nominal thickness of steel tape(mm) | Nominal thickness of PVC sheath(mm) | Approx. cable overall diameter (mm) | Max. D.C resistance @ 200C (Ω/km) |
2×1.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 12.9 | 18.1 |
2×2.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 13.7 | 12.1 |
2x4mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 15.5 | 7.41 |
2x6mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 16.5 | 4.61 |
2x10mm2 | RM | 1.0 | 0.2 | 1.8 | 19.1 | 3.08 |
2x16mm2 | RM | 1.0 | 0.2 | 1.8 | 21.2 | 1.91 |
2x25mm2 | SM | 1.2 | 0.2 | 1.8 | 18.6 | 1.20 |
2x35mm2 | SM | 1.2 | 0.2 | 1.8 | 20.1 | 0.868 |
2x50mm2 | SM | 1.4 | 0.2 | 1.8 | 22.4 | 0.641 |
2x70mm2 | SM | 1.4 | 0.5 | 2.0 | 26.9 | 0.443 |
2x95mm2 | SM | 1.6 | 0.5 | 2.1 | 30.3 | 0.320 |
2x120mm2 | SM | 1.6 | 0.5 | 2.2 | 32.6 | 0.253 |
2x150mm2 | SM | 1.8 | 0.5 | 2.3 | 35.5 | 0.206 |
2x185mm2 | SM | 2.0 | 0.5 | 2.5 | 39.1 | 0.164 |
2x240mm2 | SM | 2.2 | 0.5 | 2.7 | 43.6 | 0.125 |
2x300mm2 | SM | 2.4 | 0.5 | 2.8 | 47.6 | 0.100 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
Technical data of 0.6/1KV, three cores, Copper or Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables, CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
Cable size | Conductor type | Nominal thickness of PVC insulation (mm) |
Nominal thickness of steel tape(mm) |
Nominal thickness of PVC sheath(mm) |
Approx. cable overall diameter (mm) |
Max. D.C resistance @ 200C (Ω/km) |
3×1.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 13.4 | 18.1 |
3×2.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 14.3 | 12.1 |
3x4mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 16.1 | 7.41 |
3x6mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 17.2 | 4.61 |
3x10mm2 | RM | 1.0 | 0.2 | 1.8 | 20.0 | 3.08 |
3x16mm2 | RM | 1.0 | 0.2 | 1.8 | 22.3 | 1.91 |
3x25mm2 | SM | 1.2 | 0.2 | 1.8 | 21.3 | 1.20 |
3x35mm2 | SM | 1.2 | 0.2 | 1.8 | 23.2 | 0.868 |
3x50mm2 | SM | 1.4 | 0.2 | 1.9 | 26.2 | 0.641 |
3x70mm2 | SM | 1.4 | 0.5 | 2.0 | 31.1 | 0.443 |
3x95mm2 | SM | 1.6 | 0.5 | 2.2 | 35.4 | 0.320 |
3x120mm2 | SM | 1.6 | 0.5 | 2.3 | 38.2 | 0.253 |
3x150mm2 | SM | 1.8 | 0.5 | 2.4 | 41.7 | 0.206 |
3x185mm2 | SM | 2.0 | 0.5 | 2.6 | 46.0 | 0.164 |
3x240mm2 | SM | 2.2 | 0.5 | 2.8 | 51.4 | 0.125 |
3x300mm2 | SM | 2.4 | 0.5 | 3.0 | 56.5 | 0.100 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
Technical data of 0.6/1KV, 3+1 cores, Copper or Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables, CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
Cable size |
Conductor type | Nominal thickness of PVC insulation(mm) |
Nominal thickness of steel tape(mm) |
Nominal thickness of PVC sheath (mm) |
Approx. cable overall diameter (mm) |
Max. D.C resistance @ 200C (Ω/km) |
|||
Phase core |
Earth core |
Phase core |
Earth core |
Phase core |
Earth core |
||||
3×2.5+1.5mm2 | RE | RE | 0.8 | 0.8 | 0.2 | 1.8 | 14.9 | 12.1 | 18.1 |
3×4+2.5mm2 | RE | RE | 1.0 | 0.8 | 0.2 | 1.8 | 16.7 | 7.41 | 12.1 |
3×6+4mm2 | RE | RE | 1.0 | 1.0 | 0.2 | 1.8 | 18.2 | 4.61 | 7.41 |
3×10+6mm2 | RM | RE | 1.0 | 1.0 | 0.2 | 1.8 | 20.8 | 3.08 | 4.61 |
3×16+10mm2 | RM | RM | 1.0 | 1.0 | 0.2 | 1.8 | 23.5 | 1.91 | 3.08 |
3×25+16mm2 | SM | RM | 1.2 | 1.0 | 0.2 | 1.8 | 24.2 | 1.20 | 1.91 |
3×35+16mm2 | SM | RM | 1.2 | 1.0 | 0.2 | 1.8 | 25.9 | 0.868 | 1.91 |
3×50+25mm2 | SM | SM | 1.4 | 1.2 | 0.5 | 2.0 | 30.5 | 0.641 | 1.20 |
3×70+35mm2 | SM | SM | 1.4 | 1.2 | 0.5 | 2.1 | 33.9 | 0.443 | 0.868 |
3×95+50mm2 | SM | SM | 1.6 | 1.4 | 0.5 | 2.3 | 38.5 | 0.320 | 0.641 |
3×120+70mm2 | SM | SM | 1.6 | 1.4 | 0.5 | 2.4 | 41.8 | 0.253 | 0.443 |
3×150+70mm2 | SM | SM | 1.8 | 1.4 | 0.5 | 2.5 | 45.0 | 0.206 | 0.443 |
3×185+95mm2 | SM | SM | 2.0 | 1.6 | 0.5 | 2.7 | 49.9 | 0.164 | 0.320 |
3×240+120mm2 | SM | SM | 2.2 | 1.6 | 0.5 | 2.9 | 55.5 | 0.125 | 0.253 |
3×300+150mm2 | SM | SM | 2.4 | 1.8 | 0.5 | 3.1 | 61.0 | 0.100 | 0.206 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
Technical data of 0.6/1KV, four cores, Copper or Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables
CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
Cable size | Conductor type | Nominal thickness of PVC insulation (mm) | Nominal thickness of steel tape(mm) | Nominal thickness of PVC sheath(mm) | Approx. cable overall diameter (mm) | Max. D.C resistance @ 200C (Ω/km) |
4×1.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 14.2 | 18.1 |
4×2.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 15.1 | 12.1 |
4x4mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 17.2 | 7.41 |
4x6mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 18.5 | 4.61 |
4x10mm2 | RM | 1.0 | 0.2 | 1.8 | 21.6 | 3.08 |
4x16mm2 | RM | 1.0 | 0.2 | 1.8 | 24.1 | 1.91 |
4x25mm2 | SM | 1.2 | 0.2 | 1.8 | 23.8 | 1.20 |
4x35mm2 | SM | 1.2 | 0.2 | 1.8 | 25.9 | 0.868 |
4x50mm2 | SM | 1.4 | 0.5 | 2.0 | 31.4 | 0.641 |
4x70mm2 | SM | 1.4 | 0.5 | 2.1 | 35.0 | 0.443 |
4x95mm2 | SM | 1.6 | 0.5 | 2.3 | 39.9 | 0.320 |
4x120mm2 | SM | 1.6 | 0.5 | 2.4 | 43.1 | 0.253 |
4x150mm2 | SM | 1.8 | 0.5 | 2.6 | 47.3 | 0.206 |
4x185mm2 | SM | 2.0 | 0.5 | 2.8 | 52.3 | 0.164 |
4x240mm2 | SM | 2.2 | 0.5 | 3.0 | 58.4 | 0.125 |
4x300mm2 | SM | 2.4 | 0.5 | 3.2 | 64.3 | 0.100 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
Technical data of 0.6/1KV, five cores, Copper or Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables , CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
Cable size | Conductor type | Nominal thickness of PVC insulation (mm) |
Nominal thickness of steel tape(mm) |
Nominal thickness of PVC sheath(mm) |
Approx. cable overall diameter (mm) |
Max. D.C resistance @ 200C (Ω/km) |
5×1.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 15.0 | 18.1 |
5×2.5mm2 | RE or RM | 0.8 | 0.2 | 1.8 | 16.1 | 12.1 |
5x4mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 18.5 | 7.41 |
5x6mm2 | RE or RM | 1.0 | 0.2 | 1.8 | 19.8 | 4.61 |
5x10mm2 | RM | 1.0 | 0.2 | 1.8 | 23.3 | 3.08 |
5x16mm2 | RM | 1.0 | 0.2 | 1.8 | 26.2 | 1.91 |
5x25mm2 | SM | 1.2 | 0.2 | 1.8 | 26.1 | 1.20 |
5x35mm2 | SM | 1.2 | 0.5 | 2.0 | 30.7 | 0.868 |
5x50mm2 | SM | 1.4 | 0.5 | 2.1 | 34.6 | 0.641 |
5x70mm2 | SM | 1.4 | 0.5 | 2.3 | 38.9 | 0.443 |
5x95mm2 | SM | 1.6 | 0.5 | 2.5 | 44.4 | 0.320 |
5x120mm2 | SM | 1.6 | 0.5 | 2.6 | 47.9 | 0.253 |
5x150mm2 | SM | 1.8 | 0.5 | 2.8 | 52.6 | 0.206 |
5x185mm2 | SM | 2.0 | 0.5 | 2.9 | 57.9 | 0.164 |
5x240mm2 | SM | 2.2 | 0.5 | 3.2 | 65.0 | 0.125 |
5x300mm2 | SM | 2.4 | 0.5 | 3.4 | 71.6 | 0.100 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor
Technical data of 0.6/1KV, 4+1 cores, Copper or Aluminum conductor, PVC insulated, double steel tape armored and PVC or PE sheath cables, CABLE CONSTRUCTION 0.6/1KV AL/PVC/DSTA/PVC or PE
Cable size |
Conductor type | Nominal thickness of PVC insulation(mm) |
Nominal thickness of steel tape(mm) |
Nominal thickness of PVC sheath (mm) |
Approx. cable overall diameter (mm) |
Max. D.C resistance @ 200C (Ω/km) |
|||
Phase core |
Earth core |
Phase core |
Earth core |
Phase core |
Earth core |
||||
4×2.5+1.5mm2 | RE | RE | 0.8 | 0.8 | 0.2 | 1.8 | 15.9 | 12.1 | 18.1 |
4×4+2.5mm2 | RE | RE | 1.0 | 0.8 | 0.2 | 1.8 | 18.0 | 7.41 | 12.1 |
4×6+4mm2 | RE | RE | 1.0 | 1.0 | 0.2 | 1.8 | 19.6 | 4.61 | 7.41 |
4×10+6mm2 | RM | RE | 1.0 | 1.0 | 0.2 | 1.8 | 22.6 | 3.08 | 4.61 |
4×16+10mm2 | RM | RM | 1.0 | 1.0 | 0.2 | 1.8 | 25.6 | 1.91 | 3.08 |
4×25+16mm2 | SM | RM | 1.2 | 1.0 | 0.2 | 1.8 | 26.6 | 1.20 | 1.91 |
4×35+16mm2 | SM | RM | 1.2 | 1.0 | 0.2 | 1.9 | 28.7 | 0.868 | 1.91 |
4×50+25mm2 | SM | SM | 1.4 | 1.2 | 0.5 | 2.1 | 33.8 | 0.641 | 1.20 |
4×70+35mm2 | SM | SM | 1.4 | 1.2 | 0.5 | 2.3 | 37.8 | 0.443 | 0.868 |
4×95+50mm2 | SM | SM | 1.6 | 1.4 | 0.5 | 2.4 | 42.8 | 0.320 | 0.641 |
4×120+70mm2 | SM | SM | 1.6 | 1.4 | 0.5 | 2.6 | 46.6 | 0.253 | 0.443 |
4×150+70mm2 | SM | SM | 1.8 | 1.4 | 0.5 | 2.7 | 50.4 | 0.206 | 0.443 |
4×185+95mm2 | SM | SM | 2.0 | 1.6 | 0.5 | 2.9 | 55.9 | 0.164 | 0.320 |
4×240+120mm2 | SM | SM | 2.2 | 1.6 | 0.5 | 3.1 | 62.2 | 0.125 | 0.253 |
4×300+150mm2 | SM | SM | 2.4 | 1.8 | 0.5 | 3.3 | 68.4 | 0.100 | 0.206 |
Note: RE= round conductor RM = stranded conductor SM=sectional conductor